background image

28

     

  

   www.hysecurity.com

16 - TROUBLESHOOTING (CONT.)

Table 4: 1050 Board Display Read Out and Troubleshooting 

DISPLAY 

REASON

POSSIBLE SOLUTION 

Dynamic M1

Dynamic M2

Static M1

Static M2

Input UL/Edge

Photo Test FAIL!

Device Error

Gate Opened

BlueBus or

Input - Activated

Hard Shut Down

Overload

Slide Requires -

Min 2 Sensors

1 Open & 1 Cls -

Sensor Required

Min. 1 Sensor -

For Swing Gate!

BlueBus Error!

Scanning BluBus -

Prs Disp to Cncl 

Input STOP!

Actuated connected to Motor 

1 has a brief current spike and 

tripped Type A sensor.

Actuated connected to Motor 

2 has a brief current spike and 

tripped Type A sensor.

Actuated connected to Motor 1 

has an extended current spike 

and tripped Type A sensor.

Actuated connected to Motor 2 

has an extended current spike 

and tripped Type A sensor.

UL/Edge input is tripped while gate 

is running. Appears is IN1 or IN2 

input is tripped if configured as a 

pulsed, external sensor input.

BlueBus monitored sensor check 

fails.

Position sensor is not being correctly 

detected by the board or if there is 

an active input on the board prevent-

ing the learn process.

Appears during Learn Mode if Open 

Limit is active.

Appears when active BlueBus or 

other external entrapment sensor 

input is preventing gate motion.

Appears when Dynamic and/or 

Static sensors have two sonsecutive 

trips.

Appears when Motor 1 or Motor 2 

over-current.

Appears when there are not at least 

two external entrapment sensors 

programmed and installed on a Slide 

Gate:

1. Open direction

2. Close direction.

Appears when Slide Gate operator 

does not at have at least one exter-

nal entrapment sensor programmed 

and installed in each direction.

Appears when Swing gate operator 

does not have at least one entrap-

ment sensor programmed and 

installed for both open and close 

direction for travel.

Appears when previously learned 

numbers and type of BlueBus sen-

sors change.

Appears when initial BlueBus learn 

procedure is in process.

STOP input is not connect to GND.

Check for obstruction in gate path or degraded gate hardware.

Check for obstruction in gate path or degraded gate hardware.

Check for obstruction in gate path or degraded gate hardware.

Check for obstruction in gate path or degraded gate hardware.

Ensure photo eyes are aligned, edges are not tripped, and all inputs are pro-

grammed correctly.

Verify photo eye is connected, aligned, and internal jumpers are set correctly.

Ensure Motor 1 and Motor 2 position sensors are connected correctly for the type 

of actuator being used. Also make sure there are no active inputs.

Change gate to mid-travel and restart the learn process.

Ensure all sensors are connected correctly and properly aligned.
Ensure all inputs are programmed correctly.

Press the Reset/Hard Shut Down button to clear the trip and reenable gate oper-

ation.

Ensure motors are connected properly and there is no obstruction to gate move-

ment.

Ensure all sensors are connected correctly and functional.
Does not appear on Swing gates.

Ensure all sensors are connected correctly and functional.
Does not appear on Swing gates.

Install minimum number of sensors.
Does not appear on Slide Gates

Correct wiring/number of sensors and redo the learn procedure for the operator.

Pressing the Display button will postpone the scan and remain in Learn Mode.
Pressing and holding the open or close buttons will move the gate in the desired 

direction.

Ensure jumper wire is being used and check external stop button wiring.

Summary of Contents for TITAN12L

Page 1: ...Actuator Vehicular Swing Gate Actuator TITAN12L 936 Control Board TITAN12L1 1050 Control Board CBOX with 1050 control board CBOX with 936 control board 912L Programming controls connections and safet...

Page 2: ......

Page 3: ...al Release Handle 20 FIGURE 10 9 Wire Harness Insertion 20 FIGURE 10 10 TITAN12L 12L1 Actuator Wiring 20 10 6 936 Control Board Wiring 21 10 6 1 TITAN ACTUATOR WIRING PULL TO OPEN 21 10 6 2 TITAN ACTU...

Page 4: ...AN12L 12L1 gives dealers installers and homeowners the ability to take control of their access and security systems This actuator includes a 2 year factory warranty against manufacturing defects and l...

Page 5: ...input and the solar charge input All settings are stored in non volatile memory that is protected from power outages Programmable slowdown position Built in current sensing provides inherent gate forc...

Page 6: ...g or locking the gate Gate opening and closing speed acceleration soft start settings and reversing speed may be set to factory default settings or individually programmed per customized gate installa...

Page 7: ...security and reliable operation it is essential these components operate together as a system It is the responsibility of the system designer and or installer to ensure any safety or operational issue...

Page 8: ...four single family dwellings 2 1 2 Class II Commercial General Access Gate Operator Intended for use in a commercial location or building such as a multi family housing units ve or more single family...

Page 9: ...is supplied between the gate and adjacent structures when opening and closing to reduce entrapment risk Swinging gates shall not open into public access areas 2 6 The gate must be properly installed a...

Page 10: ...hicle detectors but should be wired accordingly 4 Gate Construction and Safety Gate construction plays a very important role in ensuring the safety of any automated gate system The standard for gate c...

Page 11: ...in the gate and in that portion of the adjacent fence that the gate covers in the open position The gate panel shall include the entire section of the moving gate including any back frame or counterba...

Page 12: ...ned constructed and installed in accordance with security related parameters speci c to the application in question 5 Maintenance of Gate Systems To keep your automated gate system performing both saf...

Page 13: ...ing gate and the ground is greater than 4 in 101 6 mm and less than 16 in 406 mm or b The distance between the center line of the pivot and the end of the wall pillar or column to which it is mounted...

Page 14: ...lose direction provided the gate in the open direction presents no risk of entrapment Slide Gates One sensor in the Open direction and one sensor in the Close direction The gate operator tests for the...

Page 15: ...WINDOW PROGRAM MENU CONTROL BUTTONS GATE OPERATION CONTROL BUTTONS ACCESSORY POWER OUTPUTS OUTPUTS POWER INPUT CONNECTIONS MOTOR CONTROLS 30A EARTH GROUND CONNECTION ACCESSORY POWER OUTPUTS and PROGRA...

Page 16: ...OTOR SERIES 1050 MOTOR 2 BATTERY SOLAR P OXI A Receiver UL325 Compliant Monitored Safety Devices s required Accessory Output Connections Power Input Connections Motor Output Connections BlueBus Connec...

Page 17: ...eometry and rate of speed of the gate it is critical that the measurements below are followed The pivot arm may need to be cut to achieve the correct placement of the actuator mounting hole Measuremen...

Page 18: ...The pivot arm may need to be cut to achieve the correct placement of the actuator mounting hole Measurements are taken from the center of pivot of the gate hinge DIRECTION OF OPENING GATES CLOSED HING...

Page 19: ...al operation is possible NOTE Manual operation may be prevented if the actuator is fully retracted FIGURE 10 6 MANUAL RELEASE DISENGAGE FIGURE 10 7 MANUAL RELEASE RE ENGAGE MANUAL RELEASE RE ENGAGE 1...

Page 20: ...om of the actuator loosen the strain relief nut and insert the wire into the actuator housing The connections are on the top of the actuator behind the limit assembly Terminal block for harness connec...

Page 21: ...e actuator with the shorter cable must plug into Motor 1 connections 10 6 2 TITAN ACTUATOR WIRING PUSH TO OPEN 10 6 1 TITAN ACTUATOR WIRING PULL TO OPEN 10 INSTALLATION PROCEDURES CONT GREEN ORANGE BL...

Page 22: ...or a dual leaf swing gate installation For dual actuators the actuator with the shorter cable must plug into Motor 1 connections 10 7 2 TITAN ACTUATOR WIRING PUSH TO OPEN 10 7 1 TITAN ACTUATOR WIRING...

Page 23: ...ked Limit 1 Open or Limit 2 Open if using motor 2 illuminate red indicating the open limit is active for a pull to open ii The LED marked Limit 1 Close or Limit 2 Close if using motor 2 illuminate red...

Page 24: ...ELLS Possible Entrapment Zones Typical Installation Diagram Utilizing Photocells Safety Loop for vehicle Detection Only Safety Loop for vehicle Detection Only 4 Min from closed gate Loop Shadow Loop E...

Page 25: ...ment protection DURING INSTALLATION DISCONNECT POWER at the control panel before making any electric service power connection Be aware of all moving parts and avoid close proximity to any pinch points...

Page 26: ...nt is required to ensure continuous functionality safety and to ensure reliable operation in all weather conditions Inspect electrical assemblies and wiring installations for damage general condition...

Page 27: ...r Adjust Force Settings Check the input LEDs Any ON will hold the gate open and indicates a problem with a keying device Check the external entrapment devices Any activated devices will hold the gate...

Page 28: ...d in each direction Appears when Swing gate operator does not have at least one entrap ment sensor programmed and installed for both open and close direction for travel Appears when previously learned...

Page 29: ...ting the force or the limit of travel retest the gate operator Failure to adjust and retest the gate operator properly can increase the risk of injury or death 4 V ri ez le fonctionnement de l ouvre b...

Page 30: ...rian usage Locate the gate such that persons will not come in contact with the vehicular gate during the entire path of travel of the vehicular gate L ouvre barri re est destin n tre install que sur d...

Page 31: ...la barri re Chaque tiquette doit tre visible des personnes situ es de chaque c t de la barri re sur laquelle l tiquette est install e For gate operators utilizing a non contact sensor Pour les ouvre...

Page 32: ...adiofr quence RF l ouvre barri re pour pr venir le coincement doit tre situ un endroit o la transmission des signaux ne sera pas obstru e ou g n e par des structures des arbres ou d autres obstacles s...

Page 33: ...www hysecurity com 33...

Page 34: ...34 www hysecurity com...

Page 35: ...www hysecurity com 35...

Page 36: ...36 www hysecurity com Contact us Nice 6705 S 209th St Suite 101 Kent WA 98032 2327 Ph 1 253 867 3700 Fax 1 253 867 3702 www hysecurity com www facebook com hsgateoperators...

Reviews: