background image

7

Direct Vent Installation

This condensing furnace is certified for installation as a 
Direct Vent (2-pipe) appliance. Direct Vent (2-pipe) furnaces 
draw combustion air directly from the outdoors and then 
vent the combustion products back outside, isolating the 
entire system from the indoor space. It is important to make 
sure that the whole system is sealed and clearances to 
combustibles are maintained regardless of the installation 
being  in  a  confined  or  unconfined  space. This  section 
specifies installation requirements for Direct Vent (2-pipe) 
piping. Table 2 (page 8) contains the length of vent and 
combustion air piping for this type of installation.

Provisions must be made during the installation of this 
furnace that provide an adequate supply of fresh air for 
combustion and ventilation. The combustion air from the 
outside needs to be clear of chemicals that can cause 
corrosion.  The  inlet  pipe  should  not  be  placed  near 
corrosive chemicals such as those listed on page 5. 

Air openings on top of the furnace and openings in closet 
doors or walls must never be restricted. If the furnace is 
operated without adequate air for combustion, the flame 
roll-out switch will open, turning off the gas supply to the 
burners. 

NOTE

This safety device is a manually reset 

switch.

 

DO  NOT  install  jumper  wires  across  these 

switches  to  defeat  their  function  or  reset  a  switch 
without identifying and correcting the fault condition.

 If 

a switch must be replaced, use only the correct sized part 
specified in the Replacement Parts List provided online.

Vent Pipe Length & Diameter

For proper furnace operation, the combustion air and vent 
piping must not be excessively restrictive. 

•  The venting system should be designed to have the 

minimum number of elbows or turns.

•  All horizontal runs must slope upwards from the furnace 

at 1/4 inch minimum per running foot of vent.

•  Transition to the final vent diameter should be done as 

close to the furnace outlet as practical.

•  Always use the same size or a larger pipe for combustion 

air that is used for the exhaust vent.

Table 2 (page 8) indicates the maximum allowable pipe 
length for a furnace of known input rate, when installed 
with piping of selected diameter and number of elbows. To 
use the table, the furnace input rate, the centerline length 
and the number of elbows on each pipe must be known.

When estimating the length of vent runs, consideration 
must be made to the effect of elbows and other fittings. 
This is conveniently handled using the idea of “equivalent 
length”. This means the fittings are assigned a linear length 
that accounts for the pressure drop they will cause. For 
example: a 3” diameter, long radius elbow is worth the 
equivalent of 3.5 feet of linear run.

The equivalent lenghts of tees and various elbows are 
listed in Table 2. Measure the linear length of your vent run 
and then add in the equivalent length of each fitting. The 

Important Information

 WARNING:

Furnace installation using methods other than 
those described in the following sections must 
comply with the National Fuel Gas Code (NFGC) 
and all applicable local codes.

 WARNING:

Upon  completion  of  the  furnace  installation, 
carefully  inspect  the  entire  flue  system  both 
inside and outside the furnace to assure it is 
properly sealed. Leaks in the flue system can 
result in serious personal injury or death due 
to exposure of flue products, including carbon 
monoxide.

 WARNING:

This  furnace  must  not  be  vented  with  other 
appliances,  even  if  that  appliance  is  of  the 
condensing type. This includes water heaters 
of any efficiency. Common venting can result 
in severe corrosion of other appliances or their 
venting  and  can  allow  combustion  gases  to 
escape through such appliances or vents. Do 
not vent the furnace to a fireplace chimney or 
building chase.

•  This  furnace  must  be  vented  in  compliance  with 

the  current  revision  of  the  National  Fuel  Gas  Code 

(ANSI-Z223.1/NFPA54).  Instructions  for  determining 

the  adequacy  of  combustion  air  for  an  installation 

can  be  found  in  the  current  revision  of  the  NFGC 

(ANSI  Z223.1  /  NFPA54). 

Consult  local  codes  for 

special  requirements

.  These  requirements  are  for 

US installations as found in the NFGC.

•  The requirements in Canada (B149.1) are structured 

differently.  In  Canada,  venting  shall  conform  to  the 

requirements of the current (CAN/CGA B149.1 or .2) 

installation codes. 

Consult local codes for special 

requirements.

Category IV Appliances

This furnace is classified as a “Category IV” appliance, 
which requires special venting materials and installation 
procedures. 

 

Category IV appliances operate with positive 

vent pressure and requires thoroughly sealed vent systems. 
They  also  produce  liquid  condensate,  which  is  slightly 
acidic and can cause severe corrosion of ordinary venting 
materials. Furnace operation can be adversely affected 
by restrictive vent and combustion air piping.

Summary of Contents for CMF95 Series

Page 1: ...l your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department WARNING RISQUE D INCENDIE OU D EXPLOSION Le non respec...

Page 2: ...Base 13 MA 100 Universal Base Installation 14 Installing the Furnace on an MA 100 Base 15 Condensate Drainage 15 GAS SUPPLY PIPING 16 Leak Check 16 High Altitude Application 17 Converting to LP Propan...

Page 3: ...ersonal injury or death This furnace must be installed in accordance with these instructions all applicable local building codes and the current revision of the National Fuel Gas Code ANSI Z223 1 NFPA...

Page 4: ...uses the appliance orequipment Behard wired batterypoweredorboth ShallcomplywithNFPA720 2005Edition c A product approved vent terminal must be used andifapplicable aproduct approvedairintakemust be us...

Page 5: ...tworkshouldbeappropriatelysizedtothecapacity of the furnace to ensure its proper airflow rating For installations above 2 000 ft the furnace should have a sea level input rating large enough that it w...

Page 6: ...SSEMENT RISQUE D EMPOISONNEMENT AU MONOXYDE DE CARBONED Le non respect des consignes suivantes portant sur chacun des appareils raccord s au syst me d vacuation mis en service pourrait entra ner l emp...

Page 7: ...t be known When estimating the length of vent runs consideration must be made to the effect of elbows and other fittings This is conveniently handled using the idea of equivalent length Thismeansthefi...

Page 8: ...mination to windows and building air intakes Vent and combustion air intake terminations must be located to ensure proper furnace operation and conformance to applicable codes A vent terminal must be...

Page 9: ...hown in Figure 4 The roof penetration mustbeproperlyflashedandwaterproofedwithaplumbing roof boot or equivalent flashing Vent and combustion air piping may be installed in an existing chimney which is...

Page 10: ...I VentilAire IV Figure 5 VentilAire III IV Vent Freezing Protection CAUTION When the vent pipe is exposed to temperatures below freezing i e when it passes through unheated spaces chimneys etc the pip...

Page 11: ...vent leakage It is good practice to seal all connections and joints with industrial grade sealing tape or liquid sealant Requirements for sealing ducts vary from region to region Consult with local co...

Page 12: ...CAUTION HAZARD OF ASPHYXIATION DO NOT COVER OR RESTRICT FLOOR RETURN AIR OPENING or equivalent For closet installation with less than 6 front clearance but not less than 1 a louvered door must be used...

Page 13: ...fastenthefrontofthefurnace and the base to the floor with 8 x 1 2 sheet metal screws FURNACE INSTALLATION NOTE Sinceallinstallationsaredifferent thesequenceof these steps may differ from the actual in...

Page 14: ...opening and center the top of the feeder duct in 14 1 8 x 14 1 8 floor opening 5 Using the feeder duct as a guide mark and cut a 12 x 12 opening in the supply duct Remove the base and transition feede...

Page 15: ...will cause improper operation or damage to the furnace It is recommended that all drain lines on the outside of the residence be wrapped with an industry approved insulation or material allowed by loc...

Page 16: ...l gas hookups are shown in Figure 12 Leak Check FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury or property damage Installation and service must be pe...

Page 17: ...nstallation may only be accomplished withfactorysuppliedorifices Donotattemptto drill out orifices in the field Improperly drilled orifices may cause fire explosion carbon monoxide poisoning personal...

Page 18: ...ple Elevation 5 000 feet Type of Gas Natural Gas Local Heating Value of Gas 750 From Table 10 find 750 and follow down the column stop at the 5 000 feet row The heating value listed is LOW Table 12 wi...

Page 19: ...ten until snug Make sure LP is visible after conversion Gas Pressure Verification Measuring the Supply Gas Pressure 1 Turn OFF the gas supply at the manual valve located on the outside of the unit 2 U...

Page 20: ...are lit check all gas connections for leaks again with the soap and water solution Measuring the Manifold Pressure The manifold pressure must be measured by installing a pressure gauge Manometer Magn...

Page 21: ...tothefurnace nameplate or Table 4 An electrical disconnect must be installed readily accessiblefromandlocatedwithinsightofthefurnace See Figure 18 page 29 or the wiring diagram label inside of the con...

Page 22: ...otection2 045 45 000 18 115 60 1 127 103 11 0 14 20 13 1 21 7 072 72 000 18 115 60 1 127 103 10 4 14 20 12 4 20 4 NOTE Minimum wire gauge and maximum fuse circuit breaker amperage are based on MCA1 an...

Page 23: ...e input rate in Btuh See example 6 The manifold pressure must be set to the appropriate valueforeachinstallationbyaqualifiedinstaller service agency or the gas supplier WARNING Do not attempt to drill...

Page 24: ...nutes before taking any temperature readings The temperature rise is the difference between the supply and return air temperatures Verifying Burner Operation CAUTION The door over the burners may only...

Page 25: ...alve and inducer remains energized The control goes to blower on delay 8 If flame is present the control energizes the blower on theselectedHEATspeed30secondsafterthegasvalve opened The gas valve and...

Page 26: ...piping at the furnace 6 Remove the piping between the gas valve and the ground joint union If applicable 7 Remove the burner box door 6 screws 8 Remove 4 screws securing the manifold assembly to the b...

Page 27: ...Fault Flash On Open Limit Switch Fault Flash Off Motor Fault On Off Diagnostic Description Yellow LED Low Flame Sensor Signal Continuous Flash Flame Present On Table 6 Control Board Fault Conditions...

Page 28: ...8 1 3 8 1 5 8 24 3 16 4 3 4 2 7 8 1 3 4 1 3 4 16 1 2 13 5 8 3 1 2 X 1 1 2 Slots for Gas Pipe Condensate drains Typ FRONT VIEW LEFT SIDE TOP VIEW BOTTOM VIEW 3 3 4 Dia 2 Places 32 2 7 8 Dia Hole for Li...

Page 29: ...SINGLE STAGE THERMOSTAT TO OUTDOOR UNIT FIELD WIRING LEGEND LOW VOLTAGE HIGH VOLTAGE WIRING DIAGRAM For 80 and 90 Single Stage Furnaces Refer to the Installation Instructions provided with the furnac...

Page 30: ...ER REVOLUTION OF GAS METER 1 5 10 10 360 1 800 3 600 12 300 1 500 3 000 14 257 1 286 2 571 16 225 1 125 2 250 18 200 1 000 2 000 20 180 900 1 800 22 164 818 1 636 24 150 750 1 500 26 138 692 1 385 28...

Page 31: ...T BTU 45 000 72 000 0 to 1 999 FT 49 47 2 000 to 2 999 FT 50 48 3 000 to 3 999 FT 50 48 4 000 to 4 999 FT 51 48 5 000 to 5 999 FT 51 49 6 000 to 6 999 FT 51 49 7 000 to 7 999 FT 52 50 8 000 to 8 999 F...

Page 32: ...ls All Clearances in this Figure apply on both walls G Clearance to inside corner All Clearances in this Figure apply on both walls All Clearances in this Figure apply on both walls H Clearance to eac...

Page 33: ...ble Wall Normal Snow Level COMBUSTION AIR Seal Caulk Around Pipes at Building 90 Elbow 7 12 Min 90 Elbow 90 Elbow Support System on Vertical Rise FLUE PIPE COMBUSTION AIR See Table 2 for PVC Pipe Leng...

Page 34: ...34...

Page 35: ...35...

Page 36: ...efully before starting the installation Return these instructions to the customer s package for future reference PROPOSITION 65 WARNING This product contains chemicals known to the state of California...

Reviews: