Nortek C7BA Manual Download Page 6

6

IMPORTANT NOTE:

To prevent internal oxidation and scaling from occurring, 

braze all connections with dry nitrogen flowing through 

the joints.

9. Install the grommet in the door cutout. Verify the grommet 

is evenly aligned around the tube and securely positioned 

in the door cutout.

Condensate Drain

 CAUTION:

The coil must be level to ensure proper condensate 

drainage. Improper condensate disposal may result 

in structural damage, premature equipment failure, 

or possible personal injury.

• Methods for disposing of condensate vary according 

to local codes. Refer to local codes or authority having 

jurisidiction for restrictions and proper condensate disposal 

requirements.

•  All condensate pans have primary and secondary drain 

connections to meet FHA requirements. If the application 

is located in or above a living space where damage may 

result from condensate overflow, a separate 3/4 inch drain 

must be provided from the secondary drain connection and 

a secondary drain pan must be installed under the entire 

unit. Run secondary drain lines to a place where they are 

noticeable if used.

•  The coil condensate pan is designed with 3/4” NPSC drain 

connections. Use a PVC or similar material fitting to attach 

the drain line to the pan. 

NOTE:

 The fitting should be hand 

tightened only. Overtightening may crack the drain pan 

and cause condensate to leak.

•  The drain pan MUST be drained with field supplied tubing 

or PVC pipe and adequately trapped.

IMPORTANT NOTE TO INSTALLER

Failure to install a trap may result in condensation 

overflowing the drain pan, resulting in substantial 

water damage to surrounding area.

•  Prime the trap with water. Insulate the drain if it is located 

in an unconditioned space, and test the condensate line 

for leaks. Consult local codes for additional restrictions or 

precautions.

•  Route the lines to a suitable drain, avoiding sharp bends 

and pinching of the lines. The drain should maintain a 

minimum horizontal slope in the direction of discharge of 

no less than 1” vertical for every 10 ft of horizontal run.

• During system checkout, inspect the drain line and 

connections to verify proper condensate drainage.

Air Filter

Air filters are not supplied as an integral part of this coil; 

however, an air filter kit is available. Refer to the Replacement 

Parts List for available part numbers.
The filter must be installed upstream of the coil and inspected 

frequently. When the filter becomes clogged with dust or 

lint, it should be replaced (disposable type) or cleaned 

(washable type). It is recommended that filters be inspected 

and replaced at least twice during the year. Generally it is 

best to replace or clean the filters at the start of each heating 

and cooling season.

COMPLETING THE INSTALLATION

1. Position the drain pan so the connections are aligned with 

the corresponding knockouts. 

2. Check the system for leaks, including the lineset and the 

brazed joints. 

3. Evacuate the system of moisture and non-condensables 

to prevent low efficiency operation or damage to the unit. 

The suggested range of evacuation is 350 - 500 microns.

4. Charge the system with refrigerant. 

Please Refer to the 

outdoor unit installation manual for additional charging 

instructions.

5. Install the coil access door (if removed).

6. Properly dispose of all removed parts.

7. Apply power to the unit.

MAINTENANCE & SERVICE

 WARNING:

ELECTRICAL SHOCK, FIRE OR 

EXPLOSION HAZARD

Failure to follow safety warnings exactly could result 

in serious injury or property damage.

Improper servicing could result in dangerous 

operation, serious injury, death or property 

damage.

•  Before servicing, disconnect all electrical power 

to the equipment.

•  When servicing controls, label all wires prior to 

disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

 CAUTION:

Do not operate the system without a suitable filter 

in the return air duct system. Always replace the 

filter with the same size and type.

To ensure optimum performance and to minimize possible 

equipment failure, the following maintenance tasks should 

be performed periodically on this equipment:
1. The air filter installed with the system should be checked 

and cleaned or replaced twice per year.

2. Check the coil, drain pan, and condensate drain line for 

cleanliness at the start of each heating and cooling season. 

Clean as needed.

Summary of Contents for C7BA

Page 1: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 2: ...unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not posses mechanical skills ortools callyourlocaldealerforassistance Under no circu...

Page 3: ...70A 3 920671A 3 5 920672A 4 920673A 5 Table 1 TXV Kit Part Numbers COIL INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failuretofollowsafetywarningsexactlycouldresult in serious injury...

Page 4: ...re electrical power to the furnace Downflow Installations C7 coils may be installed in downflow applications It is required that the furnace and coil cabinets are securely mounted together before sett...

Page 5: ...s NOTE If installing a TXV please follow the instructions supplied with the kit See Table 2 for kit part numbers 1 Remove the grommet from the suction line making note of its orientation and fit 2 Rem...

Page 6: ...stem checkout inspect the drain line and connections to verify proper condensate drainage Air Filter Air filters are not supplied as an integral part of this coil however anairfilterkitisavailable Ref...

Page 7: ...in 14 1 2 14 1 2 17 1 2 17 1 2 17 1 2 21 21 21 21 24 1 2 24 1 2 24 1 2 H Height in 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 30 1 4 30 1 4 30 1 4 30 1 4 30 1 4 HL Height of Liquid Line in 23 1...

Page 8: ...Coil Dimensions W HS HL H 5 8 4 17 3 4 20 3 4 FRONT VIEW TOP VIEW Distributor Thermal Expansion Valve TXV Door TXV Retaining Nut Liquid Line Stub w Screen Accessory Retaining Nut Grommet Figure 6 TXV...

Page 9: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 10: ...ant son installation son entretien et son utilisation Les personnes non qualifi es ne doivent pas tenter d interpr ter ces instructions ou d installer cet quipement Si vous ne poss dez pas les comp te...

Page 11: ...s blessures graves ou des dommages mat riels importants Un entretien inappropri peut provoquer un fonctionnement dangereux des blessures graves la mort ou des dommages mat riels Avant toute interventi...

Page 12: ...e que les armoires du la fournaise et les bo tiers de serpentins doivent tre solidement fix s ensemble avant l installation du serpentin Les applications au combustible fossile requi rent que le serpe...

Page 13: ...Tableau 2 pour les num ros de pi ces des trousses 1 Retirez le passe fils de la conduite de succion en notant son orientation et son ajustement 2 Retirez la porte d acc s au serpentin 3 Enlevez le bou...

Page 14: ...ssurerl vacuationappropri e du condensat Filtre air Les filtres air ne sont pas fournis avec ce serpentin toutefois une une trousse de filtre air est disponible Consultez la Liste des pi ces de rechan...

Page 15: ...26 75 26 75 26 75 26 75 30 25 30 25 30 25 HL Hauteur de la conduite de liquide po 17 5 17 5 17 5 17 5 17 5 17 5 23 5 23 5 23 5 23 5 27 27 27 HS Hauteur de la conduite de succion po 15 5 15 5 15 5 15...

Page 16: ...bligations 10 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved Figure 5 Dimensions du serpentin W HS HL H 5 8 4 17 3 4 20 3 4 VUE D AVANT VUE DE DESSUS Distributeur D tendeur thermostati...

Reviews: