Malfunction list
Most operational malfunctions are not caused by faulty equipment but rather by improper installation or
disregarding of planning guidelines. Therefore, a complete fault diagnosis always involves a thorough
examination of the entire system (e.g. hose connections, control system, etc.).
Warning
Fault
Message
Possible causes
Remedy
W14
–––
Max Door Open
The cabin door was open too long.
Note: The Condair Delta SPA Control Box or the Nordmann Omega
automatically disconnect all heating systems (steam, bench hea-
ting, sauna heater, etc.) until the cabin door is closed again.
The cabin door was open longer
than the set "Door open" time.
Close the cabin door.
–––
E18
Cabin Temp. Sensor
Instable
Measurement of cabin temperature unstable.
Note: The operation of the Condair Delta SPA Control Box or
Nordmann Omega is stopped. After eliminating the fault, the
Condair Delta SPA Control Box or the Nordmann Omega must be
switched off and on again (depending on which device the fault has
occurred).
Unstable temperature measure-
ment due to manipulation of the
temperature sensor in the cabin.
Check temperature sensor in the
cabin.
–––
E20
Safety loop
External safety loop is open.
Note: The Condair Delta SPA Control Box or the Nordmann
Omega go into standby operation. As soon as the external safety
loop is closed again the Condair Delta SPA Control Box and the
Nordmann Omega continue to work normally.
One or more monitoring
device(s) of the external safety
loop has/have triggered.
Check the monitoring device(s)
of the external safety loop.
External safety loop not connec-
ted correctly.
Let have the wiring of the external
safety loop be checked and cor-
rectly connected by an electrician.
–––
E21
Max. level
Water level in the steam tank of the Nordmann Omega too high.
Note: The operation of the Nordmann Omega is stopped. After the
fault has been eliminated, the Nordmann Omega must be swit-
ched off and on again. If the Nordmann Omega is controlled by a
Condair Delta SPA Control Box, the Condair Delta SPA Control Box
must also be switched off and on again after the Nordmann Omega
has been restarted.
Level unit calcified.
Clean level unit.
Hose connections between level
unit and steam tank blocked.
Check/clean hose connections
between level unit and steam
tank blocked.