h
Dry out signal
Description
Summary Alarm
Activated when any warning happens
On Battery
Activated when the UPS operates on battery
Battery Low
Activated with the battery low
alarm
UPS ok
Activated when the UPS has no alarms and no
fault.
On Bypass
Activated when the UPS has bypass output.
Dry in signal
Description
Disable
Disable the function.
UPS On
One second pulse activate, if active, the UPS turns
on when UPS is not on inverter. It is the same as a
remote button to control UPS status.
UPS Off
One second pulse activate, if active, the UPS turns
off when UPS is on inverter. It is the same as a
remote button to control UPS status.
Maintain bypass
One second pulse activate, if active, the UPS will
transfer to bypass mode. To recover to normal
status, first make the signal inactive, and then UPS
needs be turned on by manual operation.