background image

21

3.

Measure the time (in seconds) required for
the gas meter to complete one revolution.

4.

Convert the time per revolution to cubic
feet of gas per hour using Table 10.

5.

Multiply the gas flow rate in cubic feet per
hour by the heating value of the gas in Btu
per cubic foot to obtain the firing rate in Btu
per hour.  Example:

• Time for 1 revolution of a gas meter with

a 1 cubic  foot dial = 40 seconds.

• From Table 10 read 90 cubic feet per

hour of gas.

• Heating value of the gas (obtained from

gas   supplier) = 1040 Btu per cubic foot.

• Firing rate = 1040 x 90 = 93,600 Btuh.

6.

Adjustments to the firing rate can be made
by adjusting the gas manifold pressure.
See the High Altitude Application  section
for additional information of firing rate at
elevations above 2000 ft.

The manifold pressure must be set to the
appropriate value for your installation.  Refer to
either Table 5 for natural gas or Table 6 for LP/
propane gas to verify the manifold pressure
setting required for your particular installation.
To adjust the manifold pressure, remove the
regulator cap and turn the adjusting screw
clockwise to increase pressure or counter-
clockwise to reduce pressure.  Replace the
regulator cap after adjustments are complete.

Verifying and Adjusting Temperature Rise
Verify  the temperature rise through the furnace
is within the range specified on the furnace rating
plate. Temperature rises outside the specified
range could result in premature heat exchanger
failure and/or cycling on limit switch.

Place thermometers in the return and supply air
stream as close to the furnace as possible.  The
thermometer on the supply air side must be
shielded from direct radiation from the heat
exchanger to avoid false  readings. Adjust all
registers and duct dampers  to  the  desired
position   and  run  the furnace for ten to fifteen
minutes before taking any temperature readings.
The temperature rise is the difference between
the supply and return air temperatures.

For typical duct systems, the temperature rise
will fall within the range specified on the rating
plate with the blower speed at the factory

recommended setting.  If the temperature rise
measured is outside the range specified, it may
be necessary to change the blower speed.
Lower blower speeds will increase the
temperature rise and higher blower speeds will
decrease the temperature rise.

The furnace is equipped with a multi-speed
motor.  Heating and cooling speed selection is
made by moving the leads on the integrated
control located in the furnace.  The wiring diagram
on the furnace and Figures 12, 13  and 14 show
the speed taps for adjusting motor speed.

If it is desired that the blower operate at the same
unused speed for heating and cooling, move
blower leads to M1, M2, and/or M3 and install the
jumper wire found in the plastic instruction bag.
Remove the desired blower tap, and install the
jumper wire piggyback to the heating speed tap,
and straight quick connect to the cooling speed
tap. Reconnect the desired blower tap to
piggyback quick connect.

The integrated control  is factory set to start the
circulating air blower 30 seconds after the gas
valve is opened.  The integrated control is
factory wired to turn the blower motor off 120
seconds after the gas valve is closed.  If
necessary for comfort, the “off” time may be
changed by adjusting the Blower Off jumper on
the integrated control.  See Figure 12 or 13 for
blower on and off time adjustments.

!

 WARNING:

To avoid electric shock, personal injury,
or death, disconnect the electric power
before performing any maintenance.

Verifying Burner Operation
To verify operation of the burners, make sure
that the furnace door is in place and that there
is power to the furnace.  Set the thermostat to a
temperature above room temperature and
observe the ignition sequence. The burner flame
should carry over immediately between all
burners. The flames should be blue, without
yellow tips.  Flames should extend from each
burner without lifting off, curling, or floating.
After verifying satisfactory flame characteristics,
set the thermostat to a temperature below room
temperature and verify that the burner flame
extinguishes completely.

Summary of Contents for RA 80+ series

Page 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Page 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Page 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Page 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Page 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Page 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Page 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Page 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Page 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Page 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Page 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Page 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Page 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Page 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Page 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Page 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Page 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Page 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Page 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Page 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Page 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Page 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Page 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Page 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Page 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Page 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Page 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Reviews: