![background image](http://html.mh-extra.com/html/nidec/unidrive-m600/unidrive-m600_user-manual_1687782087.webp)
SI-Ethernet User Guide
87
Issue: 3
Sa
fe
In
Me
ch
E
G
Par
amet
er
Key
an
PC T
Sec
Di
G
Ind
ex
This parameter defines the allowable network delay (in milliseconds) for the Easy Mode
synchronous transmit cyclic links to arrive at their destination.
This parameter defines the action to be taken when a late synchronized frame is received on the
Rx1 link.
Defines the destination (slot) to trigger the event when a late synchronized frame is received on the
S.11.030
Easy Mode Maximum Network Delay
Minimum
1
Maximum
100
Default
3
Units
ms
Type
8 Bit User Save
Update Rate
Read on reset
Display Format
None
Decimal Places
0
Coding
RW, BU
S.11.040
Rx1 Late Sync Frame Action
Minimum
1
(Display: Trip)
Maximum
3
(Display: Use)
Default
1
(Display: Trip)
Units
None
Type
8 Bit User Save
Update Rate
Read on reset
Display Format
None
Decimal Places
0
Coding
RW, Txt, BU
Value
Text
Description
1
Trip
Trip drive with Slx.Er and sub-trip code
2
Do not use
The data is ignored
3
Use
The data is used immediately
S.11.041
Rx1 Late Sync Frame Dest
Minimum
0
(Display: This slot)
Maximum
4
(Display: Slot 4)
Default
0
(Display: This slot)
Units
None
Type
8 Bit User Save
Update Rate
Read on reset
Display Format
None
Decimal Places
0
Coding
RW, Txt, BU
Value
Text
Description
0
This slot
Trigger module event in this slot
1
Slot 1
Trigger module event in slot 1
2
Slot 2
Trigger module event in slot 2
3
Slot 3
Trigger module event in slot 3
4
Slot 4
Trigger module event in slot 4