background image

DE DIETRICH THERMIQUE
57, rue de la Gare F- 67580 MERTZWILLER - BP 30

DE DIETRICH THERMIQUE SAS

FRANCE

NEUBERG S.A.

LU

DE DIETRICH SERVICE

AT

DE DIETRICH 

CN

www .dedietrich-thermique.fr

www .neuberg.lu
www .dedietrich-heating .com

www .dedietrich-heating .com

www .dedietrich-heiztechnik.com

SERVICE CONSOMMATEURS

0 825 120 520

 

0,15 

 / min

03 88 80 27 00

03 88 80 27 99

+352 (0)2 401 401

0800 / 20 1608  freecall

+86 (0)106 581 4017
+86 (0)106 581 4018
+86 (0)106 581 7056

+86 (0)106 581 4019

[email protected]

Direction des Ventes France

57, rue de la Gar e - F-67580 Mertzwiller

VAN MARCKE

BE

www .vanma rcke.be

+32 (0)56/23 7 5 11

Weggevoerdenlaan 5
B- 8500 KORTRIJK

39 rue Jacques Stas - B.P.12

L- 2549 LUXEMBOU RG

Room 512, Tower A, Kelun Building

12A Guanghua Rd, Chaoyang District 

C-100020 BEIJING

DE DIETRICH REMEHA 

GMBH

DE

www .remeha .de

[email protected]

+49 (0)25 7 2 / 9 161-0

+49 (0)25 7 2 / 9 161-102

Rheiner Strasse 151

D-48282 EMSDETTEN

DE DIETRICH THERMIQUE

 

I

beria S.L.U

ES

www .dedietrich-calefaccion .es

+34 935 4 75 850

[email protected]

C/Salv ador Espriu, 11

08908 L’HOSPITALET de LLO BREGAT

CZ

www .dedietrich.cz

+420 271 001 627

[email protected]

WALTER MEIER K

lima 

S

chweiz AG

CH

www .w altermeier .com

+41 (0) 44 806 4 1 41

+41 (0) 44 806 4 1 00

[email protected]

Bahnstrasse 24 - CH -8603 SCHWE RZENBACH

Serviceline

+41 (0)8 00 846 846

WALTER MEIER C

limat 

S

uisse SA

CH

www .w altermeier .com

+41 (0) 21 943 02 22

+41 (0) 21 943 02 33

[email protected]

Z.I de la Veyre B, St-Légier

CH-1800 VEVEY 1

Jeseniova 2770/5 6  - 1 30 00 Praha 3

Serviceline

+41 (0)8 00 846 846

000 «БДP T

 P

yc

»

RU

www .dedietrich.ru

8 800 333-17-18

[email protected]

129164

, Россия, г. Москва

Зубарев переулок, д. 

15/1

Бизнес-центр «Чайка Плаза»,офис 

309

DUEDI S.

r

.

l

IT

www .duediclima .it

+39 0171 857170

+39 0171 687875

[email protected]

Distributor

e Uffi ciale Esclusiv

o

De Dietrich-Thermique Italia Via Passatore, 12 

12010 San Defendente di Cervasca CUNEO

MW

-8

0

0

0

0

0

5

-1

0

BDR THERMEA

 

C

zech 

R

epublic s.r.o

7628792 - v03 - 25072017

7628792-001-03

Summary of Contents for EcoNox EF 22

Page 1: ...EASYLIFE SUSTAINABLE COMFORT Neovo MW 8000039 3 Jordan Lebanon Syria en User Guide Oil Gas fired boiler NeOvo EcoNox EF 22 EF 29...

Page 2: ...sing the product and keep it in a safe place for later reference In order to ensure continued safe and efficient operation we recommend that the product is serviced regularly Our service and customer...

Page 3: ...Control 16 5 1 Browsing in the menus 16 5 2 Start up 16 5 3 Shutdown 16 5 3 1 Switching off the heating 16 5 3 2 Stopping domestic hot water production 17 5 3 3 Shutting down the installation 17 5 4...

Page 4: ...the hydraulic pressure 34 9 2 2 Topping up the installation with water 34 9 3 Venting the installation 35 10 Troubleshooting 36 10 1 Error messages B Control 36 10 1 1 Error code display 36 10 1 2 Fau...

Page 5: ...permitted to in stall the boiler in accordance with prevailing local and national regulations Important Allow the space required to correctly install the boiler Refer to the Overall space needed for t...

Page 6: ...urer its after sales service or per sons with similar qualifications in order to obviate any danger Important The installation must comply on all points with prevailing regulations and directives whic...

Page 7: ...thers etc that govern works and interventions in individual homes blocks of flats or other buildings Note Keep the boiler accessible at all times Caution Install the boiler in a frost free environment...

Page 8: ...may not be invoked in the following cases Failure to abide by the instructions on installing the appliance Failure to abide by the instructions on using the appli ance Faulty or insufficient maintenan...

Page 9: ...uals provided with the appliance Call on a qualified professional to carry out installation and initial commissioning Get your installer to explain your installation to you Have the required inspectio...

Page 10: ...ersonal in jury Caution Risk of material damage Important Please note important information See Reference to other manuals or pages in this manual 2 1 2 Symbols used on the appliance 1 Alternating cur...

Page 11: ...etroleum products Fatty Acid Methyl Esters used as heating fuel 3 2 Technical data Important Technical parameters obtained in association with the RDB 2 2 burner Tab 2 Technical parameters for boiler...

Page 12: ...y consumption QHE GJ 74 100 Sound power level indoors LWA dB Emissions of nitrogen oxides NOX mg kWh 116 116 1 Low temperature means for condensing boilers 30 C for low temperature boilers 37 C and fo...

Page 13: ...2 Main components 4 2 1 Boiler 1 Control panel 2 On Off switch 3 Data plate 4 3 Description of the control panel B Control 4 3 1 Description of the keys Heating temperature setting button Level acces...

Page 14: ...ed Domestic hot water function disabled Menu display Information menu displays the measured values and the statuses of the appliance User menu provides access to the User level setting parameters Inst...

Page 15: ...ogram for Wednesday Timer program for Thursday Timer program for Friday Timer program for Saturday Timer program for Sunday CLOCK sub menu CLK Temperature sensors Outside temperature sensor connected...

Page 16: ...y reverts to the main display 5 2 Start up If the boiler was powered off 1 Check that the heating system and the boiler are adequately primed with water Recommended pressure 0 15 MPa 1 5 bar 2 Check t...

Page 17: ...a qualified profes sional if the home is left empty for a long period of time and there is a chance of frost Important To prevent the radiators and the installation from freezing in pla ces where tha...

Page 18: ...menu access the next sub menu access the next parameter increase the value Press the key to access the previous menu access the previous sub menu access the previous parameter decrease the value Pres...

Page 19: ...ting a PCB 1 Access the menus by pressing the two keys on the right simultane ously 2 Access the PCB selection menu only when several PCBs are present Important The PCB selection menu is available onl...

Page 20: ...as been shut down Note Press the key to restart the appliance the screen will display 5 Confirm by pressing the key 6 Go back to the main display by pressing the h key Note The display disappears afte...

Page 21: ...nly protects the boiler not the heating system Caution Have the boiler and heating system drained by a qualified profes sional if the home is left empty for a long period of time and there is a chance...

Page 22: ...Setting the parameters 7 2 1 Setting the heating water temperature No temperature sensor connected Outside temperature sensor con nected Set the heating water temperature setpoint Set the required roo...

Page 23: ...y turning the set ting button 2 Go back to the main display by pressing the key for two seconds Note After five seconds without pressing any keys on the control panel the display goes back to the main...

Page 24: ...perature set point for the heated zone if no outside temperature sensor has been connected For the CU OH04 PCB Can be set from 7 to 90 C For the SCB 04B PCB Can be set from 7 to 100 C 75 C 50 C CP080...

Page 25: ...setting not available 10 C CP510 Circuit temporary room temperature set point Can be set from 5 to 30 C 20 C 20 C CP540 Temperature set point for SWIMMING POOL mode Can be set from 0 to 39 C not avail...

Page 26: ...eration off on 1 not available AP073 SUMMER WINTER set point switch Can be set from 15 to 30 C set to 30 5 C function deactivated 22 C only accessible to the installer AP074 SUMMER override off on 0 0...

Page 27: ...of reversal valve cycles X DC003 Number of hours reversal valve operation hours X DC004 Number of burner start ups in domestic hot water production mode X DC005 Number of hours of burner operation in...

Page 28: ...g the h key For more information see Browsing in the menus page 18 Selecting a PCB page 19 8 2 2 Setting the heating Caution Altering the factory settings may impair operation of the appliance Note Th...

Page 29: ...rature set point by pressing the key Go back to the main display by pressing the h key 8 2 4 Setting the timer programming 1 Access the COUNTERS TIME PROG CLOCK menus Important The COUNTERS TIME PROG...

Page 30: ...ion by pressing the key 8 Select the status that correspond to the period by pressing the or keys Status to for periods to Description comfort mode reduced mode 9 Confirm the selection by pressing the...

Page 31: ...he parameter available in the User menu 8 2 6 Reading out measured values The measured values are available in the Information menu of the dif ferent PCBs Certain parameters are displayed according to...

Page 32: ...CM060 Pump speed X CM120 Circuit operating mode AUTO manual frost protection temporary X X CM130 Current activity status frost protection reduced comfort anti legionella X X CM190 Desired room tempera...

Page 33: ...nal set point limited internal set point normal output check temperature stabilisation time burner shutdown burner off closure of the shut off damper closure of the flue damper end of heat demand boil...

Page 34: ...1 Check the hydraulic pressure in the installation Caution If the hydraulic pressure is lower than 0 08 MPa 0 8 bar more water should be added Top up the water level in the heating in stallation to re...

Page 35: ...enting valve with the bleed key keeping a cloth pressed against the vent 8 Wait until water comes out of the venting valve and then close the venting valve Warning The central heating water may still...

Page 36: ...he appliance s functions and thus eradicates the fault If several faults occur they are displayed one after the other 1 Reset the control panel by pressing the key for 3 seconds when an error message...

Page 37: ...r key When this menu opens the row of the error in the log appears briefly The PCB name appears Go back to the error list by pressing the h key Note The errors are stored from the most recent to the o...

Page 38: ...Do not hang curtains in front of the radiators Install reflective panels behind the radiators to prevent heat losses Insulate the pipes in rooms that are not heated cellars and lofts Close the radiato...

Page 39: ...liable for material damage intangible los ses or physical injury resulting from an installation that does not comply with Legal or regulatory requirements or provisions laid down by the local au thor...

Page 40: ...12 Warranty 40 EF 7628792 v03 25072017...

Page 41: ...12 Warranty 7628792 v03 25072017 EF 41...

Page 42: ...12 Warranty 42 EF 7628792 v03 25072017...

Page 43: ...nological information contained in these technical instructions as well as any drawings and technical de scriptions supplied remain our property and shall not be multiplied without our prior consent i...

Page 44: ...5 72 9161 102 Rheiner Str asse 151 D 48282 EMSDETTEN DE DIETRICH THERMIQUE Iberia S L U ES www dedietrich calefaccion es 34 935 4 75 850 info dedietrich calefaccion es C Salvador Espriu 11 08908 L HOS...

Reviews: