Programmable Parameters
12E –
Devicenet Address
Range:
0 - 63
Default:
0
Description:
Sets the DeviceNet network address for the soft starter.
12F –
Devicenet Baud Rate
Options:
125 kB (default)
250 kB
500 kB
Description:
Selects the baud rate for DeviceNet communications.
12G –
Profibus Address
Range:
1 - 125
Default:
1
Description:
Sets the Profibus network address for the soft starter.
12H –
Gateway Address
Range:
0 - 255
Default:
192
Description:
Sets the first component of the network gateway address. The gateway
address is set using parameters 12H~12K and the default address is
192.168.0.100.
12I –
Gateway Address
2
Range:
0 - 255
Default:
168
Description:
Sets the second component of the network gateway address.
12J –
Gateway Address
3
Range:
0 - 255
Default:
0
Description:
Sets the third component of the network gateway address.
12K –
Gateway Address
4
Range:
0 - 255
Default:
100
Description:
Sets the fourth component of the network gateway address.
NOTE
The network address can also be set via the Network Address options in the Setup
Tools. See
Network Address
on page 29 for details.
12L –
IP Address
Range:
0 - 255
Default:
192
Description:
Sets the first component of the soft starter's IP address, for Ethernet
communications. The IP address is set using parameters 12L~12O and the
default address is 192.168.0.2.
12M –
IP Address
2
Range:
0 - 255
Default:
168
Description:
Sets the second component of the soft starter's IP address, for Ethernet
communications.
12N –
IP Address
3
Range:
0 - 255
Default:
0
Description:
Sets the third component of the soft starter's IP address, for Ethernet
communications.
60