EasyGrid User Guide
71
10
Digital Communication Protocol
Nortech EasyGrid supports multiple digital communication ports. For each protocol the Ethernet
communication switch needs to be in a specific position and only the specified port can be used. Use the
following table for the required configuration for each protocol.
Protocol
Standard/ Optional
Communication Switch Position
Port to use
Nortech
Standard
RS-485/422
MODBUS
Standard
RS-485/422
IEC 61850
Optional
Ethernet
IEC 60870-5-104
Optional
Ethernet
DNP 3.0
Optional
Ethernet
10.1
Nortech
Your configuration for communication protocol should be set to “Nortech”.
The Nortech Client application exchanges configuration and monitoring information with the EasyGrid
using the Nortech protocol.
If you intend to connect multiple units to a RS-485 bus, a unique network address must be set to each
unit before installation. Otherwise, you will have to go to each unit location with a portable computer
and configure its network address on-site. The Nortech network address is configured through the
Nortech Client software.
In order for the multiple EasyGrids to work on the same serial bus, each unit must:
Be connected to the other units through the RS-485 interface.
Have a unique Nortech address.
Summary of Contents for EasyGrid V1
Page 1: ...EasyGrid User Guide i Nortech EasyGrid User Guide MAN 00084 R 10 0 ...
Page 24: ...EasyGrid User Guide 19 6 Hardware Configuration 6 1 Dimensions ...
Page 97: ...EasyGrid User Guide 92 11 3 Assembly Diagram ...
Page 99: ...EasyGrid User Guide 94 11 4 1 2 Pre Drilling 11 4 1 3 Using the Knockout Punch ...
Page 100: ...EasyGrid User Guide 95 11 4 1 4 Cutting the Cable Slot 11 4 1 5 Inserting the Easy Disk ...