•  Close-off plates are available in some air filter kits. Refer 

to the Replacement Parts List for available part numbers. 

Install the necessary close-off plates around the refrigerant 

lines and drain line where required.  Reinstall all inner and 

outer panels of the furnace/air handler that were previously 

removed when installing the indoor coil.

Upflow Installations

1. Disconnect all electrical power to the furnace.

2. Install the coil case on the furnace air discharge opening 

and level it as needed to ensure proper condensate 

drainage. If needed, make a plate to adapt the coil to the 

air discharge opening. See 

Figure 5 (page 8)

 for coil 

dimensions.

3. Make and install the plenum over the coil. Insulate as 

required.

4. Seal the enclosure as required to minimize air leakage.

5. Connect the refrigerant lines as outlined in the Refrigerant 

Line Connection section.

Horizontal Installations

C7 coils can be installed horizontally, but it is required that 

the furnace and coil cabinets be securely mounted together 

before setting in place. A horizontal drain pan kit must also 

be installed under the coil. Refer to 

Table 3

Table 4

, or 

Table 

5

  for available part numbers.

Horizontal Left Installations

1. Disconnect all electrical power to the furnace.

2. Remove the coil access door.

3. Remove the plug and knockout from one of the threaded 

holes in the horizontal drain pan.

 CAUTION:

The knockout must be removed and discarded 

to ensure proper condensate drainage. Improper 

drainage may result in structural damage, premature 

equipment failure, or possible personal injury.

4. Install plug (from horizontal drain pan) in the open drain 

hole in the drain pan at the bottom of the unit. This will 

block bypass air from entering the system.

5. Remove the drain line knockout from the coil access door. 

This will allow access to the horizontal drain.

6. Install drain pan extension (if supplied with unit).

TXV KIT P/N

SIZE OF A.C. OR H.P. (TONS)

R-22

REFRIGERANT

920662A

1.5 or 2

920663A

2.5

920664A

3

920665A

3.5

920666A

4

920667A

5

R-410A

REFRIGERANT

920668A

1.5 or 2

920669A

2.5

920670A

3

920671A

3.5

920672A

4

920673A

5

Table 1. TXV Kit Part Numbers

COIL INSTALLATION

 WARNING:

ELECTRICAL SHOCK, FIRE OR 

EXPLOSION HAZARD

Failure to follow safety warnings exactly could result 

in serious injury or property damage.

Improper servicing could result in dangerous 

operation, serious injury, death or property damage.
•  Before servicing, disconnect all electrical power 

to the equipment.

•  When servicing controls, label all wires prior to 

disconnecting. Reconnect wires correctly.

•  Verify proper operation after servicing.

 CAUTION:

The coil must be level to ensure proper condensate 

drainage. An unlevel installation may result in 

structural damage, premature equipment failure, 

or possible personal injury.

General Information

C7 Series indoor cased coils are designed for upflow, 

downflow, or horizontal applications and are equipped with 

braze type refrigerant connections for easy installation. If a 

TXV is not installed but required for your application, see 

Table 1

 to determine the proper kit based on tonnage and 

refrigerant type of the unit.
•  Check the coils orifice size and confirm that it’s suitable 

for application with the intended outdoor unit. Depending 

on application, additional installer supplied orifice or TXV 

may be required.

•  Optional cooling/heating equipment must be properly sized 

and installed in accordance with the furnace manufacturer’s 

specifications and approved recommendations.

•  Heating only furnace air circulators may have to be replaced 

with multi-speed heating / cooling blowers to upgrade the 

air delivery (CFM) when an add-on coil is installed. Refer to 

Table 3

Table 4

, or 

Table 5, (page 7)

 for coil specifications, 

recommended CFM, and allowances for pressure drop 

across the coil and filters.

•  Verify that the air delivery of the furnace/air handler is 

adequate to handle the static pressure drop of the coil, 

filter, and duct work.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

•  Refrigerant lines should be wrapped with pressure sensitive 

neoprene or other suitable material where they pass against 

sharply edged sheet metal.

•  Horizontal installations require a horizontal drain pan kit to 

be installed. See 

Table 3

Table 4

, or 

Table 5

 for available 

part numbers.

Summary of Contents for C7BA

Page 1: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 2: ...unit Unqualified individuals should not attempt to interpret these instructions or install this equipment If you do not posses mechanical skills ortools callyourlocaldealerforassistance Under no circu...

Page 3: ...70A 3 920671A 3 5 920672A 4 920673A 5 Table 1 TXV Kit Part Numbers COIL INSTALLATION WARNING ELECTRICAL SHOCK FIRE OR EXPLOSION HAZARD Failuretofollowsafetywarningsexactlycouldresult in serious injury...

Page 4: ...re electrical power to the furnace Downflow Installations C7 coils may be installed in downflow applications It is required that the furnace and coil cabinets are securely mounted together before sett...

Page 5: ...s NOTE If installing a TXV please follow the instructions supplied with the kit See Table 2 for kit part numbers 1 Remove the grommet from the suction line making note of its orientation and fit 2 Rem...

Page 6: ...stem checkout inspect the drain line and connections to verify proper condensate drainage Air Filter Air filters are not supplied as an integral part of this coil however anairfilterkitisavailable Ref...

Page 7: ...in 14 1 2 14 1 2 17 1 2 17 1 2 17 1 2 21 21 21 21 24 1 2 24 1 2 24 1 2 H Height in 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 26 3 4 30 1 4 30 1 4 30 1 4 30 1 4 30 1 4 HL Height of Liquid Line in 23 1...

Page 8: ...Coil Dimensions W HS HL H 5 8 4 17 3 4 20 3 4 FRONT VIEW TOP VIEW Distributor Thermal Expansion Valve TXV Door TXV Retaining Nut Liquid Line Stub w Screen Accessory Retaining Nut Grommet Figure 6 TXV...

Page 9: ...tention tous les avertissements de s curit et toute autre remarque sp ciale donn e dans le manuel L installation inappropri e de la fournaise ou le non respect des avertissements de s curit risque d e...

Page 10: ...ant son installation son entretien et son utilisation Les personnes non qualifi es ne doivent pas tenter d interpr ter ces instructions ou d installer cet quipement Si vous ne poss dez pas les comp te...

Page 11: ...s blessures graves ou des dommages mat riels importants Un entretien inappropri peut provoquer un fonctionnement dangereux des blessures graves la mort ou des dommages mat riels Avant toute interventi...

Page 12: ...e que les armoires du la fournaise et les bo tiers de serpentins doivent tre solidement fix s ensemble avant l installation du serpentin Les applications au combustible fossile requi rent que le serpe...

Page 13: ...Tableau 2 pour les num ros de pi ces des trousses 1 Retirez le passe fils de la conduite de succion en notant son orientation et son ajustement 2 Retirez la porte d acc s au serpentin 3 Enlevez le bou...

Page 14: ...ssurerl vacuationappropri e du condensat Filtre air Les filtres air ne sont pas fournis avec ce serpentin toutefois une une trousse de filtre air est disponible Consultez la Liste des pi ces de rechan...

Page 15: ...26 75 26 75 26 75 26 75 30 25 30 25 30 25 HL Hauteur de la conduite de liquide po 17 5 17 5 17 5 17 5 17 5 17 5 23 5 23 5 23 5 23 5 27 27 27 HS Hauteur de la conduite de succion po 15 5 15 5 15 5 15...

Page 16: ...bligations 10 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved Figure 5 Dimensions du serpentin W HS HL H 5 8 4 17 3 4 20 3 4 VUE D AVANT VUE DE DESSUS Distributeur D tendeur thermostati...

Reviews: