29
| HP Series Installation Manual
Installation of Mounting Channels
Before installing the mounting channel or channels the starting mounting point needs to be
determinedusing the duct width. If the duct width is 4ft or less then there is no need for a
mounting channel, continue to the next step.
Table 1. Mounting Channel Locations
Duct Width
Mounting Position
Number of Channels
4ft - 8ft
Middle
1
8ft - 12ft
Offset 2ft from middle
2
12ft - 16ft
Middle
3
16ft - 20ft
Offset 2ft from middle
4
Once the mounting location is determined the mounting channel(s) are ready to be cut to fit,
keeping in mind that drain pans are not level and lengths may vary. From the starting point,
each additional mounting channel is placed at 4ft centers. In the figure below a typical 4ft x 8ft
installation is shown with the mounting angle surrounding the perimeter and a mounting
channel installed vertically at the center point of the duct.
In Figure 23: Large Duct Mounting Channel Locations, a 6ft high x 10ft wide mist eliminator
frame is shown. Notice how the mounting channel placement is offset from the center.
Installations between 8ft x 12ft to 16ft x 20ft may involve the removal of excess material.
Excess material is removed equally from both sides of the frame not from the middle.
To secure the mounting channel in place use the factory supplied ½ inch self-threading screws.
Use the center row of slotted holes to attach the mounting channel to the mounting angle.
Place one screw at the top and one at the bottom making sure that the mounting channel is
level or square to the ceiling, this will help for mounting the wire mesh. See Figure 24:
Mounting Channel Installation.
If the duct height greater than 8 feet a channel extension is needed in order to link 2 mounting
channels together. The extension slides inside the mounting channel. Use 4 ½ inch factory
supplied screws for each mounting channel as shown in Figure 25: Mounting Channel Extension
Kit.
Summary of Contents for HP Series
Page 7: ...HP Series Installation Manual 4 Figure 1 Typical Installation with Medium Pump ...
Page 8: ...5 HP Series Installation Manual Figure 2 Typical Installation with Large Pump ...
Page 10: ...7 HP Series Installation Manual Installation ...
Page 15: ...HP Series Installation Manual 12 Figure 3 Medium Pump Module Installation Drawing ...
Page 16: ...13 HP Series Installation Manual Figure 4 Large Pump Module Installation Drawing ...
Page 24: ...21 HP Series Installation Manual Figure 15 Typical Valve Block Assembly ...
Page 29: ...HP Series Installation Manual 26 Figure 17 Valve Coils Figure 18 Valve Wiring ...
Page 36: ...33 HP Series Installation Manual ...
Page 37: ...HP Series Installation Manual 34 Startup Operation Maintenance ...
Page 49: ...Troubleshooting 46 Troubleshooting ...
Page 52: ...49 Troubleshooting ...
Page 53: ...Spare Parts 50 Spare Parts ...
Page 61: ...Spare Parts 58 Figure 37 3 and 6 Stage Valve Assembly Spare Parts ...
Page 62: ...59 Spare Parts ...
Page 63: ...Wiring Diagrams 60 Wiring Installation Diagrams ...
Page 64: ...61 Wiring Diagrams Figure 38 Pump Control ...
Page 66: ...63 Wiring Diagrams Figure 40 Pump Controller with Danfoss Integrated VFD ...
Page 67: ...Wiring Diagrams 64 Figure 41 1 Stage Valve Controller ...
Page 68: ...65 Wiring Diagrams Figure 42 3 Stage Valve Controller ...
Page 69: ...Wiring Diagrams 66 Figure 43 6 Stage Valve Controller ...
Page 73: ...Wiring Diagrams 70 Figure 47 HP Valve Controller April 9 2010 ...
Page 74: ...71 Wiring Diagrams ...