1.2
TRACE
MATE II-CTR
Product Overview
Temperature Range
Range:
-50°C to 500°C, -58°F to 932°F
Hysteresis:
±2°C, ±3.2°F
Absolute Accuracy:
±2.5°C, ±4.5°F
Repeatability:
±1°C, ±1.8°F
RTD:
100 ohm platinum, 3-wire 10 ohms
maximum lead resistance
Heater Switching
Installaton/Overvolatge CAT. III; Pollution Degree 2
Configuration
TM-2SIH1-RTD:
Single-pole
TM-2SIH1-RTD-240V:
Single-pole
TM-2DIH2-RTD-208~240V:
Dual-pole
TM-2SIH1-RTD-277V:
Single-pole
Ratings:
TM-2SIH1-RTD:
120Vac @ 30A
TM-2SIH1-RTD-240V:
240VAC @30A
TM-2DIH2-RTD-208~240V:
208~240VAC @30A
TM-2SIH1-RTD-277V:
277VAC @30A
250 amp 1/2 cycle inrush
Line Frequency
50 or 60Hz
Control Power
Installaton/Overvolatge CAT. III; Pollution Degree 2
Power Requirements
Control power from heater voltage
TM-2SIH1-RTD:
120VAC, 10VA
TM-2SIH1-RTD-240V:
240VAC, 10VA
TM-2DIH2-RTD-208~240V:
208~240VAC, 10VA
TM-2SIH1-RTD-277V:
277VAC, 10VA
Protection
Control power from heater voltage
protected by non-replaceable 2A, time
lag, 350 VAC fuse
MOV transient protection and RC
snubber
User Interface
DIP Switch & Jumper
Change setpoints, Reset alarm, Heater
test
Panel Indicators
Power on, Heater on, Low temperature
alarm, High temperature alarm,
Current fail alarm, Ground fault trip
alarm, RTD fail alarm
LCD Display
A comprehensive display of system
measurements, setpoint values, heater
on/off and alarm status
RS232 Port
Accessible to PDA, Laptop, PC
Environment
Approvals:
CSA and FM
Class I, Div.2, Groups A,B,C,D
Class I, Zone 2, Groups IIC
Operating Range:
TM-2SIH1-RTD:
-40°C to +50°C
TM-2SIH1-RTD-240V:
-40°C to +50°C
TM-2DIH2-RTD-208~240V:
-40°C to +50°C
TM-2SIH1-RTD-277V:
-40°C to +50°C
( LCD display:
-20°C to +50°C )
Heater current derated
Conformal Coating:
Boards conformal coated for hostile
environments. Altitude: 0-2000m
User-Definable Options
Heater Setpoint:
Low Temperature Alarm Setpoint:
High Temperature Alarm Setpoint:
0°C-511°C, 1°C steps
0°F-511°F, 1°F steps
Temperature Units:
0°C or °F
Current Fail Alarm Setpoint:
0.0A-30.0A, 1 A steps
Ground Fault Trip Alarm Setpoint:
0mA-511mA, 1 mA steps
Enclosure
Type:
Nema-4 steel, painted black
Size:
TM-2SIH1-RTD:
10”Hx8”Wx4”D
TM-2SIH1-RTD-240V:
10”Hx8”W x4”D
TM-2DIH2-RTD-208~240V:
10”Hx8”W x4”D
TM-2SIH1-RTD-277V:
10”Hx8”W x4”D
Features:
Quick release latches to open door
One 1.125” conduit knockout for power,
two 0.843” conduit knocks for RTD
wiring, one 0.875” conduit knock for
signal wiring, one 0.610” conduit knock
for RS232 communication.
Alarms
Installaton/Overvolatge CAT. II; Pollution Degree 2
Low Temperature:
Actual temperature < low temperature
alarm setpoint
High Temperature:
Actual temperature > high temperature
alarm setpoint
Current Fail:
Heater current < current fail alarm
setpoint
Ground Fault Trip:
Ground fault current > Ground fault trip
alarm setpoint
RTD Fail:
RTD Open, RTD Short
Hardware:
No incoming voltage
TraceCheck:
Current Fail Alarm
Configurationt:
NC Contacts
Alarm Output Rating:
AC contact: 12-277Vac@ 0.5A max.
50/60 Hz, CAT. II
DC contact: 30Vdc/0.1A, 500mW max.
Form C dry contact: 12- 277VAC/0.5A,
30VDC/0.1A.
Specifications