TRACE

MATE II-CTR

Product Overview

Temperature Range

Range:

-50°C to 500°C, -58°F to 932°F

Hysteresis:

±2°C, ±3.2°F

Absolute Accuracy:

±2.5°C, ±4.5°F

Repeatability:

±1°C, ±1.8°F

RTD:

100 ohm platinum, 3-wire 10 ohms
maximum lead resistance

Heater Switching

Installaton/Overvolatge CAT. III; Pollution Degree 2
Configuration

TM-2SIH1-RTD:

Single-pole

TM-2SIH1-RTD-240V:

Single-pole

TM-2DIH2-RTD-208~240V:

Dual-pole

TM-2SIH1-RTD-277V:

Single-pole

Ratings:

TM-2SIH1-RTD:

120Vac @ 30A

TM-2SIH1-RTD-240V:

240VAC @30A

TM-2DIH2-RTD-208~240V:

208~240VAC @30A

TM-2SIH1-RTD-277V:

277VAC @30A

250 amp 1/2 cycle inrush

Line Frequency

50 or 60Hz

Control Power

Installaton/Overvolatge CAT. III; Pollution Degree 2
Power Requirements

Control power from heater voltage
TM-2SIH1-RTD:

120VAC, 10VA

TM-2SIH1-RTD-240V:

240VAC, 10VA

TM-2DIH2-RTD-208~240V:

208~240VAC, 10VA

TM-2SIH1-RTD-277V:

277VAC, 10VA

Protection

Control power from heater voltage
protected by non-replaceable 2A, time
lag, 350 VAC fuse
MOV transient protection and RC
snubber

User Interface

DIP Switch & Jumper

Change setpoints, Reset alarm, Heater
test

Panel Indicators

Power on, Heater on, Low temperature
alarm, High temperature alarm,
Current fail alarm, Ground fault trip
alarm, RTD fail alarm

LCD Display

A comprehensive display of system
measurements, setpoint values, heater
on/off and alarm status

RS232 Port

Accessible to PDA, Laptop, PC

Environment

Approvals:

CSA and FM
Class I, Div.2, Groups A,B,C,D
Class I, Zone 2, Groups IIC

Operating Range:

TM-2SIH1-RTD:

-40°C to +50°C

TM-2SIH1-RTD-240V:

-40°C to +50°C

TM-2DIH2-RTD-208~240V:

-40°C to +50°C

TM-2SIH1-RTD-277V:

-40°C to +50°C

( LCD display:

-20°C to +50°C )

Heater current derated

Conformal Coating:

Boards conformal coated for hostile
environments. Altitude: 0-2000m

User-Definable Options

Heater Setpoint:
Low Temperature Alarm Setpoint:
High Temperature Alarm Setpoint:

0°C-511°C, 1°C steps
0°F-511°F, 1°F steps

Temperature Units:

0°C or °F

Current Fail Alarm Setpoint:

0.0A-30.0A, 1 A steps

Ground Fault Trip Alarm Setpoint:

0mA-511mA, 1 mA steps

Enclosure

Type:

Nema-4 steel, painted black

Size:

TM-2SIH1-RTD:

10”Hx8”Wx4”D

TM-2SIH1-RTD-240V:

10”Hx8”W x4”D

TM-2DIH2-RTD-208~240V:

10”Hx8”W x4”D

TM-2SIH1-RTD-277V:

10”Hx8”W x4”D

Features:

Quick release latches to open door
One 1.125” conduit knockout for power,
two 0.843” conduit knocks for RTD
wiring, one 0.875” conduit knock for
signal wiring, one 0.610” conduit knock
for RS232 communication.

Alarms

Installaton/Overvolatge CAT. II; Pollution Degree 2
Low Temperature:

Actual temperature < low temperature
alarm setpoint

High Temperature:

Actual temperature > high temperature
alarm setpoint

Current Fail:

Heater current < current fail alarm
setpoint

Ground Fault Trip:

Ground fault current > Ground fault trip
alarm setpoint

RTD Fail:

RTD Open, RTD Short

Hardware:

No incoming voltage

TraceCheck:

Current Fail Alarm

Configurationt:

NC Contacts

Alarm Output Rating:

AC contact: 12-277Vac@ 0.5A max.
50/60 Hz, CAT. II
DC contact: 30Vdc/0.1A, 500mW max.
Form C dry contact: 12- 277VAC/0.5A,
30VDC/0.1A.

Specifications

T race Ma te II-C T R

H ea te r C u rrent R ating

0

5

10

15

20

25

30

35

-10

0

10

20

3 0

40

5 0

Am bien t A ir T em p (°C )

H

eat

er

C

u

rr

e

n

t

(A

m

p

s)

Summary of Contents for TRACEMATE II-CTR

Page 1: ...TRACEMATE II CTR OPERATOR S MANUAL ELECTRONIC THERMOSTAT ...

Page 2: ... 3 Ground Connection 2 3 RTD Sensor Wiring 2 3 Alarm Wiring 2 4 3 Applications 3 1 Mechanical Thermostat Replacement 3 1 Remote Zone Alarm 3 1 Alarm Annunciator 3 1 Local Alarm 3 1 Switching Requirements 3 1 4 Operation 4 1 Alarms 4 1 Alarm Contacts 4 1 Alarm Messages 4 1 Alarm Indicators 4 1 Status Indicators 4 1 Alarm Reset 4 2 Heater Setpoint and Alarm Setpoints 4 2 5 Testing 5 1 Troubleshootin...

Page 3: ...ve alarm package which includes LCD displaymessages and LED indicators for quick fault identification and a ground fault trip to minimize fire hazards Bycombining the control system monitoring and testing requirements of a heat trace control system into a general purpose control the TraceMate II CTR makes it possible to significantly upgrade systems at low installed cost In addition it is very fle...

Page 4: ...ting Range TM 2SIH1 RTD 40 C to 50 C TM 2SIH1 RTD 240V 40 C to 50 C TM 2DIH2 RTD 208 240V 40 C to 50 C TM 2SIH1 RTD 277V 40 C to 50 C LCD display 20 C to 50 C Heater current derated Conformal Coating Boards conformal coated for hostile environments Altitude 0 2000m User Definable Options Heater Setpoint Low Temperature Alarm Setpoint High Temperature Alarm Setpoint 0 C 511 C 1 C steps 0 F 511 F 1 ...

Page 5: ...ber generated by S1 9 is interpreted as high temperature alarm setpoint in C or F for the selected heater GF Setpoint Number generated by S1 9 is interpreted as ground fault trip alarm setpoint in mA for the selected heater AMP Setpoint Number generated by S1 9 is divided by10 and interpreted as current fail alarm setpoint in A for the selected heater SP Setpoint Number generated byS1 9 is interpr...

Page 6: ...aceMate II CTR Controls and Indicators Figure 2 2 Typical Wiring Diagram 30VDC 0 1A 500mW MAX LOCAL ALARM 12 277VAC 0 5A 277VAC MAX 0 1A 30VDC MAX 0 5A 277VAC MAX 0 1A 30VDC MAX GF CT1 AMP CT1 RTD1 GND STUD DC NC ALM AMP CT2 RTD2 NO COM NC HEATER 1 RTD 1 PIPE ...

Page 7: ...e C 6 30 50 8 30 40 10 24 50 12 16 50 The supply voltage must be single pole 120VAC for TM 2SIH1 RTD single pole 240VAC for TM 2SIH1 RTD 240V dual pole 208 240VAC for TM 2DIH2 RTD 208 240V and single pole 277VAC for TM 2SIH1 RTD 277V Wiring methods must conform to Class 1 Division II or Class 1 Zone II requirements Heater Wiring Connect heating cable wiring to terminals 3 4 for heater 1 and 19 20 ...

Page 8: ...on output rated 30Vdc 100mA 500mW max The Form C dry alarm contact is rated 0 5A 277Vac 0 1A30Vdc max These alarm outputs are designed to interface to annunciator panels PLC or DCS Figure 2 5 Enclosure and Mounting Dimensions Warning Explosion Hazard Substitution of components may impair suitability for Class 1 Division 2 or Class 1 Zone 2 Warning Explosion Hazard Do not disconnect equipment unles...

Page 9: ...sonnel can be dispatched to the area The heat trace point with a problem can be identified by the alarm messages on the LCD display For a fast diagnosis and repair the alarm message on the displayand the status LED indicators in the TraceMate II CTR identify the exact nature of the problem This simple connection minimizes control room panel space allowing a few LCD displays and indicators to cover...

Page 10: ... very important that the alarm outputs be used so corrective action can be taken quicklyenough to prevent a process shutdown due to the loss of heat to a pipe Ground fault detection only works with resistance or solidly grounded systems If the system is ungrounded it must be grounded or an artificial ground must be created by means of a zip zag transformer Once a ground fault condition is detected...

Page 11: ...o Figure 2 1 This is useful for checking correct operation of the control If the ground fault alarm light or RTD fail alarm light is on the heater will not switch on even if the actual temperature is below the setpoint Alarm Reset The low high temperature and RTD fail alarms reset as soon as the condition disappears The ground fault trip and current fail alarm are latched alarms A latched alarm wi...

Page 12: ... installed or for periodic maintenance checks system operation can be verified by adjusting the heater setpoint 2 C above and below a known temperature on the RTD input to see if the heater turns on and off For example if the RTD input temperature is 25 C setting the heater setpoint to 27 C will force the heater on and conversely a 23 C setpoint will force the heater off By substituting a known re...

Page 13: ...y the ground fault sensor as a ground fault Size the resistor according to the table to ensure sufficient ground fault current of 30mA 25 Heater Voltage 110 240 277 AC Volts Resistance 2700 6200 6800 Ohms Wattage 5 10 15 Watts Voltage Rating 250 500 500 DC Volts 4 Applypower The ground fault indicator should come on after a short delay It should not be possible to turn on the heater even if the ac...

Page 14: ...OVIDED FOR IN WRITING IN THIS WAR RANTY EACH CONTROL IS PROVIDED WITHOUT ANY WARRANTY OF ANY KIND EITHER EXPRESSED OR IMPLIED IN PARTICULAR WITH OUT LIMITING THE GENERALITY OF THE FOREGOING THE FOLLOW ING IMPLIED WARRANTIES AND CONDITIONS ARE EXPRESSLY DIS CLAIMED a ANY IMPLIED WARRANTY OR CONDITION THAT THE CON TROL WILL MEET YOUR REQUIREMENTS b ANY IMPLIED WARRANTY OR CONDITION THAT THE OP ERATI...