background image

10 

– ENGLISH

Table 5

PROGRAMMING POSITIONS

Position

LED

Description

Position 0

(motor 1)

L1

maximum closing position: when the leaf 

relative to motor 1 strikes the closing 

mechanical stop

Position 0

(motor 2)

L2

maximum closing position: when the leaf 

relative to motor 2 strikes the closing 

mechanical stop

Position SA

(motor 2)

L3

Offset on opening: when the leaf associated 

with motor 2 moves beyond this position, leaf 

1 will start to open

Position A

(motor 1)

L4

Desired opening position: position in which 

the leaf associated with motor 1 must stop 

at the end of an opening manoeuvre. This 

position must not necessarily correspond 

to the opening mechanical stop; it can be 

chosen as desired between positions “0” and 

“1”

Position A

(motor 2)

L5

Desired opening position: position in which 

the leaf associated with motor 2 must stop 

at the end of an opening manoeuvre. This 

position must not necessarily correspond 

to the opening mechanical stop; it can be 

chosen as desired between positions “0” and 

“1”

Position SC

(motor 1)

L6

Offset on closing: when leaf 1 is below this 

position, leaf 2 will start to close

Position 1

(motor 1)

L7

Maximum opening position: when the leaf 

relative to motor 1 strikes the opening 

mechanical stop

Position 1

(motor 2)

L8

Maximum opening position: when the leaf 

relative to motor 2 strikes the opening 

mechanical stop

4.8.1 Learning in automatic mode

L3
L4

15

To effect the automatic learning procedure:

1. 

simultaneously press and hold the and 

g

 buttons 

h

2. 

release the buttons when LEDs 

“L3”

 and 

“L4”

 start flashing 

quickly (after roughly 5 seconds)

3. 

check that the automation carries out the following 

manoeuvre sequences:

a.

  slow closing of motor M1 up to the mechanical stop

b.

  slow closing of motor M2 up to the mechanical stop

c.

  slow opening of motor M2 and of motor M1 up to the 

stop

d.

  fast closing of motors M1 and M2.

If  the  first  manoeuvre  (a)  fails  to  close  the  leaf 

controlled by motor M1 but closes the one 

controlled by M2, press 

f

 or 

h

 to 

stop the learning phase. At this point, reverse the 

connections of motors M1 and M2 on the terminals 

on the control unit and those of the respective 

encoders. Then repeat the self-learning procedure.

If the first two manoeuvres (a and b) are not “closing” 

but “opening” manoeuvres, press the 

f

 or 

h

 button to stop the learning phase. At this 

point, invert the control wires (external positions 

with respect to the terminal) on the motor that 

executed the opening manoeuvre and repeat the 

self-learning procedure.

4. 

at the end of the closing manoeuvre (

d

) of the two motors, 

LEDs 

“L3”

 and 

“L4”

 switch off to signal that the procedure 

was performed correctly.

If, during the automatic learning procedure, the 

photocells or one of the devices connected to the 

“stop” input intervene, the procedure interrupts and 

LED L1 starts flashing. In this case, the self-learning 

procedure must be repeated from the beginning.

The automatic learning procedure can be run 

again at any time, even after the installation phase; 

for example, after modifying the position of the 

mechanical stops.

4.8.2 Learning in manual mode

The user has maximum 10 seconds to press 

the buttons consecutively during the learning 

procedure. After this time, the procedure terminates 

automatically and memorises the changes made up 

to that time.

L3
L4

16

When  LEDs  "L1..L8"  flash,  to  shift  between  LEDs 

simply press the 

f

 or 

h

 button briefly 

(the LED will flash to signal the current position).

While LEDs "L1..L8" flash, to move the motor in any 

one direction, it is necessary to press and hold the 

f

 or 

h

 button.

To effect the manual learning procedure:

1. 

simultaneously press and hold the and 

g

 buttons 

h

2. 

release the buttons when LED 

“L1”

  starts  flashing  (after 

roughly 3 sec)

3. 

LED “

L1

” flashes: 

position 0 of M1

 

to command and move motor 1 to 

position “0”

 (“

Figure

 

14

”): press and hold the 

f

 or 

h

 button. 

Once the position is reached, release the button to stop 

the manoeuvre

 

to memorise the position, press and hold the 

g

 

button for at least 3 seconds then release it (after 2 

seconds LED “

L1

” will remain lit and after the 

g

 

button is released, LED “

L2

” will start flashing)

Summary of Contents for MC824HHS

Page 1: ...Nice MC824HHS Control unit EN Instructions and warnings for installation and use...

Page 2: ...care by avoiding crushing impacts falls or contact with liquids of any kind Do not place the product near sources of heat nor expose it to open flames All these actions can damage the product and caus...

Page 3: ...type radio receiver paragraph and an IBT4N type connector which through the IBT4N interface can be used to connect BusT4 devices such as the Oview programmer see the Connecting the IBT4N interface pa...

Page 4: ...ENTIFICATION AND OVERALL DIMENSIONS The overall dimensions and label A that allow for identifying the product are shown in Figure 2 232 mm 310 mm 122 mm A 2 3 4 TYPICAL INSTALLATION Figure 3 shows an...

Page 5: ...ectronic circuits 3 5 INSTALLING THE CONTROL UNIT a Secure the control unit to an unmovable vertical flat surface adequately protected against possible impacts The lower part of the control unit must...

Page 6: ...ositioned in sight of the automation If located in a concealed position it must be equipped with a system that prevents inadvertent or unauthorised reconnection of power to avoid potential hazards 4 2...

Page 7: ...open contacts NC normally closed contacts or devices with 8 2 k fixed resistor output such as sensitive edges can be connected to this input Each device connected to this input will be individually r...

Page 8: ...FOTO PHOTO External photocell h 50 activated during the closing phase stops and reverses the gate s movement FOTO II PHOTO II External photocell h 100 activated during the closing phase stops and reve...

Page 9: ...mode to be assigned to the motor see Table 4 Close Open SbS Stop Bluebus 1 2 3 4 5 6 7 8 9 10 11 12 A 13 m The motor selector must be set before activating the mechanical stop learning function m Any...

Page 10: ...trolled by M2 press f or h to stop the learning phase At this point reverse the connections of motors M1 and M2 on the terminals on the control unit and those of the respective encoders Then repeat th...

Page 11: ...button is released LED L7 will start flashing 9 LED L7 flashes position 1 of M1 to command and move motor 1 to position 1 Figure 14 press and hold the f or h button Once the position is reached relea...

Page 12: ...ether the leaves can be opened and closed with a force below 390 N 3 lock the motors as described in the respective instruction manual 4 using the control devices transmitter control button key select...

Page 13: ...ction short flash OFF long flash ON 5 wait 10 seconds maximum time to exit the programming mode l To set other functions to ON or OFF while the procedure is running repeat points 2 and 3 during the ph...

Page 14: ...10 seconds to press the buttons consecutively during the programming procedure after which time the procedure terminates automatically and memorises the changes made up to then To perform Level 2 pro...

Page 15: ...of the movement namely the opening of the gate leaves instead the Close command does not cause any effect If the sent command remains for more than 2 seconds a Stop command is executed L6 STEP BY STEP...

Page 16: ...nsmitter or key selector etc If everything functions properly the gate will move normally otherwise proceed with point 2 2 within 3 seconds press the control again and hold it down 3 after roughly 2 s...

Page 17: ...e cause and increase the motor force if necessary 4 short red flashes 1 second pause 4 short red flashes Intervention of the STOP input At the start of the manoeuvre or during the movement itself the...

Page 18: ...blown verify the cause and replace it with one having the same characteristics Green LED always on Serious anomaly There is a serious problem try disconnecting the power supply to the control unit an...

Page 19: ...ton to shift flashing of the LED to L8 Anomaly list parameter 4 keep the g button pressed down it must be kept pressed throughout phases 5 and 6 5 wait roughly 3 seconds after which LED L1 correspondi...

Page 20: ...mation Unlock or only from Oview the following commands Unlock and close and Unlock and open 12 Lock automation Triggers the stoppage of the manoeuvre and locks the automation the control unit will no...

Page 21: ...CT MAINTENANCE Being an electronic part the control unit does not require any special maintenance Nonetheless the system should be regularly checked to ensure that it works efficiently at least every...

Page 22: ...command SbS input for normally open contacts the closing of the contact triggers the Step by Step command OPEN input for normally open contacts the closing of the contact triggers the OPEN command CLO...

Page 23: ...according to the requirements envisaged for partly completed machinery Annex II part 1 section B Directive 2006 42 EC of the EUROPEAN PARLIAMENT AND COUNCIL of 17 May 2006 related to machinery and am...

Page 24: ...24 ENGLISH NOTES...

Page 25: ...ystem or the programming and adjustment parameters of the control unit your installer is exclusively responsible for these operations Failure or power outage while waiting for your installer to interv...

Page 26: ...26 ENGLISH NOTES...

Page 27: ...ENGLISH 27 NOTES...

Page 28: ...www niceforyou com Nice SpA Via Callalta 1 31046 Oderzo TV Italy info niceforyou com IDV0779A00EN_27 11 2020...

Reviews: