Chapter 1: Specifications of the Model 3040 40U Cabinet
3
You can configure the cabinet to meet your data storage needs. Standard cabinet
configurations consist of a combination of these types of trays:
Controller-drive tray – Contains drives, redundant cooling fans and power
supplies, and, depending on the model, one or two controllers.
Drive tray – Contains drives, redundant cooling fans and power supplies, and
one or two environmental services modules (ESMs).
Power
Requirements
and Heat
Dissipation
The cabinet is rated at 200 VAC through 240 VAC at 50 Hz to 60 Hz, and it operates
to ±10 percent of that range. The cabinet contains a power strip that provides 72A of
usable power through six 12A banks of power. This power is provided by 24 ICE320
power outlets on each PDU.
For the 72A power strips, power cord C1 supplies power to the bottom eight outlets,
power cord C2 supplies power to the middle eight outlets, and power cord C3 supplies
power to the top eight outlets. Each PDU is clearly labelled C1, C2, or C3 where the
power cords connect. Each power outlet is rated at 10A maximum. A 15A circuit
breaker protects each of the six 12A banks. Each circuit breaker is labeled on each
PDU.
Table 1 Power Calculations and Heat Calculations for the Cabinet
Component
kVA
Watts
Btu/Hr
Cabinet PDU (72A PDUs)
14.4
14400
49176
Cabinet PDU/12A bank (72A PDUs)
2.40*
2400*
8196*
E2612 controller-drive tray
0.400
399
1366
E2624 controller-drive tray
0.331
329.6
1127.1
E2660 controller-drive tray
1.268
1222
4180
E5412 controller-drive tray
0.589
589
2016
E5424 controller-drive tray
0.567
567
1935
E5460 controller-drive tray
1.246
1204
4119
E5512 controller-drive tray (200 VAC typical)
.668
662
2262
E5512 controller-drive tray
(200 VAC maximum)
.674
670
2293
E5524 controller-drive tray (200 VAC typical)
.495
483
1653
E5524 controller-drive tray
(200 VAC maximum)
.561
554
1896
E5560 controller-drive tray (200 VAC typical)
1.146
1097
3751
E5560 controller-drive tray
(200 VAC maximum)
1.191
1179
4032
Summary of Contents for E-Series 3040 40U