background image

7

  IMPORTANT: If the webbing is not removed, the 

condensate will not drain properly and ceiling damage 

may occur.

 

NOTE:

 It is recommended that the suction line be insulated 

up to the coil inside of the cabinet.

7. Insert the plug (from horizontal drain pan) into the open 

and unused drain hole in the drain pan at the bottom of 

the unit to block bypass air.

8. Remove the corresponding drain line knockout from the 

coil access door to allow access to the horizontal drain.

9. Replace the door and attach the drain line.

Circuit Breaker Cover Installation

The air handler circuit breaker cover is designed to protect 

the breakers of an installed heater kit from debris and 

condensation.The cover attaches to the breaker recess of 

the air handler upper access door using a double-sided 

adhesive gasket. See 

Figure 5

The heater kit circuit breaker 

toggles are still accessible and can be switched with the 

cover in place.
There are 2 different circuit breaker cover sizes:

•  2-breaker cover for 2, 2.5, 3, 3.5, & 4 ton air handlers.

•  3-breaker cover for 5 ton air handlers.
After the heater kit is properly installed, remove the 

appropriate knockouts in the upper air handler access door 

and follow these instructions to install the breaker cover:
1. Clean any oil, dirt, or insulation fibers from the recess area 

of the air handler access door. This step is important for 

ensuring the gasket adheres properly to the sheet metal 

door.

2. Remove release paper from one side of the gasket 

and attach to back side of the breaker cover. 

NOTE:

 For proper alignment, It is recommended to leave 

the center section of the gasket in place when attaching 

the gasket to the breaker cover. Remove the center section 

after the gasket is applied to the breaker cover.

3. Remove the release paper from the other side of the 

gasket and attach to the circuit breaker recess area.

4. Press firmly along all four sides of the cover to ensure 

gasket and cover are securely attached to the access 

door.

Refrigerant Line Connections

 WARNING:

NITROGEN

HEALTH

FLAMMABILITY

REACTIVITY

0 Minimal Hazard

1 Slight Hazard

1

0

0

The coil in the air handler is factory shipped with 

a nitrogen charge. Avoid direct face exposure 

or contact with valve when gas is escaping. 

Always ensure adequate ventilation is present 

during the depressurization process. Address 

any uncertainties before proceeding. Failure 

to comply with this warning could result in 

equipment damage, personal injury, or death.

• The installer should make every effort to ensure the 

field installed refrigerant containing components of the 

system have been installed in accordance with these 

instructions and sound installation practices for reliable 

system operation and longevity.

•  The air handler coil does not contain a refrigerant charge. 

Refer to the installation instructions supplied with the 

outdoor unit for refrigerant charge information.

•  The  refrigerant piping to each air handler (or coil) should 

be of equal length and size. Run the copper pipes from 

condensing unit to a point equidistant between the air 

handlers (or coils). Place a tee in the lines at this point. 

After the tee (as close to the air handler as practical), 

reduce the pipe size to match the piping of the air handler 

or coil.

•  Always refer to the installation instructions supplied with 

the outdoor unit for piping requirements. The suction 

and liquid lines must be sized in accordance with the 

condensing unit specifications. See 

Figure 8 (page 14)

 

for liquid and suction line locations.

• When connecting refrigerant linesets together, it is 

recommended that dry nitrogen be flowing through the 

joints during brazing. This will prevent internal oxidation 

and scaling from occurring.

• Refrigerant tubing should be routed in a manner that 

minimizes the length of tubing and the number of bends 

in the tubing. It should be supported in a manner that 

prevents it from vibrating or abrading during system 

operation. Tubing should be kept clean of foreign debris 

during installation.

•  If precise forming of refrigerant lines is required, a copper 

tubing bender is recommended. Avoid sharp bends and 

contact of the refrigerant lines with metal surfaces.

•  Refrigerant lines should be wrapped with pressure sensitive 

neoprene or other suitable material where they pass against 

sharp sheet metal edges.

•  B64 Series air handlers are charged (with nitrogen) through 

service valves on the end of the liquid tube for each circuit. 
These must be removed before brazing the line sets.

Circuit Breaker

Cover

Circuit

Breakers

Recess

Air Handler A

ccess Door

Figure 5. Circuit Breaker Cover

Summary of Contents for B64EM Series

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury...

Page 2: ...wer Continuously 11 Selecting Continuous Low Speed Fan Operation 11 Turning the Blower Off 11 System Cooling 11 System Heating 11 Selecting Minimum Electric Heat Airflow 11 Blower Configurations 11 De...

Page 3: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Page 5: ...needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready for vertical upflow installation a...

Page 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Page 7: ...ntact with valve when gas is escaping Always ensure adequate ventilation is present during the depressurization process Address any uncertainties before proceeding Failure to comply with this warning...

Page 8: ...ondensables to prevent low efficiency operation or damage to the unit The suggested range of evacuation is 350 500 microns 9 Charge the system with refrigerant Refer to the outdoor unitinstallationman...

Page 9: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 10: ...5 Connect blue blower limit wires according to Heater Kit Installation Instructions and the corresponding Wiring Diagram If a heater kit is not installed 1 Remove the 2 wire plug of the air handler b...

Page 11: ...n B64EM models B64VM models automatically set the heating speed based on the amount of installed heat The A B switch must be set appropriately for the unit cabinet size For C sized cabinets the A B sw...

Page 12: ...cted airflow while the system is in the lo cool mode and 100 of the selected airflow while in hi cool mode Units with an FSHE control scheme B64EM have a control board that includes a 7 segment displa...

Page 13: ...or on the blower and motor as part of the annual inspection Blower Fan Wheel Inspect the blower wheel blades for accumulations of dirt and clean if necessary Inspect mounting nut for tightness when do...

Page 14: ...typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12 3 4 No B 43 5 16 19 11 16 18 1 4 No Tall...

Page 15: ...l Drain Pan Coil Assembly Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Uppe...

Page 16: ...0 795 720 685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0...

Page 17: ...TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TON 1300 4 TON 700 2 TON 700 1350 750 750 1400 800 2 5 TON 800 2 5 TON 1450 850 850 1500 875 875 1550 890 950 1600 5 TON 930 1050 3 TON 1650 950 1150 3...

Page 18: ...ING 0 OFF 1 ON AIRFLOW CFM 5 6 7 8 0 0 0 0 1100 0 0 0 1 1200 0 0 1 0 1250 0 0 1 1 1300 0 1 0 0 1350 0 1 0 1 1400 0 1 1 0 1450 0 1 1 1 1500 1 0 0 0 1550 1 0 0 1 1600 1 0 1 0 1650 1 0 1 1 1700 1 1 0 0 1...

Page 19: ...W1 W2 EHEAT ON 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 8 KW 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Page 20: ...fter 5 seconds delay 15 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 30 seconds delay 20 KW Stage 1 Heat on instantly Co...

Page 21: ...cal Heat Pump with 2 Stage Air Handler G R W2 C O Y1 Thermostat O Y1 R C G R W E Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with 2 Stage Air Handler Typical 2 Stage Heat Pump with 2 Stage A...

Page 22: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 12 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 13 Two Stage Contro...

Page 23: ...R ECM BLOWER Figure 14 Fixed Speed Motor Control Board GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTP...

Page 24: ...entation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac ut...

Page 25: ...e tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cuivre 105 C du m me gabarit WIRING DIAGRAM CONNECT TO W1...

Page 26: ...tterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the...

Page 27: ...27...

Page 28: ...10436960 NEW Specifications illustrations subject to change without notice or incurring obligations 08 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved...

Reviews: