![background image](http://html1.mh-extra.com/html/nidec/digistart-d4/digistart-d4_user-manual_1687788019.webp)
System Design
Inputs
Input rating .......................................................................... Active 24 VDC, 8 mA approx
Motor thermistor (B4, B5) ...................................................... Trip >3.6 k
Ω
, reset <1.6 k
Ω
Outputs
Relay outputs ............................ 10 A @ 250 VAC resistive, 5A @ 250 VAC AC15 pf 0.3
Main contactor/Shunt relay (33, 34) ................................................... Normally Open
Relay output A (41, 42, 44) ..................................................................... Changeover
Relay output B (53, 54) ...................................................................... Normally Open
Analog output (21, 22)
Maximum load ................................................................... 600
Ω
(12 VDC @ 20 mA)
Accuracy ............................................................................................................ ± 5%
Environmental
Operating temperature ...................................... -
10 ˚C~60 ˚C,
above 40
˚C with derating
Storage temperature ................................................................................ -25 °C~+ 60 °C
Operating Altitude ............................................... 0~1000 m, above 1000 m with derating
Humidity ................................................................................ 5%~95% Relative Humidity
Pollution degree .................................................................................. Pollution Degree 3
Vibration ................................................................................................... IEC 60068-2-6
Protection
0024B~0135B ..................................................................................................... IP20
0184B~0580B ..................................................................................................... IP00
Heat dissipation
During Start .................................................................................... 4.5 watts per ampere
During Run
0024B~0052B ................................................................................
≤ 35 watts approx
0064B~0135B ................................................................................
≤ 50 watts approx
0184B~0250B ..............................................................................
≤ 120 watts approx
0352B~0580B ..............................................................................
≤ 140 watts approx
Motor Overload Protection
Default: The default settings of parameters 1C, 1D and 1E provide Motor Overload
Protection: Class 10, Trip Current 105% of FLA (full load amperage) or equivalent.
Certification
CE .............................................................................................................. EN 60947-4-2
C-UL ................................................................................................. C22.2 Nº 60947-4-2
UL .............................................................................................................. UL 60947-4-2
Operational life (internal bypass contacts)
..................................................................................................... 100 000 operations
3.15 Disposal Instructions
Equipment containing electrical components may not be disposed of
together with domestic waste.
It must be collected separately as electrical and electronic waste
according to local and currently valid legislation.