Protection Settings
Long Time Delay (LTD) protection
26
TemBreak
PRO
P_BE-UM-001-EN V1.3.0
Adjusting I
r
(Current)
The LTD protection trip range is: 1.05...1.20 x I
r
according to standard AS/NZS IEC 60947.2.
The trip threshold tolerance I
r
for the long-time delay protection is +5% to +20%.
The I
r
trip threshold is adjusted using two I
r
dials on the front of the MCCB:
I
r1
–
maximum scale adjustment
I
r2
–
fine adjustment of the maximum scale in increments of 1%
The I
r
threshold is firstly set using the I
r1
dial to set the maximum current range, then, if necessary, from the I
r2
dial further adjustments in fine increments of
1% can be made from OFF to 0.92 x I
r1
dial. Refer to the
Commissioning
–
LTD Adjustments (I
r
,
t
r
)
section for further information on using the I
r1
and I
r2
adjustment dials.
Rating (I
n
)
Dial position
1
2
3
4
5
6
7
8
9
10
40A
I
r1
max 16
I
r1
max 18
I
r1
max 20
I
r1
max 22
I
r1
max 25
I
r1
max 28
I
r1
max 32
I
r1
max 34
I
r1
max 37
I
r1
max 40
14.72...16
16.56...18
18.4...20
20.24...22
23...25
25.76...28
29.44...32
31.28...34
34.04-37
36.8-40
100A
I
r1
max 40
I
r1
max 45
I
r1
max 50
I
r1
max 57
I
r1
max 63
I
r1
max 72
I
r1
max 80
I
r1
max 87
I
r1
max 93
I
r1
max 100
36.8...40
41.4...45
46...50
52.44...57
57.96...63
66.24...72
73.6...80
80.04...87
85.56-93
92-100
160A
I
r1
max 63
I
r1
max 70
I
r1
max 80
I
r1
max 90
I
r1
max 100
I
r1
max 110
I
r1
max 125
I
r1
max 135
I
r1
max 150
I
r1
max 160
58...63
64.4...70
73.6...80
82.8...90
92...100
101.2...110
115...125
124.2...135
138-150
147.2-160
250A
I
r1
max 100
I
r1
max 110
I
r1
max 125
I
r1
max 140
I
r1
max 160
I
r1
max 180
I
r1
max 200
I
r1
max 225
I
r1
max 250
92...100
101.2...110
115...125
128.8...140
147.2...160
165.6...180
184...200
207...225
230-250
400A
I
r1
max 160
I
r1
max 180
I
r1
max 200
I
r1
max 225
I
r1
max 250
I
r1
max 300
I
r1
max 350
I
r1
max 370
I
r1
max 400
147.2...160
165.6...180
184...200
207...225
230...250
276...300
322...350
340.4...370
368-400
630A
I
r1
max 250
I
r1
max 300
I
r1
max 350
I
r1
max 370
I
r1
max 400
I
r1
max 500
I
r1
max 600
I
r1
max 630
230...250
276...300
322...350
340.4...370
368...400
460...500
552...600
579.6...630
I
r1
max scale setting (A)
I
r2
fine adjustment range (A)
WARNING
: Setting I
r2
to OFF will disable both LTD and STD protection modes; therefore, the MCCB will provide
instantaneous protection only.
Summary of Contents for TemBreak PRO P
Page 50: ...50 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex A Dimensions P160 Dimensions...
Page 51: ...Annex A Dimensions 51 TemBreak PRO P_BE UM 001 EN V1 3 0 P250 Dimensions...
Page 52: ...Annex A Dimensions 52 TemBreak PRO P_BE UM 001 EN V1 3 0 P400 Dimensions...
Page 53: ...Annex A Dimensions 53 TemBreak PRO P_BE UM 001 EN V1 3 0 P630 Dimensions...
Page 55: ...55 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex C I2t Let Through Curves P160_BE...
Page 56: ...Annex C I2t Let Through Curves 56 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 57: ...Annex C I2t Let Through Curves 57 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 58: ...Annex C I2t Let Through Curves 58 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 59: ...59 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex D Peak Let Through Curves P160_BE...
Page 60: ...Annex D Peak Let Through Curves 60 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 61: ...Annex D Peak Let Through Curves 61 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 62: ...Annex D Peak Let Through Curves 62 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 65: ...65 TemBreak PRO P_BE UM 001 EN V1 3 0 This page is intentionally left blank...