5.1 Learning
“START” command
11
WARNING!!
The gate must be closet.
1
Put the DIP5 in ON
The gate is CLOSED
2
Press the command START
The gate STARTS OPENING
3
When the gate reach the closing limit switch ( FCC) the
motor
stops.
The gate STOPS
4
Count the time for the opening gate
PAUSE TIME
5
Press the control START to close the gate.
The gate CLOSES.
6
Wait until the gate stops automatically.
The gate is CLOSED
7
Put the Dip5 in OFF position for the standard mode. The signal light turns off
and the led TEST starts
End of the programming
5
7 4
6
5
7 4
6
5.2 Times learning with the
PARTIAL OPENING COMMAND
WARNING!!
The gate must be closed.
1
Put the DIP5 in ON
The gate is CLOSED
2
Press the PARTIAL OPENING command.
The gate start OPENING.
4
Press the PARTIAL OPENING command to stop the gate and count the
opening time.
PAUSE TIME
5
Press the PARTIAL OPENING command to start closing.
The gate starts CLOSING.
6
Wait until the gate stops automatically
The gate is CLOSED
7
Put the DIP 5 in ON to get to the standard mode.
The signal light turn off and the LED info starts.
End of the programming
5
7 4
6
5
7 4
6
The PEDONALE (partial opening control ) can be used to permit the passage for people or small vehicles .
5