Ethernet sub trip codes
If the Ethernet interface detects an alarm condition during operation, it will set the appropriate bit in
Active Alarm Bits
MM.009
shows the possible
conditions.
Table 10-4 Ethernet alarm bits
10.5
Ethernet hardware fault trip codes
If the Ethernet interface detects an internal hardware error, it will force a SlotX.HF (code 250) trip
on the drive with an appropriate sub trip string. Table 10-5 shows the possible error codes and sub
trip strings.
Table 10-5 Ethernet hardware fault trip codes
Recommended actions:
Ensure the option module is installed correctly.
•
Replace the option module.
•
Replace the drive.
Bit
(Pr MM.009)
Alarm
Description
0
User Program
The user program has generated an alarm
1
eCMP
An eCMP alarm has been generated
2
Modbus
A Modbus alarm has been generated
3
Ethernet/IP
An Ethernet/IP alarm has been generated
4
Reserved
Reserved
5
File System
File system full alarm has been generated
6
Too Hot
Temperature too high alarm has been generated
Value
Pr 0.10.070
Reason
1
The module category cannot be identified
2
All the required customisable menu table information has not been supplied or the
tables supplied are corrupt
3
There is insufficient memory available to allocate the comms buffers for this module
4
The module has not indicated that it is running correctly during drive power-up
5
The module has been removed after power-up or it has ceased to indicate to the
drive processor that it is still active
6
The module has not indicated that it has stopped accessing drive parameters
during a drive mode change
7
The module has failed to acknowledge that a request has been made to reset the
drive processor
8
The drive failed to read correctly the menu table from the module during drive power-up
9
The drive failed to upload menu tables from the module and timed-out (5s)
10
Menu table CRC invalid