82
8.2
Fault indication
Fault indication on the Nordmann Omega
without
SPA Display:
Malfunctions during operation detected by the control software are indicated by the
yellow illuminated
LED
(warning present or maintenance due) or the
red illuminated LED
(fault present) above the unit
switch.
Note: The current warning and/or fault messages can be interrogated via the integrated web interface
and a web browser. For that purpose, a laptop must be connected to the Nordmann Omega. Please
refer to the notes in the separate web interface manual.
Fault indication on the Nordmann Omega
with
SPA Display:
Malfunctions during operation detected by the control software are indicated by the
yellow illuminated
LED
(warning present or maintenance due) or the
red illuminated LED
(fault present) above the unit
switch and by the
yellow or red warning triangle
in the upper left corner of the display.
Warning (maintenance indication)
Warnings and/or a due maintenance are indicated by the yellow warning
triangle in the home screen and the yellow illuminated LED above the unit
switch. The Nordmann Omega continues operation. Depending on the type
of warning, certain operational restrictions may occur.
Fault
Operational states where further operation is limited or not possible, or where
further operation would damage the system are indicated by the red warn-
ing triangle in the home screen and the red illuminated LED above the unit
switch. Depending on the type of fault the steam production is stopped or the
Nordmann Omega continues normal operation.
By pressing on the warning triangle the error list is shown with all active warning and fault messages. By
pressing on the corresponding Warning or Fault entry additional information regarding the malfunction
are displayed (see display on the far-right).
Fault 20
Fault 22
Warning 54
Error List
Safety Loop
2018-11-06 10:15:09
ServiceId: 0, ModuleId: 10
External safety chain is open.
Fault 20