9.1.3. IoT: Configure access rights
The access rights define which instance may read and / or write the parameter
data, process data and event/diagnostic messages.
In order to configure the access rights to the IO-Link master:
‣
Select [IoT] menu.
> The menu page shows the current settings.
‣
Set the following parameters as required:
‣
Save changed values on the device.
* ... Factory setting
Name
Description
Possible values
[Access Rights] The access rights to the parameter data,
process data and the event/diagnostic
messages of the IO-Link master as well
as the connected IO-Link devices
[PR IoT]*
• PROFINET and IoT Core have read and write access rights to parameters and process
data
• PROFINET and <IoT Core> have read access rights to events/alarms
[PR IoT
(read-only)]
• PROFINET has read and write access rights to parameters and process data
• PROFINET has read access rights to events/alarms
• IoT Core only has read access rights to parameters, process data and events/alarms
[IoT only]
• IoT Core has read and write access rights to parameters and process data
• IoT has read access rights to events/alarms
• PROFINET has no access rights
If in LR DEVICE and PROFINET projection software the parameter [Access Rights] is = [PROFINET
+ IoT], the parameter values set in the PROFINET projection software will always apply.
If the parameter [Access Rights] = [IoT only] in LR DEVICE, set the parameter [Access Rights]
= [Keep settings] in the projection software.
Changes of the parameter [Access Rights] will only be effective after restarting
the IO-Link master (→ Firmware:
Reboot the device
(→ S. 33)).