| HP Series Installation Manual
Pump Controller Wiring Notes
Connections to Nortec Valve Controller
The pump controller can accept control input from many different valve controllers at once. This
is useful for cases when a single large pump skid is used to supply high-pressure water to
different zones / manifold groups. For example, 1 large pump skid supplies water to 3 different
air-handlers, each with their own manifolds, valves, and valve controller.
If there are more than 4 valve controllers, additional controllers can be added by doubling up
wires on the pump controller terminal strip. For example; valve controller 5 would share
terminals 1 and 5 with valve controller 1.
Connections to Valve Controllers by Others
Non-Nortec valve controllers can be used with the HP HVAC system. In these cases the valve
controller is wired to the pump controller, as it would be with a Nortec valve controller. The
valve controller need only close the loop, and does not need to provide a voltage or current. If
the valve controller does provide a signal, it should be wired to a relay which will then close the
pump controller loop.
Remote Monitoring
The pump controller terminal strip features several sets of dry contacts to allow for connections
to a building management system, status lights, or other types of equipment. They are
controlled by a relay and activated under certain conditions. Wire gauge is determined by the
equipment to be using the contacts. Refer to the manufacturers recommendations.
On (Terminals 10 and 11): Closed when the HP HVAC system is powered on and ready.
Active (Terminals 12 and 13): Closed when the HP HVAC system is humidifying.
Service (Terminals 14 and 15): Closed when the HP HVAC system requires regular
maintenance. (See Chapter X for service information.)
Fault (Terminals 16, 17 and 18): Terminal 16 is normally open and closes when an operation
fault occurs. Terminal 18 is normally closed and opens when an operational fault occurs.
Terminal 17 is a common terminal for both cases.
Summary of Contents for HP Series
Page 7: ...HP Series Installation Manual 4 Figure 1 Typical Installation with Medium Pump ...
Page 8: ...5 HP Series Installation Manual Figure 2 Typical Installation with Large Pump ...
Page 10: ...7 HP Series Installation Manual Installation ...
Page 15: ...HP Series Installation Manual 12 Figure 3 Medium Pump Module Installation Drawing ...
Page 16: ...13 HP Series Installation Manual Figure 4 Large Pump Module Installation Drawing ...
Page 24: ...21 HP Series Installation Manual Figure 15 Typical Valve Block Assembly ...
Page 29: ...HP Series Installation Manual 26 Figure 17 Valve Coils Figure 18 Valve Wiring ...
Page 36: ...33 HP Series Installation Manual ...
Page 37: ...HP Series Installation Manual 34 Startup Operation Maintenance ...
Page 49: ...Troubleshooting 46 Troubleshooting ...
Page 52: ...49 Troubleshooting ...
Page 53: ...Spare Parts 50 Spare Parts ...
Page 61: ...Spare Parts 58 Figure 37 3 and 6 Stage Valve Assembly Spare Parts ...
Page 62: ...59 Spare Parts ...
Page 63: ...Wiring Diagrams 60 Wiring Installation Diagrams ...
Page 64: ...61 Wiring Diagrams Figure 38 Pump Control ...
Page 66: ...63 Wiring Diagrams Figure 40 Pump Controller with Danfoss Integrated VFD ...
Page 67: ...Wiring Diagrams 64 Figure 41 1 Stage Valve Controller ...
Page 68: ...65 Wiring Diagrams Figure 42 3 Stage Valve Controller ...
Page 69: ...Wiring Diagrams 66 Figure 43 6 Stage Valve Controller ...
Page 73: ...Wiring Diagrams 70 Figure 47 HP Valve Controller April 9 2010 ...
Page 74: ...71 Wiring Diagrams ...