OCR Power Supply
Power to the P_BE OCR is self-powered whilst sufficient current is flowing through the MCCB, which provides a minimum power supply to operate and
provide alarm and configured protection functions
Minimum conditions for energizing the trip unit without an external power supply:
-
Circuit breaker closed
-
Minimum current through the circuit breaker; below is a table per rating
Trip unit rating
1 Pole fed
2 Poles fed
3 Poles fed
40A
─
> 14A
> 10A
100A
> 25A
> 15A
> 15A
160A
> 32A
> 16A
> 16A
250A
> 50A
> 25A
> 25A
400A
> 80A
> 40A
> 40A
630A
> 126A
> 63A
> 63A
Notice
: 40A trip unit with 1 Pole feed, will still provide INST protection for I > 2x I
n
(>80A).
Summary of Contents for TemBreak PRO P
Page 50: ...50 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex A Dimensions P160 Dimensions...
Page 51: ...Annex A Dimensions 51 TemBreak PRO P_BE UM 001 EN V1 3 0 P250 Dimensions...
Page 52: ...Annex A Dimensions 52 TemBreak PRO P_BE UM 001 EN V1 3 0 P400 Dimensions...
Page 53: ...Annex A Dimensions 53 TemBreak PRO P_BE UM 001 EN V1 3 0 P630 Dimensions...
Page 55: ...55 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex C I2t Let Through Curves P160_BE...
Page 56: ...Annex C I2t Let Through Curves 56 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 57: ...Annex C I2t Let Through Curves 57 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 58: ...Annex C I2t Let Through Curves 58 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 59: ...59 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex D Peak Let Through Curves P160_BE...
Page 60: ...Annex D Peak Let Through Curves 60 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 61: ...Annex D Peak Let Through Curves 61 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 62: ...Annex D Peak Let Through Curves 62 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 65: ...65 TemBreak PRO P_BE UM 001 EN V1 3 0 This page is intentionally left blank...