Installation
Reset/Starter Disable
The reset input (10, 11) is normally closed by default. The soft starter will not perform a
start if the reset input is open. The display will show "Not Ready".
If the reset input opens while the soft starter is running, the starter will remove power and
allow the motor to coast to stop.
NOTE
The reset input can be configured for normally open or normally closed operation.
Use parameter 7I
Reset/Enable Logic
.
Start/Stop
The soft starter requires two-wire control.
A
B
17622.
A
A
Reset
B
Start/Stop
WARNING
If the start input is closed when control voltage is applied, the starter will attempt to
start.
Check that the start/stop input is open before applying control voltage.
NOTE
The soft starter will only accept commands from the control inputs if parameter 1A
Command Source
is set to Digital Input.
Programmable Inputs
The programmable inputs (13, 14 and 13, 15) allow external equipment to control the
starter.
The operation of the programmable inputs is controlled by parameters 7A~7H.
USB Port
The USB port can be used to upload a configuration file, or download parameter settings
and event log information from the starter. See
USB Save & Load
on page 28 for details.
20