background image

9. Trouble Shooting

9. Trouble Shooting

Alarm Message

OV-G-V01/02/03/04

OV-G-F01/02

UN-G-F01/02

G-IMP

NO-GRID

OV-DC01/02/03/04

OV-BUS

UN-BUS01/02

GRID-INTF01/02

INI-FAULT

OV-TEM

Failure description

Over grid voltage

Under grid voltage

Over grid frequency

Under grid frequency

High grid impedance

No grid voltage 

Over DC voltage 

Over DC bus voltage

Under DC bus voltage

Grid interference

Initialization system fault

Over Temperature 

Solution

1.Resistant of AC cable is too high. 
   Change bigger size grid cable
2.Adjust the protection limit if it’s 
   allowed by electrical company.

1.Check connections and grid switch.
2.Check the grid voltage inside inverter 
    terminal.

1.Reduce the module number in series

1.Restart inverter
2.Change power board

1.Check PV input connections
2.Check DC input voltage 
    (single phase >120V, three phase >350V)
3.Check if PV+/

-

 is reversed

Inverter no power 
on LCD

No power 

LCD show initializing 
all the time

Can not start-up

1.Check if the connector on main 
    board or

 

power board are fixed.

2.Check if the DSP connector to 
    power board

 

are fixed.

1.Check inverter surrounding ventilation.
2.Check if there’s sunshine direct on 
    inverter in hot weather.

1.Use user define function to adjust the 
   protection limit if it’s allowed by 
   electrical company.

1.Check inverter inductor connection
2.Check driver connection

1.Restart inverter or contact installer.

UN-G-V01/02

DC-INTF

DC input overcurrent

1.Restart inverter

2.Identify and remove the string to the fault MPPT  
2.Change power board

IGFOL-F

Grid current tracking fail

OV-G-I

Over grid current

OV-DCA-I

IGBT-OV-I

Over IGBT current

12Power-FAULT

12V power supply fault

1.Restart inverter or contact installer.

IG-AD

Grid current sampling fail

DSP-B-FAULT

Comm. failure between main 
and slave DSP

Table 9.1 Fault message and description

1.Remove all DC input, reconnect and
    restart inverter one by one.
2.Identify which string cause the fault and 
   check the isolation of the string.

DCinj-FAULT

High DC injection current

1.Check AC and DC connection
2.Check inverter inside cable connection.

1.Restart inverter or contact installer.

Alarm Message

Failure description

Solution

PV ISO-PRO
01/02

PV isolation protection

ILeak-PRO
01/02/03/04

Leakage current protection 

RelayChk-FAIL

Relay check fail

NOTE: 

If the inverter displays any alarm message as listed in Table 9.1; please 
turn off the inverter (refer to Section 5.2 to stop your inverter) and wait for 5 
minutes before restarting it (refer to Section 5.1 to start your inverter). If the 
failure persists, please contact your local distributor or the service center. 
Please keep ready with you the following information before contacting us.

1.  Serial number of Solis Three Phase Inverter;

2.  The distributor/dealer of Solis Three Phase Inverter (if available);

3.  Installation date.

4.  The description of problem (i.e. the alarm message displayed on the LCD and the status 

    of the LED status indicator lights. Other readings obtained from the Information submenu 

    (refer to Section 6.2) will also be helpful.);

5. The PV array configuration (e.g. number of panels, capacity of     panels, number of strings

    , etc.);

6. Your contact details.

AFCI self-detection 
(model with AFCI 
module) 

AFCI module self-detect fault

1.Restart inverter or connect technician.

Arcing protection
(model with AFCI 
module) 

Detect arc in DC circuit

1. Check inverter connection whether arc 
    exists and restart inverter.

.33.

.32.

Summary of Contents for Solis 4G

Page 1: ...Ltd Ningbo Ginlong Technologies Co Ltd No 57 Jintong Road Binhai Industrial Park Xiangshan Ningbo Zhejiang 315712 P R China Tel 86 0 574 6578 1806 Fax 86 0 574 6578 1606 If you encounter any problem...

Page 2: ...ts 3 3 Keypad 3 4 LCD 5 Installation 5 1 Select Location for the Inverter 5 2 Mounting the Inverter 5 3 Electrical Connections 7 Operation 6 Start Stop 6 1 Start the Inverter 6 2 Stop the Inverter 1 1...

Page 3: ...ctor x2 User manual x1 Installation and Operation Manual Solis 4G Three Phase Inverter 5 10kW Ver 1 1 Ginlong Ningbo Technologies Co Ltd 1 Introduction 1 Introduction If anything is missing please con...

Page 4: ...h the local and national electrical safety standards WARNING Please don t connect PV array positive or negative to ground it could cause serious damage to the inverter CAUTION The PV array Solar panel...

Page 5: ...ys The keypad is used for Scrolling through the displayed options the UP and DOWN keys Access to modify the adjustable settings the ESC and ENTER keys The two line Liquid Crystal Display LCD is locate...

Page 6: ...not blocked Exposure to direct sunlight will increase the operational temperature of the inverter and may cause output power limiting Ginlong recommends inverter installed to avoid direct sunlight or...

Page 7: ...ed hexagon head tapping screws HJ0108 10 50mm fished expandable tubular using the percussion drilling with the 10mm drill need to stay vertically on the wall And the drill hole must be vertically on t...

Page 8: ...5 3 Electrical Connections Inverter designs quick connect terminal so top cover needn t open during electrical connection The sign meaning located the bottom of inverter as shown below in table 5 1 Al...

Page 9: ...el all inverters should be connected to the same ground point to eliminate the possibility of a voltage potential existing between inverter grounds B insulation stripping length is 2mm 3mm longer than...

Page 10: ...the Inverter The steps to assemble the DC connectors are listed as follows 1 Strip off the DC wire for about 7mm Disassemble the connector cap nut see Figure 5 13 3 Crimp the contact pin to the wire...

Page 11: ...e is required to be used Please make sure the resistance of cable is lower than 1 50hm If the wire is longer than 20m preferred to 6mm cable Please fixed cable with PH1 cross screwdriver Each inverter...

Page 12: ...ion 6 Start Stop 6 1 Start the Inverter To start up the Inverter it is important that the following steps are strictly followed 1 Switch the grid supply main Switch AC ON first 2 Switch the DC switch...

Page 13: ...ing the ENTER key locks Figure 7 2 a or unlocks Figure 7 2 b the screen b a Figure 7 2 Locks and Unlocks the Screen of LCD 7 Operation 7 Operation Table 7 1 Information list V_DC1 350 8V I_DC1 5 1A V_...

Page 14: ...ter menu Advanced Info and Advanced settings need password Select Advanced Info from the Main Menu The screen will require the password as below YES ENT NO ESC Password 0000 Figure 7 5 Enter password...

Page 15: ...s history of changing settings Only for maintance personel 7 4 7 Communication Data The screen shows the internal data of the Inverter see Figure 7 14 which is for service technicians only 01 05 01 25...

Page 16: ...is function is used to set the new password for menu Advanced info and Advanced information see Figure 7 18 Figure 7 18 Set new password YES ENT NO ESC Password 0000 Enter the right password before se...

Page 17: ...international grid tied standards and safety and electromagnetic compatibility requirements Before delivering to the customer the inverter has been subjected to several tests to ensure its optimal ope...

Page 18: ...BT current 12Power FAULT 12V power supply fault 1 Restart inverter or contact installer IG AD Grid current sampling fail DSP B FAULT Comm failure between main and slave DSP Table 9 1 Fault message and...

Page 19: ...60 850 Start up voltage Volts 180 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts M...

Page 20: ...160 850 Start up voltage Volts 180 Max short circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 N PE 400 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts...

Page 21: ...ort circuit input current Amps Rated DC voltage Volts Rated grid frequency Hertz 3 PE 208 220 240 47 52 or 57 62 Max DC input voltage Volts MPPT voltage range Volts Max input current Amps MPPT number...

Reviews: