Here are the formulas for the Analog Output.
The Analog Output is represented by a straight line equation of this form:
Formula
( )
( )
( )
( )
(
( ))
(
( )
)
Parameter
Symbol
Set Min T°
AnaOutMin °C
Set Max T°
AnaOutMax °C
°C / mA
m
I (mA)
x
T°
y
All channels share the same original, factory-set, configuration: the scale factor is 16.56 °C/mA.
This setting results in the 0 °C offset to be at 6.41 mA, the minimum 4 mA scale limit to be at -40 °C and
the maximum 20 mA scale limit to be at 225 °C.
For example, as for channel 1 in the Analog Output screen shoots below; if the loop reads 7.69 mA, the
corresponding temperature for that channel is then 21.19 °C:
(7.69 mA
–
6.41mA) × 16.56 °C/mA = 21.19 °C.