NESS - M1 Installation and Programming Manual
Page 6
+
+SAUX
NEG
+VAUX
NEG
+VAUX
NEG
+VAUX
NEG
AC/DC
NORMAL
ZONE 16
JP1
SW1
JUMPER TO START
WITH NO AC
POWER
TELCO SEIZED
AC/DC
Z9
NEG
Z10
Z11
NEG
Z13
NEG
Z15
Z14
Z12
NEG
Z16
Z2
Z3
NEG
Z5
NEG
Z7
Z6
Z4
NEG
Z8
Aux12VDC Power Outputs protected by
1.25A PTC NOTE:Maximum continuous current
drain from +VAUX,+VKP and J16 combined
must not exceed 900 mA or 2.5 Amps in alarm.
Test battery regularly with
ELK-BLT Battery Life Tester.
Replace every 3-5 years
DIALER ACTIVE
SMOKE
2WIRE
STATUS
REVERSE
BAT LEADS
+
-
12V Battery
5 to 18Ah
7
N.C.
N.O.
ZONE
2200
Ohm
EOL
8
N.C.
N.O.
ZONE
2200
Ohm
EOL
5
N.C.
N.O.
ZONE
2200
Ohm
EOL
6
N.C.
N.O.
ZONE
2200
Ohm
EOL
3
N.C.
N.O.
ZONE
2200
Ohm
EOL
4
N.C.
N.O.
ZONE
2200
Ohm
EOL
1
N.C.
N.O.
ZONE
2200
Ohm
EOL
2
N.C.
N.O.
ZONE
2200
Ohm
EOL
Sealed
Lead Acid
Control requires AC power to start. However, for testing purposes it can
be started from battery ONLY by momentarily shorting these two pads.
NEG
Z1
15
N.C.
N.O.
ZONE
2200
Ohm
EOL
16
N.C.
N.O.
ZONE
2200
Ohm
EOL
13
N.C.
N.O.
ZONE
2200
Ohm
EOL
14
N.C.
N.O.
ZONE
2200
Ohm
EOL
11
N.C.
N.O.
ZONE
2200
Ohm
EOL
12
N.C.
N.O.
ZONE
2200
Ohm
EOL
9
N.C.
N.O.
ZONE
2200
Ohm
EOL
10
N.C.
N.O.
ZONE
2200
Ohm
EOL
Master Power Switch (SW1) , disconnects AC and Battery power from control
This unit provides Residential fire alarm service when installed according to ANSI/
NFPA 72-1993. This unit provides Grade A Residential Burglar alarm service. In
conjunction with the enclosure, this unit also provides the following Commercial
Burglar alarm service: Grade A Local, Police Connect with Basic Line Security, and
Grades B & C Central Station. Transmission of the fire alarm signal to a fire alarm
headquarters or central station shall be permitted only with the approval of the authority
having jurisdiction. The burglar alarm signal shall not be transmitted to a police
emergency number, equipment is to be installed in accordance with NFPA
(985,55.1.P)
2-Wire
Smoke Detector
680
Ohm
EOL
+
-
Dialer/Modem is idle. If ON, Dialer/Modem is in use (communicating).
1 blink with equal On and Off times is Normal. 2 fast blinks = Control running on
bootloader only. 4 fast blinks = Control is re-initializing it's EEPROM memory after
a firmware flash. 5 fast blinks = Memory/Operation overflow
Battery is connected correctly. If ON, check battery lead connections.
AC Voltage is present and power switch is turned ON. If OFF, check AC power.
Phone line is good and house phones are connected. If ON constantly, the phone
line may be bad. During remote mode this LED will be ON since the house phones
are then disconnected from the outside line & are being powered from control.
TELCO
SEIZED
DIALER
ACTIVE
OFF
OFF
LEDS
Indicators
Power
Regular 1
sec. Blink
ON
Battery
Reversed
OFF
Status
4-Wire
Smoke Detector
2200
Ohm
EOL
To Zone Input
N.O. Alarm
Contacts
+
-
+
-
Zone 16 can be configured as a 2-wire smoke zone.
Set JP1 to "2 WIRE SMOKE" and use 680 Ohm EOL
resistor, part # ELK-ER680
Use Only Compatible Detectors:
System Sensor: 1151, 2100, 2100T, 2151
GE: 429AT, 521BXT, 521B.
Hochiki America: SLK-835.
Detection Systems: DS250, DS250TH, DS282,
DS282TH, DS282THS, DS282THC.
Maximum Number = 20 Do not mix models.
Sw12 VDC Output
protected by 1.1A PTC.
BATTERY
To Zone NEG
(Left Side Terminals)
2-Wire Smoke Circuit
NEG
Z16
Normal
State
Descriptions
2200 Ohm
EOL Resistors are
part # ELK-ER2200
All circuits are current limited except telephone line and Battery leads.
Testing of this system should be performed regularly.
Control panel specifications are subject to change without
notice.
Wiring & Hookup Diagram
2200 (2k2) Ohm
EOL Resisters are
Ness part # 605-
222
16.5 V
17VDC 3A power
supply. Non-polarity