10) Disposal

This product is made from various kinds of material, some of which
can be recycled. Make sure you recycle or dispose of the product in
compliance with laws and regulations locally in force.

Some electric components may contain polluting sub-

stances; do not dump them.

!

11) What to do if…

This section will help fitters to solve some of the most common problems that may arise during installation.

No LED is on:

• Check whether the control unit is powered (check mains voltage is present at terminals 1-2 and a voltage of approx. 24Vac at terminals

10-11)

• Check the 2 mains fuses have not blown; if they have, replace them. If the malfunction persists a serious fault has probably occurred and

the control unit should therefore be replaced.

The OK LED flashes regularly but the INPUT LED’s do not reflect the state of the respective inputs

• Carefully check the connections on input terminals 10÷20

Even if a command impulse is sent to the inputs the manouvre does not start

• Check that the LED’s of the “STOP” (FCA + FCC) and “PHOTO” safety device are on and that the relative command LED that is activated

(“STEP-BY-STEP, OPEN or CLOSE”) remains on for the whole duration of the command.

• Check the connection of the constant resistance STOP input; the manoeuvre is enabled only if there is a voltage of 9 to 11 Vdc (corre-

sponding to a resistance of 6150 

to 10250 

) on terminals 21 – 22.

The gate changes direction during a manoeuvre

An inversion is caused by: 
• Photocell triggering; in this case, check the connections of the photocells and check the input LED’s.

12) Technical specifications

Mains power input

: 230 Vac 50/60 Hz

version A100F

120 Vac 50/60 Hz

version A100F/V1

Adjustable force:

: 5 levels 30/45/60/80/100% with selector switch

Motor output

: one 500VA (2.5A) motor or two 250VA (1.25A) motors connected in parallel

Services voltage

: 24 Vac ± 25%

Max current for 24 V services

: 200mA

Phototest output

: 100mA

Sensitive edge input

: 8200 

± 25% to enable the manoeuvre

Flashing light output

: For flashing lights at mains voltage, maximum power 100 W

Courtesy light output

: For flashing lights at mains voltage, maximum power 100 W

“SCA” open gate telltale light output

: For 24 Vac telltale lights, maximum power 2 W

Operating temperature

: -20 ÷ 50 °C

Working Time (sliding mode)

: Adjustable from 2.5 to >40 s, or from <40 to >80 s with TLM

Working Time (overhead garage door mode)

: Adjustable from 2.5 to >20 s, or from <20 to >80 s with TLM

Pause Time (TP)

: Adjustable from 5 to >80 sec.

Dimensions; Weight

: 230 x 180 h100 mm ; 2110 g.

Protection class

: IP 55

Nice S.p.a. reserves the right to modify its products without any notice

Summary of Contents for Mindy A100F

Page 1: ...ra mindy A100F Istruzioni ed avvertenze per l installatore Instructions and warnings for the fitter Instructions et recommandations pour l installateur Anweisungen und Hinweise f r den Installateur In...

Page 2: ...nstallation This brochure which contains important directions regarding system safety should be saved for future reference along with the technical instructions for the automatic system mindy A100F Co...

Page 3: ...the electronic board from accidental contacts see figure 1a The electronic board can be interfered with only in the event of real need in this case proceed as shown in figure 1b 2 Installation Automa...

Page 4: ...s of the Normally Open NA contacts are not used they should be left free If there is more than one NA contact on the same input they must be connected in PARALLEL The contacts must be mechanical and p...

Page 5: ...ax 200mA 12 Phototest Phototest output power supply to photocell transmitters Max 100 mA 13 Common Common for all inputs 14 A C Light 24 Vac output for open gate indicator light Max 2W 15 OPEN limit s...

Page 6: ...nnected to each other in parallel with an 8 2K termination resistance Note 2 The NO and NC combination can be obtained by placing the two contacts in parallel and placing in series to the NC contact a...

Page 7: ...ntrol unit terminals 17 18 Set Dip Switch 10 to ON Phototest enabled in the future it can be disabled at any time by setting Dip Switch no 10 to OFF Pho totest disabled When using 2 pairs of photocell...

Page 8: ...ic movement stops immediately and briefly reverses direction after the device connected to the input is triggered Repeat this test for the closing manoeuvre The OK LED located in the centre of the boa...

Page 9: ...ement stops as soon as the input command stops During an opening manoeuvre movement will stop when the limit switch is trig gered during a closing manoeuvre movement will stop if the Pho tocell or the...

Page 10: ...eached In the Automatic operating mode an opening manoeuvre is followed by a pause after which the gate closes automatically The Always Close function comes into play following a power failure if the...

Page 11: ...imit switch the duration of the deceleration stage will be proportional to the Work ing Time for proper operation of the deceleration feature we recommend the installation of the limit switches During...

Page 12: ...ode Use two motors with the control units connected as indicated in fig 5 Connect the flashing light end the Gate Open Indicator to any one of the two control units setting up the connections as shown...

Page 13: ...he connection of the constant resistance STOP input the manoeuvre is enabled only if there is a voltage of 9 to 11 Vdc corre sponding to a resistance of 6150 to 10250 on terminals 21 22 The gate chang...

Reviews: