the settings. Some settings would change the specification, and some settings
would enable or disable some functions. The unsuitable option set by user
may result in potential failures or protecting function loss, even directly
damage the load, battery or UPS.
The detail description shows in the next table.
Description
Available Settings
Default Setting
User password
<enable><disable>
If enable, you must enter an correct
password.
disable
Audio alarm
<enable><disable>
If disable, all alarm is mute
enable
Output voltage
<208V><220V> <230V> <240V>
230V
Output frequency
<50HZ><60HZ>
< Auto-sensing>
<50HZ>
Power strategy
<normal>
<high efficiency><converter>
Normal
DC start
<enable><disable>
Cold start
enable
Site wiring fault
alarm
<enable><disable>
disable
Ambient
temperature
warning
<enable><disable>
enable
Automatic battery
tests period
<0>…….<31days>
If select 0, Automatic battery test is disable.
7days
Auto restart
<enable><disable>
Enabled means UPS will auto restart to
normal mode while utility recover after the
UPS has been shutdown for battery low.
enable
Automatic
overload restart
<enable><disable>
Enabled means UPS transfer from
bypass mode to normal mode after over
load disappears.(Recover to 70%)
enable
Auto bypass
<enable><disable>
enabled means UPS will have bypass
output when utility power on.
Disabled means UPS will not have bypass
output when power on but could get
bypass output when UPS is fault or
overload.
disable