Connecting the Multiple EXBs in rack form
1. Connect Earth line between UPS and the first EXB, and then connect
Earth Line between the first EXB and the second EXB.
2. Take off the front panel, and connect the battery terminal (A) from
UPS to EXB terminal (B) shown as below. And then connect the
battery terminal (D) from the first EXB to the battery terminal (E) from
the second EXB. User needs to remove the small gate(C) on side of
the front panel to allow the outlet wire of the EXB to pass through the
gate and then reassemble front panel.
Note:
Three or more EXB can be connected to the UPS in the same way
as shown above.
Note:
After connect the EXB, please do not forget to set the number of
EXB on LCD, if use the nonstandard EXB, please call local dealer or
distributor for setting method.
1.2 Operation
★
Do not disconnect the mains cable on the UPS or the building wiring
socket (grounded shockproof socket) during operation as this would
remove the ground to the UPS and of all connected loads.
★
The UPS features its own, internal current source (batteries). You may be
electric shock when you touch the UPS output sockets or output terminal
block even if the UPS is not connected to the building wiring socket.
★
In order to fully disconnect the UPS, first press the OFF button to turn off
the UPS, then disconnect the mains lead.