NESS - M1 Installation and Programming Manual
Page 42
Z001: Sel
Prg
[Name of Zone]
Z001:A=00 R=00
Byp=00 Tbl=00
Menu 10 - Zone Reporting Codes
10-Zone Reportng
Codes
Zone Report Codes
Description of Option
Each of the 208 Zones has specific communicator reporting codes for Alarm, Restore,
Bypass, and Trouble. Using the up/down arrow keys, select the appropriate zone, then
press the right arrow key to begin programming of that zone.
The cursor starts at the 00 beside A (Alarm). Enter the desired two digit reporting code
and press the right arrow key to advance to the R (Restore). To jump the cursor to another
report without changing this one simply press the right arrow key. The next press of the
right arrow key after Tbl (Trouble) will advance the screen back to the beginning of that
zone. Range is 00 to FF. Default for all entries is 00 (no report).
NOTE: Each reporting code must be programmed according to the desired reporting
format. However, for SIA and Contact ID formats the actual reporting digits will be
produced by the control according to the type of alarm or event. The only programming
required to enable reporting with the SIA and Contact ID formats is to set the programmed
code to a non zero (0) value. See below:
Press RIGHT arrow key to select this menu. Press UP or DOWN arrow keys to select
another menu. The ELK key backs up one menu level. To exit press the * or Exit key.
NOTE: Enter a two digit value to enable a report code. To disable a report code enter 00. When SIA or Contact ID is the
reporting format, the two digit value can simply be 01 since the control automatically produces the correct code
according to the SIA or Contact ID protocol. For 4+2 pulse format, enter a value from 01 to FF. To enter the A thru F
HEX characters press the RIGHT arrow key to position the cursor under the desired digit, then press the UP arrow (shift)
key once. Each press of the 2 key will now produce the following: 2, A, B, C. Each press of the 3 key will now produce
the following: 3, D, E, F. Press the RIGHT arrow key to cancel shift and move to the next character. See Appendix for
a summary of the SIA and Contact ID codes.
Alarms Restore
Bypass Trouble
Zone RCs
CID SIA CID SIA CID SIA CID SIA
01 = Burglar Entry/Exit 1 1134 BA 3134 B R 1573 BB 1370 BT
02 = Burglar Entry/Exit 2 1134 BA 3134 B R 1573 BB 1370 BT
03 = Burglar Perim Inst
1131 BA 3131 B R 1573 BB 1370 BT
04 = Burglar Interior
1132 BA 3132 B R 1573 BB 1370 BT
05 = Burglar Int Follower 1132 BA 3132 B R 1573 BB 1370 BT
06 = Burglar Int Night
1135 BA 3135 B R 1573 BB 1370 BT
07 = Burglar Int Nt Fllwr
1135 BA 3135 B R 1573 BB 1370 BT
08 = Burglar 24 Hour
1133 BA 3133 B R 1573 BB 1370 BT
09 = Burglar Box Tamper 1137 TA 3137 T R 1573 TB 1370 BT
10 = Fire Alarm
1110 FA 3110 F R 1571 FB 1373 FT
11 = Fire Verified
1110 FA 3110 F R 1571 FB 1373 FT
12 = Fire Supervisory
1200 FS 3200 F R 1571 FB 1373 FT
13 = Aux Function 1
1150 UA 3150 U R 1572 UB ---- ----
14 = Aux Function 2
1150 UA 3150 U R 1572 UB ---- ----
15 = Aux Function 3
1150 UA 3150 U R 1572 UB ---- ----
16 = Aux Function 4
1150 UA 3150 U R 1572 UB ---- ----
17 = Carbon Monoxide
1162 GA 3162 G R 1572 GB ---- ----
18 = Gen Pur. Do Nothing ---- ---- ---- ---- ---- ---- ---- ----
Based on the zone definition, the CID (Contact ID) or SIA formats for Zone Reporting Codes will be:
Alarms Restore
Bypass Trouble
Zone RCs
CID SIA CID SIA CID SIA CID SIA
19 = Emergency Alarm
1101 QA 3101 Q R 1572 QB ---- ----
20 = Freeze Alarm
1159 ZA 3159 Z R 1572 ZB ---- ----
21 = Gas Alarm
1151 GA 3151 G R 1572 GB ---- ----
22 = Heat Alarm
1114 KA 3114 K R 1572 KB ---- ----
23 = Medical Alarm
1100 MA 3100 M R 1572 MB ---- ----
24 = Police Alarm
1120 P A 3120 P R 1572 PB ---- ----
25 = Police No Indication 1120 P A 3120 P R 1572 PB ---- ----
26 = Water Alarm
1154 WA 3154 WR 1572 WB ---- ----
27 = Key Mom Arm/Disarm ---- ---- ---- ---- ---- ---- ---- ----
28 = Key Mom Arm Away ---- ---- ---- ---- ---- ---- ---- ----
29 = Key Mom Arm Stay
---- ---- ---- ---- ---- ---- ---- ----
30 = Key Mom Disarm
---- ---- ---- ---- ---- ---- ---- ----
31 = Key On/Off
---- ---- ---- ---- ---- ---- ---- ----
32 = Mute Audibles
---- ---- ---- ---- ---- ---- ---- ----
33 = Analog Zone
---- ---- ---- ---- ---- ---- ---- ----
34 = Power Supervisory 1338 YT ---- ---- ---- ---- 1342 YP
35 = Phone Key
---- ---- ---- ---- ---- ---- ---- ----