background image

6

2.3.3) Constant resistance STOP input

It enables the connection to the control unit of devices with 8.2K

constant resistance (e.g. sensitive edges)

The input measures the value of the resistance and disables the manoeuvre when the resistance is outside the nominal value 
The control unit is supplied with 8.2K

resistance connected to the input, which simulates the resistance of the devices even if the input is

not used; the resistance must of course be removed when connecting a device with 8.2K

output.

Also devices with normally open “NO” or normally closed “NC” contacts, or multiple devices, even of different type, can be connected to the
constant resistance STOP input, provided that appropriate arrangements are made.

For this purpose, refer to the following the table:

Note 1.

Any number of NO devices can be connected to each other in parallel, with an 8.2K

termination resistance

Note 2.

The NO and NC combination can be obtained by placing the two contacts in parallel, and placing in series to the NC contact an 8.2K

resi-

stance (therefore, the combination of 3 devices is also possible: NO, NC and 8.2K

).

Note 3.

Any number of NC devices can be connected in series to each other and to an 8.2K

resistance.

Note 4.

Only one device with 8.2K

constant resistance output can be connected; multiple devices must be connected in cascade with a single

8.2K

termination resistance (see 11. What to do if…)

if the constant resistance STOP input is used to connect devices with safety functions, only the devices with 8.2K

constant resistance output (the resistance is inside the device) guarantee the fail-safe category 3.

1st device type:

NO

NC

8,2K

NO

In parallel

(note 1)

(note 2)

In parallel

NC

(note 1)

In series (note 3)

In series

8,2K

In parallel

In series

(note 4) 

Table 1

2nd device

type:

NO

NC

8,2k

NOTE 2

NO

NO

8,2k

NOTE 1

NOTE 3

8,2k

NC

NC

!

Summary of Contents for Mindy A100F

Page 1: ...ra mindy A100F Istruzioni ed avvertenze per l installatore Instructions and warnings for the fitter Instructions et recommandations pour l installateur Anweisungen und Hinweise f r den Installateur In...

Page 2: ...nstallation This brochure which contains important directions regarding system safety should be saved for future reference along with the technical instructions for the automatic system mindy A100F Co...

Page 3: ...the electronic board from accidental contacts see figure 1a The electronic board can be interfered with only in the event of real need in this case proceed as shown in figure 1b 2 Installation Automa...

Page 4: ...s of the Normally Open NA contacts are not used they should be left free If there is more than one NA contact on the same input they must be connected in PARALLEL The contacts must be mechanical and p...

Page 5: ...ax 200mA 12 Phototest Phototest output power supply to photocell transmitters Max 100 mA 13 Common Common for all inputs 14 A C Light 24 Vac output for open gate indicator light Max 2W 15 OPEN limit s...

Page 6: ...nnected to each other in parallel with an 8 2K termination resistance Note 2 The NO and NC combination can be obtained by placing the two contacts in parallel and placing in series to the NC contact a...

Page 7: ...ntrol unit terminals 17 18 Set Dip Switch 10 to ON Phototest enabled in the future it can be disabled at any time by setting Dip Switch no 10 to OFF Pho totest disabled When using 2 pairs of photocell...

Page 8: ...ic movement stops immediately and briefly reverses direction after the device connected to the input is triggered Repeat this test for the closing manoeuvre The OK LED located in the centre of the boa...

Page 9: ...ement stops as soon as the input command stops During an opening manoeuvre movement will stop when the limit switch is trig gered during a closing manoeuvre movement will stop if the Pho tocell or the...

Page 10: ...eached In the Automatic operating mode an opening manoeuvre is followed by a pause after which the gate closes automatically The Always Close function comes into play following a power failure if the...

Page 11: ...imit switch the duration of the deceleration stage will be proportional to the Work ing Time for proper operation of the deceleration feature we recommend the installation of the limit switches During...

Page 12: ...ode Use two motors with the control units connected as indicated in fig 5 Connect the flashing light end the Gate Open Indicator to any one of the two control units setting up the connections as shown...

Page 13: ...he connection of the constant resistance STOP input the manoeuvre is enabled only if there is a voltage of 9 to 11 Vdc corre sponding to a resistance of 6150 to 10250 on terminals 21 22 The gate chang...

Reviews: