background image

27

W   G   Y   R

Thermostat

A/C
Unit

Twin 
Terminal

R

C

Y

G

W

R

C

Y

G

W

Twin 
Terminal

Figure 15. Twinning

4.

The circulating air blower is de-energized
after a 90-second delay.

Fan Mode:

1.

On a call for fan operation, the thermostat
applies 24 VAC to the G terminal on the
furnace control board.

2.

The circulating air blower is energized
immediately on the heating speed.

3.

If the furnace is operated in the continuous
ON position at the thermostat and is then
switched to AUTO, the circulating blower
will operate for a specified delay (factory
set at 120 seconds).

Furnace Fails to Operate

If the furnace does not operate check the
following:

1.

Is the thermostat operating properly?

2.

Is the blower compartment door in place?

3.

Is the furnace disconnect closed?

4.

Has the circuit breaker tripped or the control
board  fuse burned open?

5.

Is the gas turned on?

6.

Are any manual reset switches open?

7.

Is the filter dirty or plugged?

8.

Is the flame sensor coated? (Remove and
clean with steel wool.)

If the furnace locks out after 5 attempts for
ignition, it will try again every hour if a call for
heat remains. If the inducer and circulating air
blowers are operating, and items 1 through 8
have been checked, press the red reset button
on the burner roll-out switches (See Figure 14).
If the furnace operates after depressing either
reset button, contact a qualified serviceman to
identify and repair the problem.

If the furnace continues to not operate, depress
the red reset buttons on the flame roll-out
switches. (See Figure 14.) If the furnace oper-
ates after depressing the reset buttons, contact
a qualified servicemen to identify and repair the
problem.

Twinning
The control board on these furnaces is capable
of being twinned to another furnace of the same
series or a G series furnace with a UTEC control
board. If using UTEC control boards, leave the
fuses installed on each board.  The thermostat
wires and the 3/16 inch quick-connect terminals
marked “TWIN”  on the furnace controls must
be wired for twinning. (See Figure 15.)

Summary of Contents for RA 80+ series

Page 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Page 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Page 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Page 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Page 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Page 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Page 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Page 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Page 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Page 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Page 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Page 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Page 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Page 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Page 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Page 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Page 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Page 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Page 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Page 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Page 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Page 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Page 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Page 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Page 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Page 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Page 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Reviews: