OM-IO-Link Master.024
01/21
IO Link Master - PROFINET
NC-MP-4A4B-12DLA/AL1403
This device is “powered by ifm”. In all electronic interfaces, this device will
appear as AL1403. All firmware and electronic files are provided by ifm.
9.1.4. IoT: Configure the interface to LR AGENT or LR SMARTOBSERVER
9.1.5. Fieldbus: Configure IP settings
To enable transfer of process data from the IO-Link master to LR AGENT or LR
SMARTOBSERVER, the interface has to be configured accordingly.
‣
Select [IoT] menu.
> The menu page shows the current settings.
‣
Set the following parameters as required:
To be able to access the IO-Link master from the PROFINET network or with the LR DEVICE parameter
setting software, the IP settings of the PROFINET interface must be adapted correspondingly.
‣
Select [Fieldbus] menu.
> The menu page shows the current settings.
‣
Set the following parameters as required:
Name
Description
Possible values
[IP address LR Agent or SMARTOBSERVER] IP address of LR AGENT or LR SMARTOBSERVER
Factory setting: 255.255.255.255
[Port LR Agent or SMARTOBSERVER]
Port number that is used to send process data to LR AGENT or LR
SMARTOBSERVER
0 ... 65535
Factory setting: 35100
[Interval LR Agent or SMARTOBSERVER]
Cycle time for the transfer of the process data to LR AGENT or LR
SMARTOBSERVER (value in milliseconds)
[Off]
no transfer
500 ... 2147483647
500 ms ... 2147483647 ms
[Application Tag]
Source identifier of the IO-Link master in the structure of LR AGENT or
LR SMARTOBSERVER (String32)
Factory setting: NC-MP-4A4B-12DLA/AL1403
Name
Description
Possible values
[IP address]
IP address of the PROFINET interface
Factory setting: 0.0.0.0
[Subnet mask]
Subnet mask of the PROFINET network
Factory setting: 0.0.0.0
[Default gateway IP address]
IP address of the PROFINET gateway
Factory setting: 0.0.0.0
[MAC address]
MAC address of the IO-Link master
The value is firmly set.
[Fieldbus firmware]
After changing the parameter [Port LR Agent or SMARTOBSERVER] or [Application Tag],
it may take 120 seconds before the device establishes a new TCP connection.
To prevent the delay:
‣
Reboot the device after changing the parameter.
‣
Save changed values on the device.
‣
Save changed values on the device.