89
Warning
Fault
Message
Possible causes
Remedy
–––
E170
Hum. Sensor out of Range
The measured humidity in the cabin is outside the permissible
range.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After eliminating the fault, the
Condair Delta SPA Control Box or the Nordmann Omega must be
switched off and on again (depending on which device the fault has
occurred).
Wrong humidity sensor con-
nected.
Check that the correct humidity
sensor is connected.
Humidity sensor not connected
or not correctly connected.
Check/correctly connect the
wiring of the humidity sensor.
Incorrect configuration of the
humidity sensor in the control
software.
Check/correctly set the humidity
sensor settings in the control
software.
Humidity sensor defective.
Replace humidity sensor.
–––
E171
Hum. Sensor
Instable
Measurement of cabin humidity unstable.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After eliminating the fault, the
Condair Delta SPA Control Box or the Nordmann Omega must be
switched off and on again (depending on which device the fault has
occurred).
Unstable humidity measurement
due to manipulation of the humi-
dity sensor in the cabin.
Check humidity sensor in the
cabin.
–––
E172
Bench Sensor out of Range
The measured bench temperature in the cabin is outside the per-
missible range.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After eliminating the fault, the
Condair Delta SPA Control Box or the Nordmann Omega must be
switched off and on again (depending on which device the fault has
occurred).
Wrong temperature sensor
connected.
Check if the correct temperature
sensor is connected.
Temperature sensor not or not
correctly connected.
Check/correctly connect the wi-
ring of the temperature sensor.
Incorrect configuration of the
temperature sensor in the con-
trol software.
Check/correctly set temperature
sensor settings in the control
software
Temperature sensor defective.
Replace temperature sensor.
–––
E173
Wall Sensor out of Range
The measured wall temperature in the cabin is outside the permis-
sible range.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After eliminating the fault, the
Condair Delta SPA Control Box or the Nordmann Omega must be
switched off and on again (depending on which device the fault has
occurred).
Wrong temperature sensor
connected.
Check if the correct temperature
sensor is connected.
Temperature sensor not or not
correctly connected.
Check/correctly connect the wi-
ring of the temperature sensor.
Incorrect configuration of the
temperature sensor in the con-
trol software.
Check/correctly set temperature
sensor settings in the control
software
Temperature sensor defective.
Replace temperature sensor.