background image

21

d. No voltage to control module - determine if 24 volts (or 120

volts) is available to the control module.  If voltage is not
available check for:

Blown fuse, defective transformer, circuit breaker, no
electrical supply.

Limit switch open.

Loose connections.

Combustion Blower Does Run - No Flame

a. Defective centrifugal switch (M1B* Model).

Check the operation of centrifugal switch by removing
end bell of the burner motor.

Clean contacts of motor.

If the contacts are closed, replace the motor.

b. Defective pressure switch (M1M* and M1G* 077, 090

Models) - check air tube and electrical connections.

c. Burner in purge mode - allow 75 seconds for flame

establishing period.

d. Check for proper electrical connections at purge timer,

control box, or gas valve.

e. Check for gas supply - gas line valve on, control lever on.

Control Module Is Powered—
 Ignitor Does Not Heat Up

a. Disconnect ignitor leads at AMP receptacle and check for

120 volts at the plug during ignition sequence.

b. Replace ignition control if 120 volts is not available at AMP

plug during ignition sequence.

 

120 Volts Is Available At AMP Plug—

 Ignitor Does Not Heat Up

a. Disconnect power to the furnace.
b. Disconnect AMP plug to the ignitor, and check ignitor

resistance with an ohm meter. Set on RX1 scale.

Normal reading should be 40 - 75 ohms.

If above or below this rating at room temperature

change ignitor.

c. Check for continuity from ignitor receptacle to burner.

Main Flame Ignites—
Burner Locks Out

a. Ignition control is not properly grounded.
b. Defective ignition control.
c. Improper polarity of 120 volt power supply.
d. Ignitor has hairline crack.
e. Improper gas pressure or burner air adjustment is not

allowing flame to contact ignitor tip for flame rectification.

f. Misaligned ignitor does not allow flame to contact ignitor

tip for flame rectification.

Burner Short Cycling —-
Thermostat Calls for Heat, Limit Switches Closed

a. Check for polarity.
b. Check ground.
c. Check flue.
d. Check combustion air.
e. Check gas pressure.
f. Check orifice.
g. Check the position of ignitor, a normal reading should be

40-75 ohms.

24 Volts Supplied To Gas Valve During Ignition —
No Main Gas Flow

a. Gas valve may be defective.  Replace if necessary.
b. Gas piping may be plugged.  Check for adequate gas

supply to gas valve at union.

Burner Operates—
Insufficient Heat

a. Check thermostat for proper setting and location.

Thermostat should not be located where it will be affected
by another heat source.

b. Check for clean filter and proper air flow.
c. Check burner for proper gas firing rate.
d. Be sure unit is not undersized for its thermal load.
e. Check thermostat anticipator. The nominal anticipator

setting is 0.4.

Control Module Status Indicator - M1B* Series

a. One flash - the control is in lock-out because the

motor centrifugal switch is or was stuck closed.

b. Two flashes - the control is in lockout because the

signal was not received by the control that the
motor centrifugal switch had closed within the time.

c. Three flashes- the control is in lockout because

a failed ignition attempt, a gas valve error, or a
false flame sensed during the warm up period. If
false flame has been sensed, the control will return
to normal operation, and repeat ignition sequence
when the false flame is not present.

d. Four flashes- the control is in lockout due to a

failure within the control board.

Control Module Status Indicators - M1M Series

Control Status
The Red LED labeled “STATUS” is provided to indicate
system faults.

Steady ON:

Control OK

Steady OFF:

No power

Rapid flash:

False flame or internal control fault

One flash:

Limit switch is open

Two flashes:

Pressure switch is open

Three flashes:

Pressure switch is stuck closed

Four flashes:

Lockout due to failed ignition

Five flashes:

L1 neutral reversed or L1 voltage
not present on L1

Flame Status
A Yellow LED labeled “Flame” is provided to indicate flame
status. When flame is sensed, the flame LED is lit. If flame
sense is weak, yellow LED will flash.

Summary of Contents for M1GB 056

Page 1: ...fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING Iftheinformationinthismanualisnotfollowedexactly afireorexplosionmayresu...

Page 2: ...E GUIDE 18 18 MAINTENANCE 22 19 OPTIONAL ACCESSORIES 23 20 WIRING DIAGRAMS 24 26 21 EQUIVALENT ORIFICE SIZES AT HIGH ALTITUDES 27 Table 1 Model Identification Door Color W White G Gray Cabinet Dimensi...

Page 3: ...nstallation Blower Assemblies A C Capacity Blower Wheel Motor Hp Ton 903412 10 x 8 1 3 2 2 3 903413 11 x 8 1 2 2 2 3 4 903414 10 x 8 3 4 2 2 3 4 5 Part No Blower Motor Assembly Furnace Input Output Or...

Page 4: ...ion furnace adjustments improper operating procedure on the part of the user etc Some specific examples of service calls which cannot be included in warranty payments are 1 Converting the furnace to u...

Page 5: ...followingconditionstohave acceptablereturnairsystemsfor closet installed forced air heating appliances a Regardless of the location the return air opening into the closet shall not be less than specif...

Page 6: ...ertiduct program to determine proper duct size for A C 8 AIR DISTRIBUTION SYSTEMS For proper air distribution the supply duct system must be designed so that the static pressure measured external to t...

Page 7: ...2 ROOF SLOPE 2 SLANT DECK 12 1 2 ROOF JACK WITH 2 FLASHING 12 SLANT 1 2 S S AW T 20 32 2 AW ALL WEATHER FLASHING PITCH 12 RISE 0 FLAT 2 2 5 12 4 4 12 MIN ADJ LENGTH F S FLAT FLASHING SLANT FLASHING TY...

Page 8: ...flooropening SeeFigure13 b Cut ceiling and roof holes as follows Ceiling Hole 8 3 4 222 mm diameter Roof Hole 9 3 8 238 mm diameter c DO NOT ALLOW DEBRIS TO FALL INTO THE FURNACE THIS COULD CAUSE UNSA...

Page 9: ...8 CUT DUCT OPENING a Place duct connector through the floor opening with bottom tabs resting on top of the supply air duct b Center duct connector and push back against rear edge of floor opening c Ma...

Page 10: ...r opening c Slide onto mounting plate Bottom rear slots on furnace should engage with mounting plate tabs d Secure front with one 1 fastener at each corner See Figure 19 or 20 NOTE Additional fastener...

Page 11: ...ion door Gas or Oil To furnace wall thermostat MANUFACTURED HOME SITE a Transit mode weather cap to be removed and upper Roof Jack crown installed See Figure 24 b Place upper Roof Jack crown on to the...

Page 12: ...ircuit 2 wire is required for furnace only 5 wire for heating and optional cooling systems Once the furnace is installed check the thermostat anticipator against the nominal setting of 0 4 1 Connect t...

Page 13: ...ttom of the fuel tank to the fuel pump must not exceed ten feet Keep the tank filled especially in the summer to reduce the accumulation of condensation CAUTION The furnace must be converted by a qual...

Page 14: ...n the oil supply line and all plugs nuts and fittingsonthepumpmustbeairtight Thisincludesthenutthat covers the pressure adjustment It is important that the hook up be done carefully and with a good fl...

Page 15: ...old the control lever for about one 1 minute after the pilot is lit Release the lever and it will spring back to the PILOT position Pilot should remain lit If it goes out repeat steps d through h abov...

Page 16: ...appliancebeforeservicing unit c Set the ON OFF switch to OFF d Honeywell pushinthegascontrolknobandturnclockwise to OFF Robertshaw push the gas control lever to OFF e Replace the furnace door SEQUENCE...

Page 17: ...ust be reset e When call for heat is satisfied the thermostat contacts open and the burner will stop Gas Gun Models M1 gas gun furnaces may be converted to oil gun in the field by using the proper con...

Page 18: ...hrough the observation door The same pilot orifice is used with both natural and L P gas b After this sequence the control module tests to see if flame is sensed If it has the furnace continues to hea...

Page 19: ...wn in Figure 32 Do not permit any electrodes to be grounded to any surface GAS CONVERSION This gas fired heating appliance was shipped from the factory for use with natural gas However the appliance c...

Page 20: ...o put the furnace into operation NOTE Thepilotflameisadjustablebyturningtheadjustment screw located on the gas valve with a small screwdriver See Figure 29 TROUBLESHOOTING STANDING PILOT MODELS Main B...

Page 21: ...s Closed a Check for polarity b Check ground c Check flue d Check combustion air e Check gas pressure f Check orifice g Check the position of ignitor a normal reading should be 40 75 ohms 24 Volts Sup...

Page 22: ...filters with a vacuum or with warm water and soap Reinstall when dry Also clean dust and lint around furnace and in the furnace vestibule Figure 35 3 Seasonal Service Information During extremely col...

Page 23: ...thasbeendesignedspecifically for manufactured housing applications and can best handle your home comfort needs Listed and ARI Certified all models are protected by the NORDYNE Air Conditioner Limited...

Page 24: ...ied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent BLACK BLACK SUPPLIED BY INSTALLER BLUE WHITE MANUAL RESET VENT SWITCH 1 5 2 3 6 4 GAS VALVE FAN SWITCH HI LI...

Page 25: ...ce orange wire with red wire low speed NOTE To run at same speed in both heating and cooling mode remove wire from either terminal 4 or 6 on the relay then attach jumper to terminals 4 and 6 6 5 4 3 2...

Page 26: ...original wires as supplied with the appliance must be replaced use 105 C Thermoplastic type wire or its equivalent SUPPLIED BY INSTALLER C W G R COM BLUE 1 5 2 A C BLOWER RELAY 3 6 4 FAN SWITCH HI LIM...

Page 27: ...2 46 2 44 4 42 6 40 9 39 3 37 7 ORIFICE SIZE NAT GAS 21 23 23 24 25 26 27 28 28 29 M1M 077 ORIFICE SIZE LP 40 41 42 42 42 43 43 44 44 45 OUTPUT MBTUH 61 7 56 9 54 6 52 4 50 3 48 3 46 4 44 5 42 7 41 0...

Page 28: ...MO 707776C Replaces 707776B Specifications and illustrations subject to change without notice and without incurring obligations Printed in U S A 04 99 INSTALLER Please leave these installation instruc...

Reviews: