13
TemBreak
PRO
P_BE-UM-001-EN V1.3.0
Internal Accessories
Internal accessories include Auxiliary and Alarm contacts, Shunt Trip and Undervoltage Trip (UVT) modules, which may be installed under the front cover of
the MCCB in various combinations to provide additional functionality and connection with external control circuits.
Auxiliary & Alarm Switches
Auxiliary Contact
An auxiliary contact can be installed to indicate whether an MCCB is Open (both OFF and Tripped positions) or
Closed (ON). Auxiliary contacts come in either general purpose or micro-switch type, with some combinations pre-
wired or with terminals. Each contact type is provided as a single change-over switching arrangement (1x C/O).
Alarm Contact
An alarm contact can be installed to indicate whether an MCCB is in the Tripped or Not Tripped position (ON, OFF).
Alarm contacts come in either general purpose or micro-switch type, with some combinations pre-wired or with
terminals. Each contact type is provided as a single change-over switching arrangement (1x C/O).
Part Number
Description
Contact Type
Connection Type
T2AX00LML3SWA
Auxiliary
General purpose
Pre-wired
T2AX00LML3STA
Auxiliary
General purpose
Terminal
T2AX00LML3RWA
Auxiliary
Micro-switch
Pre-wired
T2AL00LML3SWA
Alarm; left side only
General purpose
Pre-wired
T2AL00LML3STA
Alarm; left side only
General purpose
Terminal
T2AL00LML3RWA
Alarm; left side only
Micro-switch
Pre-wired
General purpose contact
Micro-switch contact
AC (V)
DC (V)
Minimum Load
DC (V)
Minimum Load
Volts
(V)
Amperes (A)
Volts
(V)
Amperes (A)
Volts
(V)
Amperes (A)
Resistive
Load
Inductive
Load
Resistive
Load
Inductive
Load
Resistive
Load
480
─
─
250
─
─
100 mA @ 15 Vdc
30
0.1
1 mA @ 5 Vdc
250
3
2
125
0.4
0.05
125
3
2
30
3
2
Summary of Contents for TemBreak PRO P
Page 50: ...50 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex A Dimensions P160 Dimensions...
Page 51: ...Annex A Dimensions 51 TemBreak PRO P_BE UM 001 EN V1 3 0 P250 Dimensions...
Page 52: ...Annex A Dimensions 52 TemBreak PRO P_BE UM 001 EN V1 3 0 P400 Dimensions...
Page 53: ...Annex A Dimensions 53 TemBreak PRO P_BE UM 001 EN V1 3 0 P630 Dimensions...
Page 55: ...55 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex C I2t Let Through Curves P160_BE...
Page 56: ...Annex C I2t Let Through Curves 56 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 57: ...Annex C I2t Let Through Curves 57 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 58: ...Annex C I2t Let Through Curves 58 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 59: ...59 TemBreak PRO P_BE UM 001 EN V1 3 0 Annex D Peak Let Through Curves P160_BE...
Page 60: ...Annex D Peak Let Through Curves 60 TemBreak PRO P_BE UM 001 EN V1 3 0 P250_BE...
Page 61: ...Annex D Peak Let Through Curves 61 TemBreak PRO P_BE UM 001 EN V1 3 0 P400_BE...
Page 62: ...Annex D Peak Let Through Curves 62 TemBreak PRO P_BE UM 001 EN V1 3 0 P630_BE...
Page 65: ...65 TemBreak PRO P_BE UM 001 EN V1 3 0 This page is intentionally left blank...