28
Figure 30 – 44658-51 Interface Board Configuration Switch
Figure 31 –DAH valve (left) and DH valve (right)
If the switch is not turned on for DH
hydraulics, the boom slant will not
function.
8.
Connect the NORAC C12A between the J4
connection on the HARDI PCB and the blue
wiring harness.
a)
Remove the blue harness from J4 (37-pin
DB male socket) on the PCB inside of
the Job-com.
b)
Insert the 37-pin DB female socket on
the PCB of the interface cable (
C12A
)
into
J4
. Screw it down to
J4.
This
requires removing the small nuts on the
DB-37 connector.
c)
Insert the blue-wire harness into the 37-
pin DB male socket on the other side of
the PCB of
C12A
. Screw it down to the
socket.
Figure 32 – J1, J2 and J4 on HARDI DAH
Board
Do not connect spade connectors to
J1&J2 until step 9.
ON
Summary of Contents for UC4+ Roll Control
Page 11: ...7 Figure 4 Hydraulic Plumbing Schematic ...
Page 40: ...36 6 3 ITEM C3 44656D CABLE VALVE VARIABLE RATE DT ...
Page 41: ...37 6 4 ITEM C10 44658 52 CABLE UC4 BC POWER C10 HARDI ...
Page 42: ...38 6 5 ITEM C11 44658 50 CABLE UC4 BC EXTENSION C11 HARDI ...
Page 43: ...39 6 6 ITEM C12A 44658 51 CABLE UC4 BC INTERFACE HARDI DAH ...
Page 44: ...40 6 7 ITEM C12 44658 78 CABLE UC4 BC INTERFACE HARDI DAH 09 ...