background image

10

designed to burn solid fuel. If the furnace vent is
to be connected to a chimney serving a fireplace,
the fireplace must be sealed off from the chimney.

Single wall metal vents shall not be used for
Category I venting. Category I furnaces
must be vented vertically or near vertically.

For Category I furnace installations, the furnace
shall be connected to a factory built chimney or
vent complying with a recognized standard, or
a masonry or concrete chimney lined with a
lining material acceptable to the authority having
jurisdiction. Venting into an unlined masonry
chimney or concrete chimney is prohibited.

The furnace vent, if metal, may be insulated if
local codes allow.  Any part of the vent system,
metal vent only, not exposed to weather, but
which are exposed to ambient temperatures
below 35° F must be insulated to prevent
condensation.  All vent insulation shall be foil
backed fiberglass of one inch minimum
thickness.

Three sheet metal fasteners (field supplied)
should be used to secure the vent pipe to the
furnace flue.  These fasteners should be evenly
spaced around the flue diameter, if possible.

Combustion Air Quality
The recommended source of combustion air is
to use the outdoor air supply. However, the use
of indoor air in most applications is acceptable
except as follows:

1. If the furnace is installed in a confined

space it is recommended that the necessary
combustion air come from the outdoors by
way of attic, crawl space, air duct, or direct
opening.

2. If outdoor combustion air is used, there

must be no exposure to the installations or
substances listed in Item 3 below.

3. The following types of installation may

require Outdoor Air for combustion, due
to chemical exposures:

• Commercial buildings
• Buildings with indoor pools
• Furnaces installed in laundry rooms
• Furnaces installed in hobby or craft

rooms

• Furnaces installed near chemical storage

areas

Exposure to the following substances in
the combustion air supply may also require
Outdoor Air for combustion:

• Permanent wave solutions
• Chlorinated waxes and cleaners
• Chlorine based swimming pool

chemicals

• Water softening chemicals
• De-icing salts or chemicals
• Carbon tetrachloride
• Halogen type refrigerants
• Cleaning solvents (such as

perchloroethylene)

• Printing inks, paint removers, varnishes,

etc.

• Hydrochloric acid
• Cements and glues
• Antistatic fabric softeners for clothes

dryers

• Masonry acid washing materials

Category I - Common Venting

When an existing furnace is removed from a
venting system serving other appliances, the
venting system is likely to be too large to properly
vent the remaining appliances. An improperly
sized venting system can result in the formation
of condensate, leakage, spillage, etc.

The venting system should be designed to have
the minimum number of elbows or turns.  All
horizontal runs  shall  be  sloped  upwards  from
the furnace at 1/4 inch per running foot of vent.
Supports for the vent pipe must be installed a
minimum of every five feet along the vent run to
ensure no displacement after installation.

Under no circumstances shall any portion of the
vent system extend into or pass through any
return air duct, supply air duct, or plenum.

If the furnace is operated with blocked or restricted
venting, the burner roll-out limit switch will open,
turning off the gas supply to the burners.  The roll-
out limit switch is a manually reset device.  DO
NOT install a jumper wire across this switch to
defeat its function.  DO NOT reset the switch
without identifying and correcting the fault
condition which caused the switch to trip.  If this
switch must be replaced, use only factory-
approved replacement parts.

!

 WARNING:

Upon completion of the furnace
installation, carefully inspect the entire
flue system both inside and outside the
furnace to assure it is properly sealed.
Leaks in the flue system can result in
serious personal injury or death due to
exposure of flue products, including
carbon monoxide.

Summary of Contents for RA 80+ series

Page 1: ...property damage personal injury or death Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Donottrytolightan...

Page 2: ...ication 15 Pressure Switch Conversion for High Altitude Applications 15 Natural Gas High Altitude Conversion 15 LP Propane Gas Sea Level and High Altitude Conversion 15 Electrical Wiring 16 General 16...

Page 3: ...s as specified on Page 14 of these instructions 6 Always install furnace to operate within the furnace s intended temperature rise range with a duct system which has an external static pressure within...

Page 4: ...52 1240 54 1175 57 1210 55 1195 55 1180 56 1160 57 1135 59 1100 60 1060 63 1010 66 2375 28 2320 29 2280 30 2215 30 2150 31 2085 32 2015 33 1940 34 1975 33 1955 34 1920 35 1895 35 1850 36 1800 37 1740...

Page 5: ...acetobemovedtotheinstallation point The furnace must be installed so that all electrical components are protected from water The furnace must be installed upstream from a refrigeration system This fur...

Page 6: ...a Platform Upflow and Horizontal Furnaces UPFLOWAPPLICATION RIGHT SIDE BOTTOM TOP LEFT SIDE TOP BOTTOM SIDE SIDE HORIZONTAL APPLICATION Allow 24 minimum clearance for servicing Therecommendedclearanc...

Page 7: ...forB ventusethe recommended clearance Do not place combustiblematerials includinggasoline and any other flammable vapors and liquids in the vicinity of the furnace requirements ForCanadianinstallatio...

Page 8: ...y to provide outside air to ensure adequate combustion and venting even though the furnace is located in an unconfined space Installation In A Confined Space A confined space is an area with volume le...

Page 9: ...per 2 000 Btuh of total appliance input If the unit is installed in an area with an exhaust fan provide sufficient ventilation to prevent negative pressures from occurring in the room The combustion...

Page 10: ...icalstorage areas Exposure to the following substances in the combustion air supply may also require Outdoor Air for combustion Permanent wave solutions Chlorinated waxes and cleaners Chlorine based s...

Page 11: ...A B149 1 Natural Gas and Propane Installation Codes and these instructions Determine that there is no blockage or restriction leakage corrosion and other deficiencies which could cause an unsafe condi...

Page 12: ...irculatedintotheliving space and create potentially hazardous conditions including carbon monoxide poisoning that could result in personal injury or death The return air ductwork may be connected to a...

Page 13: ...ce must be properly labeled by the installer in case emergency shutdown is required Leak Check After the gas piping to the furnace is complete all connections must be tested for gas leaks To check for...

Page 14: ...to 10000 Manifold Pressure Setting in WC 3 5 3 5 3 5 3 5 3 0 For a Natural Gas Sea Level Heating Value of 900 to 999 Btu cu ft Elevation feet above sea level zero to 1999 2000 to 4999 5000 to 5999 600...

Page 15: ...witch kit is 903853 The directions to convert the furnace are given below 1 READ ALL INSTRUCTIONS BEFORE PROCEEDING WITH THE CONVERSION 2 Disconnect all electrical power to the furnace 3 Remove the ac...

Page 16: ...o the furnace must be suppliedfromadedicatedbranchcircuitcontaining the correct fuse or circuit breaker for the furnace See Table 9 An electrical disconnect must be installedtobereadilyaccessiblefroma...

Page 17: ...board must be connected to the thermostat for proper cooling mode operation COOL Figure 10 Line Voltage Field Wiring Field Supplied Disconnect Within Sight of Furnace Field Supplied Panel Connector F...

Page 18: ...in water column 0 36 psig and is not less than 4 5 in water column 0 16 psig for natural gas For LP gas the line service pressure must not exceed 14 in water column 0 51 psig and must not be less than...

Page 19: ...ow room temperature and verify steps 9 through 11 of the Sequence of Operation Verifying and Adjusting Firing Rate The firing rate must be verified for each installation to prevent over firing the fur...

Page 20: ...Factory Wiring Low Voltage High Voltage Power On Limit Circuit Open or External Load On W Pressure Switch is Open with Inducer On Pressure Switch is Closed with Inducer Off Ignition Failure Check Gro...

Page 21: ...t systems the temperature rise will fall within the range specified on the rating plate with the blower speed at the factory recommended setting If the temperature rise measured is outside the range s...

Page 22: ...Exhaust Adapter 9 Low Voltage Transformer 10 Burner Assembly 11 Supply Air Limit Switch 12 Blower Assembly 13 Induced Draft Blower 14 Vent Transition 1 Igniter 2 Flame Sensor Not Shown 3 Gas Valve 4 F...

Page 23: ...rove that flame has carried over from the igniter to the opposite end burner If no flame is sensed the furnace will shut down within 7 seconds Flame Roll Out Switch The flame roll out switch verifies...

Page 24: ...s are found Failure to prevent products of combustion from being circulated into the living space can create potentially hazardousconditionsincludingcarbon monoxidepoisoningthatcouldresultin personal...

Page 25: ...the wires from the gas valve igniter and flame sensor 6 Using wrenches separate the ground joint union in the gas supply piping at the furnace 7 Remove the piping between the gas valve and the ground...

Page 26: ...xed at this level In general whenever ignition failure occurs the warm up interval is increased by 3 seconds on the next try And if successful it remains there Minimum and maximum warm up time limits...

Page 27: ...or plugged 8 Is the flame sensor coated Remove and clean with steel wool If the furnace locks out after 5 attempts for ignition it will try again every hour if a call for heat remains If the inducer a...

Page 28: ...s Piping Connections leak tested ______________________ Gas Line Pressure __________________ in water column with furnace operating Manifold Pressure __________________ in water column with furnace op...

Reviews: