background image

11

  Verify the thermostat is wired correctly. Make sure all low 

voltage wires are securely connected.

 Verify the power supply branch circuit overcurrent 

protection is sized properly.

  Verify filter is properly and securely installed.

IMPORTANT:

 Before starting the unit, install the initial 

charge on units that are factory shipped with a nitrogen 

holding charge:

1. Read all installation instructions first.

2. Purge the nitrogen holding charge.

3. Evacuate the unit to 350 - 500 microns.

4. Allow the unit to remain under vacuum for at least 30 

minutes.

5. Weigh in the proper amount of new (or reclaimed) 

refrigerant. Refer to the air conditioner or heat pump  

installation manual for the proper type and quantity of 

refrigerant.

Air Circulation

Running the Blower Continuously

Set the thermostat’s system mode to 

OFF

 and the 

thermostat’s fan mode to 

ON

. The blower motor should run 

continuously. Check for air delivery at the register(s). Ensure 

that there are no obstructions at the registers or in the ducts.

Selecting Continuous Low Speed Fan Operation

(Standard Blower)

The air handler is equipped with an option of continuous low 

speed fan operation. When 

G

 is energized without 

Y/Y2

, the 

air handler will operate using the cooling speed. With 

G

 & 

Y/Y2

 or 

Y/Y2

 energized, the air handler will operate in the 

selected cooling speed (including 40 sec blower-off delay).

Turning the Blower Off

Set thermostat’s fan mode to 

AUTO

, the blower will shut 

down immediately.

System Cooling

1. Set the thermostat’s system mode to 

COOL

 and fan mode 

to 

AUTO

. Lower the thermostat’s temperature mode below 

room temperature and observe that the blower energizes. 

Check the air being discharged at the register is cooler 

than room temperature. Verify unit refrigerant pressures 

are in order. Blower should be turning in direction indicated 

by arrow.

 NOTE:

 DO NOT alter unit wiring. Listen for any unusual 

noises. Locate the source and correct as needed.

2. Allow the unit to run for several minutes and then set the 

thermostat’s temperature above room temperature. Verify 

the blower cycles off with the thermostat.

System Heating

1. Set the thermostat’s system mode to 

HEAT

 and the fan 

mode to 

AUTO

. Increase the thermostat’s temperature 

above room temperature and observe that the blower 

energizes. Check the air being discharged at the register 

is warmer than room temperature.

2. Allow the unit to run for several minutes and then set the 

thermostat’s temperature below room temperature. Verify 

the blower cycles off with the thermostat.

Selecting Minimum Electric Heat Airflow

The minimum electric heat airflow setting controls the 

minimum air flow that will be produced whenever electric 

heater kits are used. When the electric heater kit is energized 

along with a heat pump, the airflow may be higher depending 

on the basic cooling/heat-pump airflow setting. The minimum 

electric heat airflow is selected by setting switches 1, 2, 3, & 

4 on B64EM models. B64VM models automatically set the 

heating speed based on the amount of installed heat. The 

A/B switch must be set appropriately for the unit cabinet 

size. For C-sized cabinets, the A/B switch can be set in 

either position. The remaining 3 HEAT switches have no 

function. Switch settings are listed in 

Table 6, (page 16) 

or 

Table 9, (pages 19 and 20)

.

NOTES:

• For B64EM Models, the minimum electric heat airflow 

setting may be set higher, but must never be set lower 

than the setting shown in 

Table 7, (page 17)

.

•  Variable speed motor control boards do not support non-

electric heat because the heating air flow cannot be set 

independently.

Blower Configurations

Determining Nominal System Capacity

To select the appropriate airflows for the air handler, the 

nominal system capacity must be known. The nominal 

system capacity is always the nominal capacity of the 

outdoor unit. However, in some situations the nominal system 

capacity may not be the same as the nominal capacity of 

the air handler. Always refer to the nominal capacity of the 

outdoor unit to determine the nominal system capacity. Use 

Table 8, (page 18)

 as a guide for acceptable airflow CFM 

(dependent on air handler cabinet size and nominal capacity 

of the outdoor unit).

NOTE:

 The CFM values listed in 

Table 9, (pages 19 and 

20)

 are not dependent on duct static pressure. The VSHE 

motor automatically compensates for changes in duct static 
pressure (within the limits of the motor).

High Efficiency Units (Variable & Fixed Speed)

IMPORTANT! 

This air handler has been designed to give the 

installer maximum flexibility to optimize system performance, 

efficiency, and comfort. Because there are so many different 

ways to set up the air handler it is important to read and 

follow these directions carefully.
B64EM & B64VM air handlers use high efficiency circulating 

air motors that come in two variations and both are 

controlled differently. The variable speed motor control board 

(

Figure 15

controls the airflow at a constant CFM when 

paired with a separate control board. The fixed speed unit 

has a single integrated control board (

Figure 14 (page 23)

that controls the torque of the motor.
Before operation, the air handler must be configured to 

match the unit with the system, system options, and climatic 

conditions. During normal operation, the motor will gradually 

change speeds during start-up, shut down, when thermostat 

inputs change, and when the duct static pressure changes 

(vents closed or opened, filter clogging, etc.). The air handler 

is configured by setting the selector switches and removing 

jumper connectors.

Basic Heating Airflow for Variable & Fixed Speed

Fixed & variable speed motor control boards (

Figure 14 

Figure 15 (page 23)

) contain a set of dip switches for setting 

the blower speed. For B64EM models, pins 1-4 set the 

speed for heating. For B64VM models, the A/B switch must 

be set for the appropriate cabinet size (either setting can be 

used for C-size cabinets). The airflow is set automatically 

based on the amount of installed heat. To determine 

the appropriate switch settings for your installation, see 

Table 6, (page 16)

or 

Table 9, (pages 19 and 20)

.

Summary of Contents for B64EM Series

Page 1: ...well Pay attention to all safety warnings and any other special notes highlighted in the manual Improper installation of the furnace or failure to follow safety warnings could result in serious injury...

Page 2: ...wer Continuously 11 Selecting Continuous Low Speed Fan Operation 11 Turning the Blower Off 11 System Cooling 11 System Heating 11 Selecting Minimum Electric Heat Airflow 11 Blower Configurations 11 De...

Page 3: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 4: ...ment Refer to applicable building codes for details Static pressure drop through louvered openings and through return air plenums should be considered in the overallductdesigninthedeterminationoftheto...

Page 5: ...needed gaskets and grommets around penetrations into the air handler such as for electrical wiring AIR HANDLER INSTALLATION B64 series air handlers are shipped ready for vertical upflow installation a...

Page 6: ...Right Installations 1 Remove the coil access door Unscrew the line set tube close off plate from the front left cabinet rail 2 Slide the coil and drain pan assembly out of the unit 3 Remove the sheet...

Page 7: ...ntact with valve when gas is escaping Always ensure adequate ventilation is present during the depressurization process Address any uncertainties before proceeding Failure to comply with this warning...

Page 8: ...ondensables to prevent low efficiency operation or damage to the unit The suggested range of evacuation is 350 500 microns 9 Charge the system with refrigerant Refer to the outdoor unitinstallationman...

Page 9: ...ation service and operation of this unit Unqualified individuals should not attempt to interpret these instructions or install this equipment Failure to follow safety recommendations could result in p...

Page 10: ...5 Connect blue blower limit wires according to Heater Kit Installation Instructions and the corresponding Wiring Diagram If a heater kit is not installed 1 Remove the 2 wire plug of the air handler b...

Page 11: ...n B64EM models B64VM models automatically set the heating speed based on the amount of installed heat The A B switch must be set appropriately for the unit cabinet size For C sized cabinets the A B sw...

Page 12: ...cted airflow while the system is in the lo cool mode and 100 of the selected airflow while in hi cool mode Units with an FSHE control scheme B64EM have a control board that includes a 7 segment displa...

Page 13: ...or on the blower and motor as part of the annual inspection Blower Fan Wheel Inspect the blower wheel blades for accumulations of dirt and clean if necessary Inspect mounting nut for tightness when do...

Page 14: ...typ 13 4 K O typ 1 7 8 3 5 8 5 5 8 DETAIL D 3 1 4 2 1 4 15 1 4 13 SUCTION LIQUID W 1 1 8 1 7 8 7 8 K O H 22 A CABINET SIZE H W A DETAIL D A 43 5 16 14 3 16 12 3 4 No B 43 5 16 19 11 16 18 1 4 No Tall...

Page 15: ...l Drain Pan Coil Assembly Motor Mount Kit Blower Motor Transformer Capacitor Circuit Breaker 60A Heating Element Assembly Filter Tracks Blower Wheel Blower Housing Motor Control Board Filter Door Uppe...

Page 16: ...0 795 720 685 0 1 1 0 1095 1040 995 950 900 850 805 750 1 1 1 0 1155 1105 1060 1010 965 920 870 825 0 0 0 1 1230 1185 1140 1090 1045 1010 965 920 1 0 0 1 1285 1260 1210 1165 1125 1080 1040 1010 0 1 0...

Page 17: ...TON 560 560 1200 3 5 TON 600 600 1250 625 650 2 TON 1300 4 TON 700 2 TON 700 1350 750 750 1400 800 2 5 TON 800 2 5 TON 1450 850 850 1500 875 875 1550 890 950 1600 5 TON 930 1050 3 TON 1650 950 1150 3...

Page 18: ...ING 0 OFF 1 ON AIRFLOW CFM 5 6 7 8 0 0 0 0 1100 0 0 0 1 1200 0 0 1 0 1250 0 0 1 1 1300 0 1 0 0 1350 0 1 0 1 1400 0 1 1 0 1450 0 1 1 1 1500 1 0 0 0 1550 1 0 0 1 1600 1 0 1 0 1650 1 0 1 1 1700 1 1 0 0 1...

Page 19: ...W1 W2 EHEAT ON 5 KW Stage 1 Heat on instantly Heat blower on after 3 second delay 8 KW 10 KW Stage 1 Heat on instantly Heat blower on after 3 second delay Stage 2 Heat on after 5 seconds delay 15 KW...

Page 20: ...fter 5 seconds delay 15 KW Stage 1 Heat on instantly Cool blower on after 3 second delay Stage 2 Heat on after 5 seconds delay Stage 3 Heat on after 30 seconds delay 20 KW Stage 1 Heat on instantly Co...

Page 21: ...cal Heat Pump with 2 Stage Air Handler G R W2 C O Y1 Thermostat O Y1 R C G R W E Thermostat Y1 C Y1 W2 Typical 2 Stage Air Conditioner with 2 Stage Air Handler Typical 2 Stage Heat Pump with 2 Stage A...

Page 22: ...1 BLWDTC BLWDTC_R HEAT COOL EAC L 1 L 2 P2 R C G W Y 3A Fuse HEATER P1 Figure 12 Single Stage Control Board C R G Y2 Y O 1W 2W 1Y L LED 1 HEATER P1 L 2 HUM EAC P2 3A Fuse P3 Figure 13 Two Stage Contro...

Page 23: ...R ECM BLOWER Figure 14 Fixed Speed Motor Control Board GND SENSOR DEHUM Y1 H L2 OUT L2 IN L1 IN L1 OUT Y1 Y Y2 W C EXPANSION PORT R RED GREEN TEST PORT BLOWER MOTOR RED INPUTS COOL HEAT FAN SPEED OUTP...

Page 24: ...entation avant l entretien 3 Le transformateur peut avoir un robinet principal double tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac ut...

Page 25: ...e tension Agencez la position du robinet au type de tension de l installation 4 Si le c blage interne est remplac utilisez seulement un fil de cuivre 105 C du m me gabarit WIRING DIAGRAM CONNECT TO W1...

Page 26: ...tterthanyourcustomer This includes being able to install the product according to strict safety guidelines and instructing the customer on how to operate and maintain the equipment for the life of the...

Page 27: ...27...

Page 28: ...10436960 NEW Specifications illustrations subject to change without notice or incurring obligations 08 22 O Fallon MO Nortek Global HVAC LLC 2022 All Rights Reserved...

Reviews: