OM-IO-Link Master.038
01/21
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All firmware and electronic files are provided by ifm.
IOLD proxy modules
Port Parameter
Digital Input
Digital Input
without PD
Digital Output
Digital Output
without PD
IO-Link Input
+ PQI
IO-Link Output
+ PQI
IO-Link Input +
PQI
Fail Safe Mode
-
-
X
X
-
X
X
Pattern Value
-
-
-
-
-
X
X
Enable Port Diagnosis
X
X
X
X
X
X
X
Enable Process Alarm
X
X
X
X
X
X
X
Port Configuration without Tool
-
-
-
-
X
X
X
Enable Pull/Plug
-
-
-
-
X
X
X
Port Mode
-
-
-
-
X
X
X
Validation / Data Storage
-
-
-
-
X
X
X
Vendor ID (VID)
-
-
-
-
X
X
X
Device ID (DID)
-
-
-
-
X
X
X
Port Cycle Time
-
-
-
-
X
X
X
The different IOLD proxy modules have specific parameter sets.
IO-Link Ports: Parameter setting
X ... Parameter available
Details about the parameters of the IOLD proxy modules:
→
Parameters of the IOLD proxy modules
(→ S. 65)
To set the parameters of an IOLD proxy module:
> The operating mode and the process data of the port are set.
> Detailed view [Device overview] is opened.
‣
In [Device overview]: Select the slot of the port.
> the window [Properties] > [General] shows information via the port module.
‣
Select the menu item [Module parameters].
> The detailed view shows the current settings of the module parameters.
‣
Set the parameters as required.
‣
Save the project.