![Nordyne M1GB 056 Installation Instructions And Owner'S Manuals Download Page 9](http://html1.mh-extra.com/html/nordyne/m1gb-056/m1gb-056_installation-instructions-and-owners-manuals_1704757009.webp)
9
Figure 12. Closet or Alcove
Figure 13. Cut-Out Locations
Figure 15. Duct Connector
Figure 14. Mounting Plate
Figure 16. Installation of Duct Connector
INSTALL DUCT CONNECTOR
a. Place duct connector through the floor opening with
bottom tabs extending through the duct opening. (See
Figure 15)
b. Secure duct connector to floor.
c. Bend bottom tabs under and up tightly against the
supply air duct (See Figure 16).
NOTE: The duct connector is designed for use on ducts 12"
in width. When using the connector on 12" wide ducts, there
may be insufficient clearance to bend the tabs on two sides of
the duct connector. In such cases the tabs may be attached
to the sides of the duct by using sheet metal screws or other
suitable fasteners. (See Figure 17).
If tape is used to provide a better seal, it should be approved
by applicable national or local codes.
ALTERNATE ATTACHMENT METHODS
This procedure may also be used to install a furnace duct
connector to narrow metal ductwork where insufficient
clearance prevents bending of the duct connector tabs at the
side(s) of the duct. (See Figure 18).
CUT DUCT OPENING
a. Place duct connector through the floor opening with
bottom tabs resting on top of the supply air duct.
b. Center duct connector and push back against rear
edge of floor opening.
c. Mark cut-out location (tab area) and remove duct
connector.
d. Cut out duct opening 1/4" larger than area marked.
INSTALL FURNACE MOUNTING PLATE
a. Place mounting plate (supplied within duct connector)
at rear of the floor opening (See Figure 15).
REAR WALL
MOUNTING
PLATE
FLOOR
OPENING
FUEL
LINE
HOLES
SUPPLY AIR DUCT
CUT DUCT OPENING
1/16TH. LARGER THAN
DUCT CONNECTOR
REAR WALL
SUPPLY AIR DUCT
FUEL
LINE
HOLES
MOUNTING
PLATE
FLOOR
OPENING
UNDER DUCT OPENING
TABS
TABS
DUCT
DUCT
1. INSERT DUCT PLENUM CONNECTOR
INTO DUCT CUT-OUT.
2. BEND BOTTOM TABS OVER
AND ONTO THE UNDERNEATH
DUCT SERVICE.
FLOOR CUT-OUT
FOR DUCT CONN.
CEILING
CUT-OUT FOR
FLUE AND
ROOF JACK
(See Fig 12)
CL
CL
CL
CL
24"
23-1/4"
21-3/4"
14-1/2"
2-1/4"
2-3/4"
20"
14-1/2"
13-1/2"
FURNACE OUTLINE
FLOOR CUT-OUT
FOR OPTIONAL
COOLING COIL
10"
12-7/8"
14-3/4"
15-1/2"
1-1/4" D.
ALT FUEL-LINE
ENTRY
FURNACE
OUTER DOOR
REAR WALL OF CLOSET OR ALCOVE
FUEL-LINE
1-3/4"
2"
3/4"
CEILING AND ROOF
OPENINGS
C
L
C
L
13-1/2"
10"
23 -1/4"
FLOOR
OPENING
C
L
C
L
ALT. FUEL
LINE HOLES
SIDE WALL
REAR WALL
FUEL LINE
HOLE