18
Low Voltage Wiring
Install the thermostat per the manufacturer’s
instructions. The low voltage (24 volt)
connections from the thermostat are made at
the terminal strip on the integrated control in the
furnace. See Figure 11 for the proper
connections for heating only (two-wire) and
heating/cooling (four-wire) applications. The
recommended minimum wire gauge for
thermostat wiring is shown in Table 9.
The thermostat must not be installed on an
outside wall or any other location where its
operation may be adversely affected. Adverse
affects include radiant loading from fireplaces,
sunlight, or lighting fixtures, and convective loading
from warm air registers or electrical appliances.
To determine the heat anticipator setting either:
1.
Add the current draw of the system
components; or
2.
Measure the current flow on the thermostat
R-W circuit after the circulating blower
motor has started.
Set the heat anticipator according to the
thermostat manufacturer’s instructions for heat
anticipator settings.
START-UP AND ADJUSTMENTS
General
Prior to start-up, verify that:
1.
The line voltage power leads are securely
connected, that the polarity of the
connections is correct, and that the furnace
is properly grounded.
2.
The thermostat wires (R, W, Y, and G) are
securely connected to the correct leads on
the terminal strip of the circuit board.
3.
The gas line service pressure does not
exceed 10.0 in. water column (0.36 psig),
and is not less than 4.5 in. water column
(0.16 psig) for natural gas. For LP gas the
line service pressure must not exceed 14
in. water column (0.51 psig), and must not
be less than 11.0 in. w.c. (0.40 psig).
4.
The roll-out manual reset switch is closed.
If necessary, press the red button to reset
a switch. DO NOT install a jumper wire
across a switch to defeat its function. If
a switch reopens on start-up, DO NOT
reset the switch without identifying and
correcting the fault condition which caused
the switch to trip.
TIME FOR
TIME FOR
ONE REVOLUTION
ONE REVOLUTION
(SECONDS)
1
5
10
(SECONDS)
1
5
10
10
360
1800
3600
66
55
273
545
12
300
1500
3000
68
53
265
529
14
257
1286
2571
70
51
257
514
16
225
1125
2250
72
50
250
500
18
200
1000
2000
74
49
243
486
20
180
900
1800
76
47
237
474
22
164
818
1636
78
46
231
462
24
150
750
1500
80
45
225
450
26
138
692
1385
82
44
220
439
28
129
643
1286
84
43
214
429
30
120
600
1200
86
42
209
419
32
113
563
1125
88
41
205
409
34
106
529
1059
90
40
200
400
36
100
500
1000
92
39
196
391
38
95
474
947
94
38
191
383
40
90
450
900
96
38
188
375
42
86
429
857
98
37
184
367
44
82
409
818
100
36
180
360
46
78
391
783
102
35
176
353
48
75
375
750
104
35
173
346
50
72
360
720
106
34
170
340
52
69
346
692
108
33
167
333
54
67
333
667
110
33
164
327
56
64
321
643
112
32
161
321
58
62
310
621
114
32
158
316
60
60
300
600
116
31
155
310
62
58
290
581
118
31
153
305
64
56
281
563
120
30
150
300
GAS FLOW RATE (CUBIC FEET PER HOUR)
CUBIC FEET PER REVOLUTION OF
METER
CUBIC FEET PER REVOLUTION OF
METER
Table 10. Gas Flow Rate