background image

18

M1G*-models and “slow-open” for M1M*- and M1B*-
models which means it opens to a “low-fire” position, and
after a few seconds, “steps-open” to “high-fire.”

4. Roll Out Switch - (M1G* - 056 & 070) The furnace is

protected by a manual reset safety switch located on the
bottom left hand side of the combustion pipe.

5. Oil Burner Primary Control - The primary control for oil

gun furnaces starts the burner, monitors a safe operating
cycle, and shuts the burner off at the end of a heating
cycle.  The control uses a light sensing transducer to
determine if fuel ignition has been successfully attained.
If ignition is not attained by the end of the safety ignition
timing period, the control shuts the burner off and enters
“lock-out.”

6. a. Summer Cooling - (H Series):  Your furnace is equipped

to operate the circulating fan only. Turn the Fan On-Auto
switch to the “ON” position during warm weather.  The
blower will now operate to circulate air in your home
through the duct system.

b. Summer Cooling - (A, B, C, & D Series):  Your furnace
is A/C ready, equipped with A/C relay and transformer.
The unit is equipped to use a 4-wire thermostat.  When
using a 5-wire thermostat, RC and RH should be jumped
(see instructions included with thermostat).

17.  SERVICE GUIDE

BURNER ADJUSTMENTS

Burner settings and adjustments are made at the factory.
However, these settings may change during shipping,
handling, and installation.  Therefore the following items
should be checked and readjusted if necessary.

Atmospheric Gas with Standing Pilot and Direct Ignition
Furnaces, Including Gas Gun.

a. Gas Pressure

The gas pressure can be checked with a manometer at
the pressure tap located on the side of the gas valve.  The
gas valve pressure regulator can be adjusted by removing
the regulator selector stack and turning the slotted insert
located directly under the selector stack.  The regulator
selector stack must be secured in place before each
pressure reading is taken.  Natural gas manifold pressure
should be 3.5" W.C. and L.P. gas manifold pressure
should be 10" W.C.  Replace the gas pressure tap plug
on the gas valve.

b. Pilot Flame (Standing Pilot Only)

The pilot flame can be adjusted by turning the pilot adjustment
screw, located on top of the gas valve (See Figure 29).  The
pilot flame height should be between 3/4” and 1.”  The flame
tip should be visible just above the pilot bracket when
viewed through the observation door.  The same pilot
orifice is used with both natural and L.P. gas.

b. After this sequence, the control module tests to see if

flame is sensed.  If it has, the furnace continues to heat
until the thermostat is satisfied.

c. If the burner has not lit, the ignition sequence is repeated

a maximum of two more times.  If flame is not sensed after
three attempts, the control enters “Lockout” and no further
attempts to light the burner will occur.  If “Lockout” occurs,
contact a qualified service technician for assistance.

d. When call for heat is satisfied, the thermostat contacts

open and the gas valve shuts off gas flow.

TO TURN OFF GAS/OIL APPLIANCE:

a. Set the thermostat to the lowest setting.
b. Turn off all electric power to the appliance before servicing

unit.

c. Set the  On-Off Switch to “OFF.”
d. Honeywell - turn gas control knob clockwise to “OFF”

Robertshaw - Push the gas control lever to “OFF.”

e. For oil, shut off all valves.
f. Replace the furnace door.

THE FURNACE CONTROLS AND FUNCTIONS

1. On-Off Switch - This switch turns electrical power to the

furnace on and off.  The switch must be set in the “On”
position for the furnace to operate.  For M1G* models, in
warm weather there is a possibility of the blower coming
on periodically or operating continuously due to a heat
buildup within the furnace by a combination of warm
weather and heat from the pilot.  This is normal operation
as long as there is power to the furnace and the On-Off
switch is at the “ON” position.  If blower operation is not
desired, the On-Off switch may be set in the “OFF”
position to cut the electrical power to the furnace.

2. Limit Control - This furnace is protected by two high

temperature safety limit switches. The auxiliary (upper)
limit switch and the high temperature (lower) limit switch
are automatic reset types.  If either limit trips, the burner
will shut off.  If either limit switch trips off again soon after
resetting, set the furnace On-Off switch to the “OFF”
position and call your authorized serviceman.

3. Gas Valve - The gas valves for the gas furnaces are a

100% shut-off type and will fail safe if for some reason the
gas is turned off.  The valve is a “step-open” type for

Before placing the furnace in service it must be
checked to make sure it is equipped for the type
of gas being used. The burner flame must also be
observed and adjusted if necessary. Failure to
observe this caution may result in unsafe
operation, explosion and/or fire, or asphyxiation.
See the following sections “Gas Supply” and
“Combustion Air.”

DANGER:

!

Summary of Contents for M1GB 056

Page 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Iftheinformationinthismanualisnotfollowedexactly afireorexplosionmayresu...

Page 2: ...E GUIDE 18 18 MAINTENANCE 22 19 OPTIONAL ACCESSORIES 23 20 WIRING DIAGRAMS 24 26 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 27 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Page 3: ...nstallation Blower Assemblies A C Capacity Blower Wheel Motor Hp Ton 903412 10 x 8 1 3 2 2 3 903413 11 x 8 1 2 2 2 3 4 903414 10 x 8 3 4 2 2 3 4 5 Part No Blower Motor Assembly Furnace Input Output Or...

Page 4: ...ion furnace adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which cannot be included in warranty payments are 1 Converting the furnace to u...

Page 5: ...followingconditionstohave acceptablereturnairsystemsfor closet installed forced air heating appliances a Regardless of the location the return air opening into the closet shall not be less than specif...

Page 6: ...ertiduct program to determine proper duct size for A C 8 AIR DISTRIBUTION SYSTEMS For proper air distribution the supply duct system must be designed so that the static pressure measured external to t...

Page 7: ...2 ROOF SLOPE 2 SLANT DECK 12 1 2 ROOF JACK WITH 2 FLASHING 12 SLANT 1 2 S S AW T 20 32 2 AW ALL WEATHER FLASHING PITCH 12 RISE 0 FLAT 2 2 5 12 4 4 12 MIN ADJ LENGTH F S FLAT FLASHING SLANT FLASHING TY...

Page 8: ...flooropening SeeFigure13 b Cut ceiling and roof holes as follows Ceiling Hole 8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE THIS COULD CAUSE UNSA...

Page 9: ...8 CUT DUCT OPENING a Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct b Center duct connector and push back against rear edge of floor opening c Ma...

Page 10: ...r opening c Slide onto mounting plate Bottom rear slots on furnace should engage with mounting plate tabs d Secure front with one 1 fastener at each corner See Figure 19 or 20 NOTE Additional fastener...

Page 11: ...ion door Gas or Oil To furnace wall thermostat MANUFACTURED HOME SITE a Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 24 b Place upper Roof Jack crown on to the...

Page 12: ...ircuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems Once the furnace is installed check the thermostat anticipator against the nominal setting of 0 4 1 Connect t...

Page 13: ...ttom of the fuel tank to the fuel pump must not exceed ten feet Keep the tank filled especially in the summer to reduce the accumulation of condensation CAUTION The furnace must be converted by a qual...

Page 14: ...n the oil supply line and all plugs nuts and fittingsonthepumpmustbeairtight Thisincludesthenutthat covers the pressure adjustment It is important that the hook up be done carefully and with a good fl...

Page 15: ...old the control lever for about one 1 minute after the pilot is lit Release the lever and it will spring back to the PILOT position Pilot should remain lit If it goes out repeat steps d through h abov...

Page 16: ...appliancebeforeservicing unit c Set the ON OFF switch to OFF d Honeywell pushinthegascontrolknobandturnclockwise to OFF Robertshaw push the gas control lever to OFF e Replace the furnace door SEQUENCE...

Page 17: ...ust be reset e When call for heat is satisfied the thermostat contacts open and the burner will stop Gas Gun Models M1 gas gun furnaces may be converted to oil gun in the field by using the proper con...

Page 18: ...hrough the observation door The same pilot orifice is used with both natural and L P gas b After this sequence the control module tests to see if flame is sensed If it has the furnace continues to hea...

Page 19: ...wn in Figure 32 Do not permit any electrodes to be grounded to any surface GAS CONVERSION This gas fired heating appliance was shipped from the factory for use with natural gas However the appliance c...

Page 20: ...o put the furnace into operation NOTE Thepilotflameisadjustablebyturningtheadjustment screw located on the gas valve with a small screwdriver See Figure 29 TROUBLESHOOTING STANDING PILOT MODELS Main B...

Page 21: ...s Closed a Check for polarity b Check ground c Check flue d Check combustion air e Check gas pressure f Check orifice g Check the position of ignitor a normal reading should be 40 75 ohms 24 Volts Sup...

Page 22: ...filters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During extremely col...

Page 23: ...thasbeendesignedspecifically for manufactured housing applications and can best handle your home comfort needs Listed and ARI Certified all models are protected by the NORDYNE Air Conditioner Limited...

Page 24: ...ied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent BLACK BLACK SUPPLIED BY INSTALLER BLUE WHITE MANUAL RESET VENT SWITCH 1 5 2 3 6 4 GAS VALVE FAN SWITCH HI LI...

Page 25: ...ce orange wire with red wire low speed NOTE To run at same speed in both heating and cooling mode remove wire from either terminal 4 or 6 on the relay then attach jumper to terminals 4 and 6 6 5 4 3 2...

Page 26: ...original wires as supplied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent SUPPLIED BY INSTALLER C W G R COM BLUE 1 5 2 A C BLOWER RELAY 3 6 4 FAN SWITCH HI LIM...

Page 27: ...2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28 28 29 M1M 077 ORIFICE SIZE LP 40 41 42 42 42 43 43 44 44 45 OUTPUT MBTUH 61 7 56 9 54 6 52 4 50 3 48 3 46 4 44 5 42 7 41 0...

Page 28: ...MO 707776C Replaces 707776B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 04 99 INSTALLER Please leave these installation instruc...

Reviews: