36
S
ection
4
622293 Roof cap.
616319 Exhaust vent
0 - 1 in. clearance max.
Distance between the top of the
lower vent opening and bottom of
baffle 4¼ to 4¾ in..
Bottom baffle
0 - 1 in. clearance max.
621156 Vent
Vent even or below enclosure floor
1/4 in. clearance max.
Aluminum or galvanized steel sheet baffle
full width of enclosure.
Wood, aluminum or galvanized steel
sheet solid baffle.
Full width of enclosure
Starts 18 to 18½ from enclosure floor
Fans
Figure 4-4. —Roof venting - Exhaust vent centered over cooling system, enclosure depth
more than 26 in. - Box baffle required.