.19.
.18.
5.
Installation
5.
Installation
5.3.3 Connect grid side of inverter
B) Insert the cable through the jacket and cap nut of connector, then insert the wires to the grid
terminal and tighten the screws on the connector (see figure 5.22).
Please try to pull out the wire to make sure it is well connected.
Internal of AC connector signs "L1","L2","L3","N" and "PE " five connection
ports (see Figure 5.20). Three live wires are connected the "L1", "L2"and
"L3" terminals respectively; ground wire connects "PE "; neutral wire
connects "N" terminal:
Figure 5.23 AC connector to inverter
For all AC connections, 2.5 – 6 mm², 105°C cable is required to be used. Please make sure the
resistance of cable is lower than 1.50hm. If the wire is longer than 20m, preferred to 6mm² cable.
Please fixed cable with PH1 cross screwdriver.
Each inverter has a corresponding AC grid terminal connector. See figure 5.19.
Figure 5.19
AC Grid Terminal Connector
Figure 5.20
AC Grid Terminal Connector Inside
L3
N
L1
PE
The steps to assemble AC grid terminal connector are listed as follows:
A) Strip the end of AC wire about 8mm. See figure 5.21 left.
Figure 5.21 Connect Wires to the Grid Terminal
Figure 5.22 Connected cable
C) Assemble the connector and tighten up cap on the terminal. See Figure 5.21 right.
D) Connect AC grid terminal connector to the inverter, small click will confirm that connection
is appropriate. (see figure 5.23)
PH1 cross screwdriver
L2