NELSON
™
HEAT TRACING SYSTEMS
INSTALLATION
PLT-BC
STANDARD POWER CONNECTION KIT
INSTRUCTIONS
POWER CONNECTION
Ground Wire
Terminal Block
Ground Braid
Power Termination
TERMINAL BLOCK CONNECTION
Ground
Power Leads
Braid
Heater Cable
*Conduit & Drain; not included in kit
(must be positioned lower than the junction box)
Note: This detail shows Overjacket “J” or “JT” Products only. For Braided “CB” Product, see diagram
on sheet 1.
Place gasket on box adapter.
Position junction box on box adapter and secure it with the conduit locknut.
Connect bus wires, power wires and ground braid to the terminal block. See diagram above.
For Overjacket “J” or “JT” Products only:
Apply silicone at point braid leaves the overjacket
Push all wires, cable and terminal block inside junction box.
Place the box cover and box cover gasket onto the junction box.
Fill-in the voltage, catalog number & wattage blocks on the label with the actual field installed data.
Nelson Heat Tracing Systems products are supplied with a limited warranty. Complete Terms and Conditions may be found on Nelson's
website at
P.O. BOX 726 TULSA, OK 74101 TEL 918-627-5530 FAX 918-641-7336 www.nelsonheaters.com
GA-1859 Rev. 6
Sheet 8 of 8
October 2006