Nordyne M1GB 056 Installation Instructions And Owner'S Manuals Download Page 16

16

Figure 30. Direct Ignition Gas Valve - Honeywell

d. When the gas valve is energized it steps open at a

reduced flow and opens fully after approximately 14
seconds.

e. When the call for heat is satisfied the thermostat contacts

open, the gas valve shuts off gas flow, and the induced
draft blower stops.

GENERAL-DIRECT IGNITION MODELS

Read safety information on front page of these installation
instructions before operating furnace.    DO NOT ATTEMPT
TO OPERATE FURNACE IF YOU SMELL GAS.

OPERATING INSTRUCTIONS FOR
M1M — MODELS WITH DIRECT IGNITION:

a. STOP! Read the SAFETY INFORMATION.
b. Set the thermostat to the lowest setting.
c. Turn off all electric power to the appliance.
d. This appliance is equipped with an ignition device which

automatically lights the burner. Do not try to light the
burner by hand.

e. Honeywell - push in the gas control knob and turn clockwise

to “OFF.” Robertshaw - push the gas control lever to
“OFF.” NOTE: The lever cannot be placed in the “OFF”
position unless it is pushed in slightly. DO NOT FORCE
(See Figures 30 & 31).

f. Wait ten (10) minutes to clear out any gas. If you smell

gas, STOP! and follow step “d” in the SAFETY
INFORMATION section. If you do not smell gas, go to the
next step.

g. Set the On-Off switch to the “ON” position.
h. Honeywell - turn knob on gas control counter clockwise to

“ON.” Robertshaw - push the gas control lever to “ON.”

i. Turn on all electric power to the appliance.
j. Replace the furnace door.
k. Set the thermostat to “HEAT” and the desired temperature

setting. The furnace should light after approximately 75
seconds. If the appliance will not operate, follow the
instructions “To Turn Off Gas To Appliance” and call your
service technician or gas supplier.

In the event of any flashback or explosion, immediately shut
off the furnace and call your service technician.

TO TURN OFF GAS APPLIANCE:
a. Set the thermostat to the lowest setting.
b. Turn off all electric power to the appliance before servicing

unit.

c. Set the  ON-OFF switch to “OFF.”
d. Honeywell - push in the gas control knob and turn clockwise

to “OFF.” Robertshaw - push the gas control lever to
“OFF.”

e. Replace the furnace door.

SEQUENCE OF OPERATION FOR M1M MODELS WITH
DIRECT IGNITION
Direct ignition model furnaces do not have a pilot. Ignition is
accomplished automatically by a silicon carbide hot surface
ignitor. A control module takes care of all timing functions.
After lighting, the control module uses the ignitor as a flame
sensor, shutting off gas should the flame go out. There are no
external relays or timing devices.

Do not try to light this furnace manually. The control
module is not field serviceable.

a. On a call for heat, the thermostat contacts close, supplying

24 VAC between terminals “C” and “W” of the control
module, which starts combustion motor.

b. When the inducer starts, the air pressure switch closes at

-0.30”WC differential pressure and energizes the control.

c. After a 45 second purge period, the ignitor is energized

for a 30 second warm-up period, after which the gas
valve opens.

d. The trial period for ignition is approximately 6 seconds,

after which the gas valve either remains open if flame is
sensed, or closes if flame is not sensed.

e. If flame is not sensed, the entire sequence is repeated

four more times before “lockout” occurs.  To reset, wait 30
seconds and then interrupt the 24 VAC power by turning
the room thermostat below room temperature, then
returning it to the original set point.

f. If flame is not established on the fifth trial for ignition (initial

try + 4 re-tries), the control de-energizes the gas valve,
flashes “4” on the Status LED, and lockouts out heat
operation for 1 hour.

g. If a flame is present, the control energizes the main blower

on heat speed 30 seconds after the gas valve opens.

h. When call for heat is satisfied the thermostat contacts

open, the gas valve shuts off gas flow and the combustion
blower remains on for a 30 second post-purge period.

i. The main blower is de-energized after a 120 second

blower off delay.

Gas Control

Figure 31. Direct Ignition Gas Valve - Robertshaw

GAS CONTROL KNOB

Summary of Contents for M1GB 056

Page 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Iftheinformationinthismanualisnotfollowedexactly afireorexplosionmayresu...

Page 2: ...E GUIDE 18 18 MAINTENANCE 22 19 OPTIONAL ACCESSORIES 23 20 WIRING DIAGRAMS 24 26 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 27 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Page 3: ...nstallation Blower Assemblies A C Capacity Blower Wheel Motor Hp Ton 903412 10 x 8 1 3 2 2 3 903413 11 x 8 1 2 2 2 3 4 903414 10 x 8 3 4 2 2 3 4 5 Part No Blower Motor Assembly Furnace Input Output Or...

Page 4: ...ion furnace adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which cannot be included in warranty payments are 1 Converting the furnace to u...

Page 5: ...followingconditionstohave acceptablereturnairsystemsfor closet installed forced air heating appliances a Regardless of the location the return air opening into the closet shall not be less than specif...

Page 6: ...ertiduct program to determine proper duct size for A C 8 AIR DISTRIBUTION SYSTEMS For proper air distribution the supply duct system must be designed so that the static pressure measured external to t...

Page 7: ...2 ROOF SLOPE 2 SLANT DECK 12 1 2 ROOF JACK WITH 2 FLASHING 12 SLANT 1 2 S S AW T 20 32 2 AW ALL WEATHER FLASHING PITCH 12 RISE 0 FLAT 2 2 5 12 4 4 12 MIN ADJ LENGTH F S FLAT FLASHING SLANT FLASHING TY...

Page 8: ...flooropening SeeFigure13 b Cut ceiling and roof holes as follows Ceiling Hole 8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE THIS COULD CAUSE UNSA...

Page 9: ...8 CUT DUCT OPENING a Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct b Center duct connector and push back against rear edge of floor opening c Ma...

Page 10: ...r opening c Slide onto mounting plate Bottom rear slots on furnace should engage with mounting plate tabs d Secure front with one 1 fastener at each corner See Figure 19 or 20 NOTE Additional fastener...

Page 11: ...ion door Gas or Oil To furnace wall thermostat MANUFACTURED HOME SITE a Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 24 b Place upper Roof Jack crown on to the...

Page 12: ...ircuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems Once the furnace is installed check the thermostat anticipator against the nominal setting of 0 4 1 Connect t...

Page 13: ...ttom of the fuel tank to the fuel pump must not exceed ten feet Keep the tank filled especially in the summer to reduce the accumulation of condensation CAUTION The furnace must be converted by a qual...

Page 14: ...n the oil supply line and all plugs nuts and fittingsonthepumpmustbeairtight Thisincludesthenutthat covers the pressure adjustment It is important that the hook up be done carefully and with a good fl...

Page 15: ...old the control lever for about one 1 minute after the pilot is lit Release the lever and it will spring back to the PILOT position Pilot should remain lit If it goes out repeat steps d through h abov...

Page 16: ...appliancebeforeservicing unit c Set the ON OFF switch to OFF d Honeywell pushinthegascontrolknobandturnclockwise to OFF Robertshaw push the gas control lever to OFF e Replace the furnace door SEQUENCE...

Page 17: ...ust be reset e When call for heat is satisfied the thermostat contacts open and the burner will stop Gas Gun Models M1 gas gun furnaces may be converted to oil gun in the field by using the proper con...

Page 18: ...hrough the observation door The same pilot orifice is used with both natural and L P gas b After this sequence the control module tests to see if flame is sensed If it has the furnace continues to hea...

Page 19: ...wn in Figure 32 Do not permit any electrodes to be grounded to any surface GAS CONVERSION This gas fired heating appliance was shipped from the factory for use with natural gas However the appliance c...

Page 20: ...o put the furnace into operation NOTE Thepilotflameisadjustablebyturningtheadjustment screw located on the gas valve with a small screwdriver See Figure 29 TROUBLESHOOTING STANDING PILOT MODELS Main B...

Page 21: ...s Closed a Check for polarity b Check ground c Check flue d Check combustion air e Check gas pressure f Check orifice g Check the position of ignitor a normal reading should be 40 75 ohms 24 Volts Sup...

Page 22: ...filters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During extremely col...

Page 23: ...thasbeendesignedspecifically for manufactured housing applications and can best handle your home comfort needs Listed and ARI Certified all models are protected by the NORDYNE Air Conditioner Limited...

Page 24: ...ied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent BLACK BLACK SUPPLIED BY INSTALLER BLUE WHITE MANUAL RESET VENT SWITCH 1 5 2 3 6 4 GAS VALVE FAN SWITCH HI LI...

Page 25: ...ce orange wire with red wire low speed NOTE To run at same speed in both heating and cooling mode remove wire from either terminal 4 or 6 on the relay then attach jumper to terminals 4 and 6 6 5 4 3 2...

Page 26: ...original wires as supplied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent SUPPLIED BY INSTALLER C W G R COM BLUE 1 5 2 A C BLOWER RELAY 3 6 4 FAN SWITCH HI LIM...

Page 27: ...2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28 28 29 M1M 077 ORIFICE SIZE LP 40 41 42 42 42 43 43 44 44 45 OUTPUT MBTUH 61 7 56 9 54 6 52 4 50 3 48 3 46 4 44 5 42 7 41 0...

Page 28: ...MO 707776C Replaces 707776B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 04 99 INSTALLER Please leave these installation instruc...

Reviews: