76
Hot-adding a DS14/DS14mk2 FC/DS14mk4 FC
7
Connect the grounding strap connecting the disk shelf to the other
disk shelves or your storage controller.
8
If the disk shelf...
Then...
Is a DS14
Then go to
Step 9
.
Is a DS14mk2 FC or a
DS14mk4 FC
Set the loop speed:
◆
The 1-Gb loop speed setting must
be used if there is any component
on any part of the loop that is only
capable of 1-Gb operation.
Examples of these components are
LRCs, the FAS270 or the DS14.
◆
The 2-Gb loop speed setting must
be used if there is any component
on any part of the loop that is only
capable of 2-Gb operation.
Examples of these components are
the DS14mk2FC, SFPs, HBAs, or
drives.
◆
For the 4-Gb loop speed setting to
be used, all components on any
part of the loop must be of 4-Gb
capable. Examples of these
components are this disk shelf
model, SFPs, HBAs, or drives.
Caution
An incorrectly set loop speed causes
the storage controller to panic.
9
Connect the two disk shelf power cords of each disk shelf that you
are adding to a power source.
Caution
Do not turn on the power to the disk shelf yet.
Step
Action